LSI AA1167-E1 manual AC Power Distribution, Inch Cabinet AC Distribution

Page 19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements

AC Power Distribution

The 72-inch cabinet has two identical AC power boxes (Figure 5). Depending on the configuration ordered, each box supports either domestic or international units and includes the following features:

One domestic plug (NEMA L6-30P, 30 A, 220 VAC) or one international plug (IEC 309, 30 A, 3-pin, 230 VAC)

One circuit breaker (20 A)

Two power outlets (IEC 320, 16 A, C-19, filtered individually for international and domestic EMC compliance)

Support for up to 12 attachments per box (24 per cabinet) using two, ladder-attach cables (see "Power Box Cables" on page 12)

Figure 5 72-Inch Cabinet AC Distribution

72-Inch Cabinet Site Preparation and Installation Guide

11

Image 19
Contents Inch Cabinet Trademark Acknowledgments Inch Cabinet Site Preparation and Installation Guide Revision Record Date Affected Pages/Remarks Contents List of Figures List of Tables Inch Cabinet Site Preparation and Installation Guide Customer Responsibilities About this Site Preparation GuidePopulated Cabinet Cabinet FeaturesCabinet Features Reference Documentation Cabinet Features Dimensions Dimensions and WeightsUnit WeightsCabinet Area Requirements Area RequirementsEnvironment Requirements Environmental RequirementsUnit/Component Requirements Power Requirements72-Inch Cabinet AC Distribution AC Power DistributionLadder-Attach Cable for a 72-Inch Cabinet Power Box CablesAC Power Cords and Receptacles Power Cords and ReceptaclesSite Wiring and Power Considerations Tools and Equipment Installation InstructionsUnpacking and Moving the Cabinet Installation Instructions Inch Cabinet Site Preparation and Installation Guide Cabinet without Stability Foot Cabinet with Stability Foot Installing the Cabinet Transportation Instructions Inch Cabinet Site Preparation and Installation Guide