Siemens manual Getting started with the RWF40 menu

Page 4

2. Hints

2.1 Getting started with the RWF40 menu

The RWF40 menu system has three Levels, beyond the Basic Display, the User Level,

the Parameter Level and

the Configuration Level.

RWF40 user manual Section 6 Operation.

2.1.1 Start with the Basic Display

Shown at the right is the basic display.

The upper, larger, 4 digit red LEDs, (180)

will be referred to as, the ‘Actual value display’.

The lower, smaller, 4 digit green LEDs, (180) will be referred to as, the ‘Setpoint display’.

The current configuration of your specific controller will determine which levels you will be allowed to access.

C112 must be xxx0 to access the configuration level.

The C112 locking code can only be adjusted by the manufacturer.

All controllers will return to the basic display automatically, if no key is pressed for 30 seconds.

The RWF40 configuration codes

(C111, C112, and C113) are all four digits.

The x’s used in the explanations in this manual represent a ‘don’t care’ digit in the code,

so, xxx0 could mean 1000, 2100, 5430, etc,

and we are only concerned with the ‘non-x’ digits.

C112 code summary :

C112 code

xxx0

Locks nothing

C112 code

xxx1

Locks the Configuration Level

C112 code

xxx2

Locks the Parameter Level

C112 code

xxx3

Locks all levels and keys

2.1.2 User Level

From the basic display,

you may advance to the user level, by pressing and releasing it.

The actual value display, (180)

shows the setpoint you are adjusting or viewing.

The setpoint display, (SP 1)

shows the parameter you are adjusting or viewing.

You can adjust the values, within limits, for SP1, SP2, dSP, view tA, SP.E, depending on your specific configuration.

To adjust user level values, please see the “4 How to change a setpoint “,

or RWF40 user manual Section 6.2.1.

2.1.3 Parameter Level

From the user level you may advance to the parameter level,

by pressing and holding, for 3 seconds, and then releasing it.

C112 must be xxx0 or xxx1, to access this level.

The actual value display, (0)

shows the parameter ’s actual value.

The setpoint display, (AL)

shows the parameter you are adjusting or viewing.

You can adjust the values for AL, Hyst, Pb.1, dt, rt, HYS.1, HYS.2, HYS.3, q, H, and P, depending on your specific configuration.

To adjust parameter values, please see “3 How to adjust parameters “,

or RWF40 user manual Section 7.

2.1.4 Configuration Level

From the parameter level you may advance to the configuration level,

by pressing and holding, again for 3 seconds, and then releasing it.

C112 must be xxx0 to access this level.

The actual value display, (9030)

shows the configuration item’s actual value.

The setpoint display, (C111)

shows the configuration item you are adjusting.

You can adjust the values, within limits, for C111, C112, C113, SCL, SCH, SCL2, SCH2, SPL, SPH, OFF1, OFF2, OFF3, and dF1 depending on your specific configuration.

To adjust configuration values, please see the “2 How to configure our RWF40 “,

or RWF40 user manual Section 8.

Return to the Basic Display

You may exit any level, and return to the basic display at any time, in two ways.

First, to exit immediately, press and release it.

The second way is to simply wait 30 seconds, and the controller will automatically return to the basic display.

2/16

CC1B-Hints-en Preliminary

04.02.2003

HVAC Products

Image 4
Contents RWF40 04.02.2003This page is intentionally left blank… Contents Getting started with the RWF40 menu How to configure your RWF40 How to adjust parameters Parameter level items summaryHow to change a setpoint You can Decrease Increase Value By pressingConfigure Codes \ Units summary How to display the software version and unitsManual operation Manual operation … Modulating burner, 3-Position outputModulating burner, Modulating output To exit manual operationAuto-tune self-setting function ProcedureTechnical Explanation ConditionsSetting up a standard temperature application Setting up a standard pressure application Using a QBE sensor Siemens QBE620-P10 P10 is 150PSIAnalog input Std Signal 0-1VDC None D2 function SetPoint High Limits high setpoint to 205 F12/16 CC1B-Hints-en Preliminary 04.02.2003 Your record of values Range14/16 CC1B-Hints-en Preliminary 04.02.2003 Hvac Products