2. Hints

2.4 How to change a setpoint

(SP1, SP2, or dSP)

RWF40 user manual Section 6.2

Shown at the right is the basic display.

The current configuration of your specific controller will determine which levels you will be allowed to access.

C112 must be xxx2, xxx1, or xxx0 to access the parameter level.

The C112 locking code can only be adjusted by the manufacturer.

From the basic display, you may skip the user level, to reach the parameter level.

Press and hold, for 3 seconds, and release.

The actual value display, (0) shows the current parameter value.

The setpoint display, (AL)

shows the parameter item you are adjusting.

Parameter level items summary:

AL

Alarm Limit value for comparator

HYSt

Switching differential, Hysteresis for limit comparator

Pb.1

Proportional band 1

dt

derivative time

rt

Integral action time

db

* dead band, contact spacing

tt* Actuator running time

HYS1 Switch-on threshold, HYSteresis 1, 2-stage burner HYS2 Switch-off threshold, HYSteresis 2, 2-stage burner HYS3 Switch-off threshold, HYSteresis 3, upper

qResponse threshold

HHeating curve slope

PParallel displacement

* items are only displayed when controller is configured for 3-pos output.

Example Adjust the value for parameter AL.

If no keys are pressed for 30 seconds, at anytime, the controller will automatically return to the basic display.

The current value of AL, (0)

is shown in the actual value display.

The current parameter item (AL) is shown in the setpoint display.

The display is steady, (nothing is flashing) and the value for AL can now be adjusted.

You can

You can

decrease

increase

the value

the value

by pressing

by pressing

and

and

releasing it.

releasing it.

You can

Or, you can

accept the

advance to

change by

the next

waiting 2

parameter

seconds.

by pressing

 

once

The red

and releasing it.

LED’s will

 

blink once,

HYSt can be

and become

adjusted the

the new

same way you

value.

just did AL

Your options at this point are:

Press and release, to immediately return to the basic display.

Press and release it,

to advance down to Pb.1, (the next parameter).

… after the last parameter item P,

press and release it,

to advance down to SP1, (the 1st user item).

… after the last user item,

the menu cycles back to the 1st user item.

Or simply wait 30 seconds and the controller will automatically return to the basic display.

5/16

CC1B-Hints-en Preliminary

04.02.2003

HVAC Products

Image 7
Contents 04.02.2003 RWF40This page is intentionally left blank… Contents Getting started with the RWF40 menu How to configure your RWF40 Parameter level items summary How to adjust parametersYou can Decrease Increase Value By pressing How to change a setpointConfigure Codes \ Units summary How to display the software version and unitsManual operation To exit manual operation Manual operation …Modulating burner, 3-Position output Modulating burner, Modulating outputConditions Auto-tune self-setting functionProcedure Technical ExplanationSetting up a standard temperature application SetPoint High Limits high setpoint to 205 F Setting up a standard pressure applicationUsing a QBE sensor Siemens QBE620-P10 P10 is 150PSI Analog input Std Signal 0-1VDC None D2 function12/16 CC1B-Hints-en Preliminary 04.02.2003 Range Your record of values14/16 CC1B-Hints-en Preliminary 04.02.2003 Hvac Products