29. Wire Distance Chart
To meet NEC compliance (North America), the largest PV array that can be connected to the FLEXmax 80 must have a rated
1.5% maximum voltage drop. Temperature and conduit fill corrections may be required. Using a higher voltage PV array with a low voltage battery system allows you to use a much smaller wire size or go up to 5 times as far with the same gauge wire.
(The figures below assumes 2 conductor copper wire and allows for a 1.5% voltage drop)
12V PV ARRAY (16v Vmp)
WIRE GAUGE | #8 | #6 | #4 | #3 | #2 | #1/0 | #2/0 | #4/0 | ||
AMPS | 10 | 15 | 24 | 39 | 49 | 62 | 98 | 124 | 197 | |
20 | 8 | 12 | 19 | 24 | 31 | 49 | 62 | 99 | ||
| ||||||||||
| 30 | 5 | 8 | 13 | 16 | 21 | 33 | 41 | 66 | |
| 40 | 4 | 6 | 10 | 12 | 15 | 25 | 31 | 49 | |
| 50 | 3 | 5 | 8 | 10 | 12 | 20 | 25 | 39 | |
| 60 | 3 | 4 | 6 | 8 | 10 | 16 | 21 | 33 | |
| 70 | 2 | 3 | 6 | 7 | 9 | 14 | 18 | 28 |
24V PV ARRAY (32v Vmp)
WIRE GAUGE | #8 | #6 | #4 | #3 | #2 | #1/0 | #2/0 | #4/0 | ||
AMPS | 10 | 31 | 49 | 78 | 98 | 124 | 197 | 248 | 395 | |
20 | 15 | 24 | 39 | 49 | 62 | 98 | 124 | 197 | ||
| ||||||||||
| 30 | 10 | 16 | 26 | 33 | 41 | 66 | 83 | 132 | |
| 40 | 8 | 12 | 19 | 24 | 31 | 49 | 62 | 99 | |
| 50 | 6 | 10 | 16 | 20 | 25 | 39 | 50 | 79 | |
| 60 | 5 | 8 | 13 | 16 | 21 | 33 | 41 | 66 | |
| 70 | 4 | 7 | 11 | 14 | 18 | 28 | 35 | 56 |
METRIC #8…8.37mm2 #6…13.30mm2 #4…21.15mm2 #3…26.7mm2 #2…33.6mm2 #1/0…53.5mm2 #2/0…67.4mm2 #4/0…107mm2
36V PV ARRAY (48v Vmp)
WIRE GAUGE | #8 | #6 | #4 | #3 | |
AMPS | 10 | 46 | 73 | 117 | 147 |
20 | 23 | 37 | 58 | 73 | |
| 30 | 15 | 24 | 39 | 49 |
| 40 | 12 | 18 | 29 | 37 |
| 50 | 9 | 15 | 23 | 29 |
| 60 | 8 | 12 | 19 | 24 |
| 70 | 7 | 10 | 17 | 21 |
#2 | #1/0 | #2/0 | #4/0 |
186 | 295 | 372 | 592 |
93 | 148 | 186 | 296 |
62 | 98 | 124 | 197 |
46 | 74 | 93 | 148 |
37 | 59 | 74 | 118 |
31 | 49 | 62 | 99 |
27 | 42 | 53 | 85 |