FIGURE 17
INSTALLING FLASHING AND
STORM COLLAR
Remove the nails from the shingles above and to the sides of the chimney. Place the fl ashing over the chimney pipe and slide under- neath the sides and upper edge of the shingles. Ensure that the chim- ney pipe is properly centered within the fl ashing, giving a 3/4" margin all around. Fasten to the roof on the top and sides. DO NOT NAIL through the lower portion of the fl ashing. Make
13
IF THE CHIMNEY IS
UNLINED:
A stainless steel liner listed to either
S t a n d a r d U L C - S640M,
structure must be supported by angle iron anchored into the masonry walls. Figures 19 & 20. The allowable masonry used in chimney construction is
In no case is the masonry enclosure to be supported by the
FIGURE 18
ANCHOR PLATE
FIREPLACE TOP
FIGURE 21
FLUE TILE SUPPORT FOR A MASONRY FIREPLACE
CONNECTION TO A MASONRY
CHIMNEY
Model
IF THE CHIMNEY IS LINED, the flues must be made of vitrifi ed clay and be in sizes of 8" square, 8" x 12", or 8" round with a minimum height of 11 feet above the fireplace. 8" round fl ues are recommended. Installation must conform to both national and local code requirements.
FIGURE 19
HI-TEMP GASKET
FIREPLACE TOP
FIGURE 22
For a masonry fi replace use a fl ue tile support. For a