Siemens RWF40 Manual operation …, Modulating burner, 3-Position output, To exit manual operation

Page 9

2. Hints

2.6 Manual operation continued…

Modulating burner, 3-Position output

Press and hold for 5 seconds, and release.

The red LED above the manual icon turns on to indicate that the controller is now in the manual mode.

Relay 2 and relay 3 will hold their current state, (energized or de-energized) that they were in until another key is pressed.

Modulating burner, Modulating output

Press and hold for 5 seconds, and release.

The red LED above the manual icon turns on to indicate that the controller is now in the manual mode.

Relay 2 and relay 3 will hold their current state, (energized or de-energized) that they were in until another key is pressed.

By design, the 0 output starts driving the modulating device to low fire, but if you promptly press the after the red LED above the hand icon turns on, you can prevent the from going all the way.

When the is pressed: -Relay 3 is energized -Decrease icon turns on

-N.O. contact Q-Y2 closes, to drive the modulating device down, which decreases the firing rate

of the burner.

When the is pressed: -Relay 2 is energized -Increase icon turns on

-N.O. contact Q-Y1 closes, to drive the modulating device up, which increases the firing rate of the burner.

When the is released: -Relay 3 is de-energized-Decrease icon turns off

-N.O. contact Q-Y2 opens, to hold the modulating device where it is, which holds the

firing rate

of the burner.

When the is released: -Relay 2 is de-energized-Increase icon turns off

-N.O. contact Q-Y1 opens, to hold the modulating device where it is, which holds the firing rate of the burner.

When the

When the

is pressed,

is released,

the output value

output value,

starts increasing,

stops increasing,

and the output,

and the output,

to terminals

to terminals

X1+ and X1-

X1+ and X1- also

starts increasing,

stops increasing,

the same amount,

and holds

and increases

the current

the firing rate

firing rate

of the burner.

of the burner.

When the

When the

is pressed,

is released,

the output value

output value,

starts decreasing,

stops decreasing,

and the output,

and the output,

to terminals

to terminals

X1+ and X1-

X1+ and X1- also

starts decreasing,

stops decreasing,

the same amount,

and holds

and decreases

the current

the firing rate

firing rate

of the burner.

of the burner.

To exit manual operation

Press for 5 seconds, and release.

The red LED above the hand symbol turns off, and the controller returns to the automatic mode.

On Modulating burners, with modulating output, the output to terminals X1 and X2,

also returns to automatic operation.

On Modulating burners, with 3-position output, the output to relay 2 and relay 3,

also returns to automatic operation.

7/16

CC1B-Hints-en Preliminary

04.02.2003

HVAC Products

Image 9
Contents 04.02.2003 RWF40This page is intentionally left blank… Contents Getting started with the RWF40 menu How to configure your RWF40 Parameter level items summary How to adjust parametersYou can Decrease Increase Value By pressing How to change a setpointHow to display the software version and units Configure Codes \ Units summaryManual operation Modulating burner, 3-Position output Manual operation …Modulating burner, Modulating output To exit manual operationProcedure Auto-tune self-setting functionTechnical Explanation ConditionsSetting up a standard temperature application Using a QBE sensor Siemens QBE620-P10 P10 is 150PSI Setting up a standard pressure applicationAnalog input Std Signal 0-1VDC None D2 function SetPoint High Limits high setpoint to 205 F12/16 CC1B-Hints-en Preliminary 04.02.2003 Range Your record of values14/16 CC1B-Hints-en Preliminary 04.02.2003 Hvac Products