. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
AC Power Distribution
The 72-inch cabinet has two identical AC power boxes (Figure 5). Depending on the configuration ordered, each box supports either domestic or international units and includes the following features:
•One domestic plug (NEMA L6-30P, 30 A, 220 VAC) or one international plug (IEC 309, 30 A, 3-pin, 230 VAC)
•One circuit breaker (20 A)
•Two power outlets (IEC 320, 16 A, C-19, filtered individually for international and domestic EMC compliance)
•Support for up to 12 attachments per box (24 per cabinet) using two, ladder-attach cables (see "Power Box Cables" on page 12)
Figure 5 72-Inch Cabinet AC Distribution
72-Inch Cabinet Site Preparation and Installation Guide | 11 |