Power Requirements
Table 3 Power Requirements
Unit/Component |
|
| Requirements |
| |
|
|
|
|
| |
| Domestic |
| International | ||
|
|
| |||
AC Power | 250 VAC, 30 A | 230 VAC, 32 A | |||
|
|
| |||
AC Plug | NEMA | IEC 309 locking plug | |||
|
|
| |||
Receptacle | IEC 309 receptacle | ||||
|
|
|
|
|
|
Circuit Breaker |
|
| 20 A |
| |
|
|
|
|
| |
Voltage Range |
|
| 180 to 257 VAC |
| |
|
|
|
|
| |
Frequency |
|
| 49 to 50.5 Hz or 59 to 60.6 Hz |
| |
|
|
|
|
|
|
Current |
|
| 220 VAC, 50/60 Hz |
| |
(specified frequency) |
|
|
| ||
|
|
|
|
| |
|
|
|
|
| |
|
| Configuration A1 | Configuration B1 | Configuration C1 | |
Operational Current | LP Drives2 |
| 7.35 A | 14.70 A | 13.16 A |
HH Drives2 |
| 7.70 A | 15.40 A | 13.72 A | |
|
| ||||
Surge Current | LP Drives |
| 10.95 A | 21.90 A | 22.20 A |
|
|
|
|
| |
HH Drives |
| 11.45 A | 22.90 A | 23.00 A | |
|
| ||||
|
|
|
|
|
|
1Power specifications for three configurations containing
Configuration B contains 2 command modules and 10 drive modules Configuration C contains 3 command modules and 8 drive modules
2LP drives are 1.0 inch tall; HH drives are 1.6 inches tall.
10 |
|