4-3. Self-Diagnostics Table (Wall Mounted Type)

INDOOR UNIT

(1) OPERATION lamp

(2) TIMER lamp

(3) QUIET lamp

ION lamp

OPERATION button

REMOTE CONTROL receiver

Since the indications cover various units, the corresponding parts listed below may not be present in some models.

Indication on indoor unit

.... OFF

 

 

.... Blinking

.... ON (Illuminated)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quiet

Timer

Operation

Code

Diagnostics items

 

 

 

 

 

Diagnostics contents

 

(3)

(2)

(1)

 

 

 

 

 

 

 

 

 

S01

Room temperature sensor failure

(1)

Sensor open circuit or short circuit

 

 

 

 

 

 

 

 

 

 

(2)

Contact failure at connector or open circuit at terminal crimping location

 

 

 

S02

Indoor heat exchanger sensor failure

 

 

 

 

(short-circuit detection only for the humidity sensor)

 

 

 

 

 

 

 

 

(3)

Indoor/outdoor PCboard failure

 

 

 

 

 

 

 

 

S03

Humidity sensor failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S04

Compressor temperature sensor failure

(1)

Sensor open circuit or short circuit

 

 

 

 

 

 

 

 

 

 

(2)

Contact failure at connector or open circuit at terminal crimping location

 

 

 

S05

Outdoor heat exchanger sensor failure

 

 

 

(3)

Outdoor PCboard failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S06

Outdoor air temperature sensor failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S07

Outdoor electrical current detection

Outdoor PCboard failure

 

 

 

 

 

 

 

 

 

 

failure

 

 

 

 

 

 

 

 

 

 

 

Indoor/outdoor communications failure

(1)

Mis-wiring

(2) AC power failure

(3) Blown fuse

(4) Power Relay failure

 

 

 

E01

(5)

Indoor or outdoor PCboard failure

(6) Outdoor Fan Motor failure (7) Reactor failure

 

 

 

(serial communications)

(8)

High-Pressure Switch failure

(9) Overload Relay failure

(10) Magnetic Coil failure

 

 

 

 

 

* See detailed flowchart in this section.

 

 

 

 

 

 

 

E02

• HIC circuit failure

(1)

HIC or power Tr failure (2) Outdoor fan does not turn.

(3) Instantaneous power outage

 

 

 

(4)

Service valve not opened.

(5) Outdoor fan blocked.

(6) Continuous overload operation

 

 

 

• Power Tr (transistor) circuit failure

 

 

 

 

 

(7)

Compressor failure

(8) Outdoor PCboard failure

 

 

 

 

 

 

 

E03

Outdoor unit external ROM (OTP data)

(1)

External ROM data failure

 

(2) Outdoor PCboard failure

 

 

 

 

failure

 

 

 

 

 

E04

Peak current cut-off

(1)

Instantaneous power outage

(2) HIC or power transistor failure

 

 

 

(3)

Outdoor PCboard failure

 

 

 

 

 

 

 

 

 

 

E05

PAM circuit failure

(1)

Outdoor PCboard failure

(2) Outdoor power supply voltage failure

 

 

 

Active circuit failure

 

 

 

E06

Compressor discharge overheat

(1) Electric expansion valve failure

(2) Capillaries choked

(3) Shortage of refrigerant

 

 

 

prevention activated.

(4) Continuous overload operation

(5) Outdoor fan does not rotate

(6) Outdoor PCboard failure

 

 

 

E07

Indoor fan operating failure

(1)

Fan motor failure

(2) Contact failure at connector

 

(3) Indoor PCboard failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E08

4-way valve switching failure

(1)

4-way valve failure (heat pump model only)

 

 

 

 

 

 

 

Indoor zero-cross failure

(2)

Outdoor PCboard failure

 

 

 

 

 

 

 

 

 

 

E09

No-refrigerant protection

(1)

Service valve not opened.

 

(2) Shortage of refrigerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E10

DC compressor drive circuit failure

(1)

Open phase

(2) Outdoor PCboard failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E11

Outdoor fan operating failure

(1)

Fan motor failure

(2) Contact failure at connector

 

(3) Outdoor PCboard failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor system communications failure

(1)

Mis-wiring

(2) Blown fuse

(3) Power Relay failure

 

(4) Outdoor PCboard failure

 

 

 

E12

OLR operation

(5)

Compressor failure

 

 

 

 

 

 

 

 

 

 

 

Outdoor power supply open phase

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor coil freezing

* See detailed flowchart in this section.

 

 

 

 

 

 

 

E13

Freeze-prevention operation activated.

(1)

Indoor fan system failure

(2) Shortage of refrigerant

(3) Low-temperature operation

8

Image 8
Contents Model No Product Code No 852 353Please Read Before Starting Table of Contents Specifications Type Indoor Unit Model No Ceiling Cassette TypeWall Mounted Type SELF-DIAGNOSTICS Timer lamp High Power lamp Remote Control receiver Code Diagnostics itemsOperation button Operation lampSelf-Diagnostics Table Wall Mounted Type OI-852-6-4181-139-00-0 Mode D’EMPLOI STK-RCS-7TWSUAContents Alert SymbolsInstallation Location Safety InstructionsSymbols FeaturesRemote Control Unit Display Remote Control Unit Mode selector button HR. Timer button 1-HOUR OFF TimerTimer Select button ON/OFF operation buttonOperation with the Remote Control Unit Automatic Operation Only for COOL/DRY/HEAT ModelCooling and DRY Mode Heating Mode Only for COOL/DRY/HEAT ModelSpecial Remarks Automatic fan speedSetting the Timer Using the 1-HOUR OFF Timer Adjusting the Airflow DirectionAppendix B Installation Instructions STK-RCS-7TWSUA Installation location Switching the room temperature sensorSanyo Commercial Solutions Sanyo Canada IncInstalling with in-wall junction box Installing directly onto the wallHow to wire the remote controller How to Test Run the Air Conditioner Appendix C Parts included in the package 7000 BTU, 9000 BTU, and 12000 BTU inverter modelsRefer to the Installation Instructions BTU and 24000 BTU inverter models Operation lamp Timer lamp Quiet lamp ION lamp