3. Notes

3.2 Your record of values

RWF40

Setpoint

Your

Configuration level items ( Sec 6.4 )

 

 

 

 

 

 

 

 

 

Man. Ref.

Display

Setting

 

Range

 

Factory

 

 

Sec 8.1

C111

 

Analog input 1, 2 and 3;D2 setpoint changeover / shift

 

 

N /A

 

9030

 

 

Sec 8.1 / 8.2

C112

 

Limit comparator; controller type; setpoint 1; locking

 

 

N /A

 

0010

 

 

Sec 8.1

C113

 

Unit address; decimal place / unit, signal for out-of-range

 

 

N /A

 

0110

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.1

SCL

 

SCale Low, analog input 1, measured value range

 

-1999 to +9999

 

0

 

 

Sec 8.3.2

SCH

 

SCale High, analog input 1, measured value range

 

-1999

to +9999

 

100

 

 

Sec 8.3.3

SCL2

 

SCale Low, analog input 2, measured value range

 

-1999

to +9999

 

0

 

 

Sec 8.3.4

SCH2

 

SCale High, analog input 2, measured value range

 

-1999

to +9999

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.5

SPL

 

Set Point Low limit

 

-1999

to +9999

 

0

 

 

Sec 8.3.6

SPH

 

Set Point High limit

 

-1999

to +9999

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.7

OFF1

 

OFFset analog input 1, Actual value correction

 

-1999

to +9999

 

0

 

 

Sec 8.3.8

OFF2

 

OFFset analog input 2, Actual value correction

 

-1999

to +9999

 

0

 

 

Sec 8.3.9

OFF3

 

OFFset analog input 3, Actual value correction

 

-1999

to +9999

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.10

dF1

 

digital Filter, analog input 1, 2nd order, in seconds

 

0

to

100

 

1

 

 

 

Setpoint

Your

 

 

 

 

 

 

 

 

 

 

 

 

Display

Setting

Configuration level items, Modbus option (only RWF40.0X2B97) ( Sec 6.4 )

 

 

 

 

 

 

 

 

 

 

Range

 

Factory

 

 

Sec 8.3.11

dF3

 

Filter time constant, digital Filter, analog input 3 weather-dependent setpoint shift

 

0

to

1440

 

1278

 

 

Sec 8.3.12

oLLo

 

Working range, Limit Lower

-

1999 to +9999

 

-1999

 

 

Sec 8.3.13

oLHi

 

Working range, Limit High

-

1999 to +9999

 

9999

 

 

Sec 8.3.14

Dtt

 

Bus watchDog timer (in seconds)

 

0 to 7200

 

30

 

 

 

Setpoint

Your

Parameter level items ( Sec 6.3 )

 

 

 

 

 

 

 

 

 

 

 

Display

Setting

 

 

Range

 

Factory

 

 

Sec 7 / 8.2

AL

 

Alarm value for K6 Limit comparator (alarm programmable relay)

 

-1999

to +9999

 

0

 

 

Sec 7 / 8.2

HYSt

 

Hysteresis, (switching differential) for K6 limit comparator

 

0

to

999.9

 

1

 

 

Sec 7 / 8.2

Pb.1

 

Proportional band 1 (affects P-responseof controller)

 

0.1

to

999.9

 

10

 

 

Sec 7 / 8.2

dt

 

derivative time (in seconds) (affects D-responseof controller)

 

0

to

9999

 

80

 

 

Sec 7 / 8.2

rt

 

Integral action time (in seconds) , (affects I-responseof controller)

 

0

to

 

9999

 

350

 

 

Sec 7 / 8.2

db *

 

dead band, contact spacing, * visible when C112 is xxx0, 3-pos modulating

 

0

to 999.9

 

1

 

 

Sec 7 / 8.2

tt *

 

Actuator running time (in seconds) , * visible when C112 is xxx0, 3-pos modulating

 

10

to

3000

 

15

 

 

Sec 7 / 5.51

HYS1

 

Switch-on threshold, HYSteresis 1, 2-stage burner

 

0 to

-199.9

 

-5

 

 

Sec 7 / 5.2

HYS2

 

Switch-off threshold, HYSteresis 2, 2-stage burner

 

0

to HYS3

 

3

 

 

Sec 7 / 5.2

HYS3

 

Switch-off threshold, HYSteresis 3, upper

 

0

to

999.9

 

5

 

 

Sec 7 / 5.6

q

 

Response threshold (Q)

 

0

to

999.9

 

0

 

 

Sec 7 / 5.51

H

 

Heating curve slope

 

0

to 4

 

1

 

 

Sec 7 / 5.5

P

 

Parallel displacement (weather dependent setpoint shift)

 

-90

to

+90

 

0

 

 

 

Setpoint

Your

User level items ( Sec 6.2.1 )

 

 

 

 

 

 

 

 

 

 

 

Display

Setting

 

 

Range

 

Factory

 

 

Sec 6.2.1

SP1

 

Set Point 1

 

SPL to SPH

 

0

 

 

Sec 6.2.1

SP2

 

Set Point 2, digital input 2, D2=0

 

 

SPL to SPH

 

0

 

 

Sec 6.2.1

dSP

 

digital Set Point shift, digital input 2, D2=1

 

 

SPL to SPH

 

0

 

 

Sec 11.1.3

tA

 

temperature, Ambient (outside) analog input 3, visible when C111 is xx1x, xx2x, xx3x

 

 

 

 

 

 

 

--

 

 

Sec 11.1.2

SP.E

 

Set Point External, predefinition, analog input 2, visible when C111 is xx1x, xx2x, xx3x

 

 

SPL to SPH

 

--

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13/16

CC1B-Hints-en Preliminary

04.02.2003

HVAC Products

Image 14
Contents RWF40 04.02.2003This page is intentionally left blank… Contents Getting started with the RWF40 menu How to configure your RWF40 How to adjust parameters Parameter level items summaryHow to change a setpoint You can Decrease Increase Value By pressingManual operation How to display the software version and unitsConfigure Codes \ Units summary Modulating burner, Modulating output Manual operation …Modulating burner, 3-Position output To exit manual operationTechnical Explanation Auto-tune self-setting functionProcedure ConditionsSetting up a standard temperature application Analog input Std Signal 0-1VDC None D2 function Setting up a standard pressure applicationUsing a QBE sensor Siemens QBE620-P10 P10 is 150PSI SetPoint High Limits high setpoint to 205 F12/16 CC1B-Hints-en Preliminary 04.02.2003 Your record of values Range14/16 CC1B-Hints-en Preliminary 04.02.2003 Hvac Products