Siemens RWF40 manual Auto-tune self-setting function, Technical Explanation, Conditions, Procedure

Page 10

2. Hints

2.7 Auto-tune (self-setting function)

RWF40 user manual section 6.2.4 and 9.1

The RWF40 User manual refers to a self-setting-function

that for the purposes of this manual will be refered to as Auto-tune’.

Technical Explanation

Auto-tuneis a self-setting software function, that is integrated into the RWF40 controller, and can be repeated as often as desired.

Auto-tunetests the reaction, in the modulating mode of operation, of the process-control loop, to steps in the actuator position, according to a special procedure.

The data, during the forced oscillations, is then recorded, and used to calculate new values, that are optimized for your specific controlled system.

Auto-tune items summary:

Items at the user level that will affect Auto tune

SP 1 Set Point 1

HYS1 Switch-on threshold, HYSteresis 1

HYS3 Switch-off threshold, HYSteresis 3,

Items at the Parameter level that Auto-tunewill adjust

 

Pb.1

Proportional band 1

(Factory setting

10)

dt

derivative time

(Factory setting

80)

rt

Integral action time

(Factory setting

350)

Item at the configuration level that Auto-tunewill adjust

dF1 Time constant for digital Filter, analog 1

Values for Pb.1, dt, rt and dF1, can always be changed.

Auto-tune uses two different methods to force oscillations, and will automatically select and use, a method, based on, at the start of Auto-tune, what the difference is,

between the setpoint (w), and the process value.

When Auto-tuneis started with a large difference, (typically before the process-control loop has stabilized) Auto-tuneperforms a forced oscillation around a switching level.

When Auto-tune is started with a small difference, (typically after the process-control loop has stabilized)

Auto-tuneperforms a forced oscillation, around the setpoint (w).

If for any reason the controller exceeds the switch off threshold (HYS3) Auto-tunewill be cancelled.

Conditions

The controller must be :

-in the modulating output mode (D1 is open and the step icon is off)

-burner is released (green LED above is on, relay 1, is activated, contact between terminals Q14 and Q13 is closed)

-controller is not in manual mode (red LED above is off)

Procedure

Start Auto-tuneby pressing and release.

The current temperature value, (175) is shown in the actual value display.

The current function item (tunE) is flashing in the setpoint display.

You can cancel Auto-tunewhile it is flashing

pressing and releasing.

When tunE stops flashing on it’s own

Auto-tuneis complete.

You can save the new values for Pb.1, dt, rt and dF1, by pressing , and holding for at least 2 seconds.

Possible results,and their correction. A favorable value for dt is rt/4.

Block diagram of Auto-tune.

8/16

CC1B-Hints-en Preliminary

04.02.2003

HVAC Products

Image 10
Contents RWF40 04.02.2003This page is intentionally left blank… Contents Getting started with the RWF40 menu How to configure your RWF40 How to adjust parameters Parameter level items summaryHow to change a setpoint You can Decrease Increase Value By pressingConfigure Codes \ Units summary How to display the software version and unitsManual operation Modulating burner, Modulating output Manual operation …Modulating burner, 3-Position output To exit manual operationTechnical Explanation Auto-tune self-setting functionProcedure ConditionsSetting up a standard temperature application Analog input Std Signal 0-1VDC None D2 function Setting up a standard pressure applicationUsing a QBE sensor Siemens QBE620-P10 P10 is 150PSI SetPoint High Limits high setpoint to 205 F12/16 CC1B-Hints-en Preliminary 04.02.2003 Your record of values Range14/16 CC1B-Hints-en Preliminary 04.02.2003 Hvac Products