Haier AU282XHERA, AU342XHERA installation manual Refrigerant piping work

Page 12

Refrigerant piping work

1. Selection of pipe

To this unit, both liquid and gas pipes shall be insulated as they become low temperature in operation. Use optional parts for piping set or pipes covered with equivalent insulation material.

Liquid pipe

6.35mm ( 1/4'' ) x 0.8mm

 

 

Gas pipe

9.52mm ( 3/8'' ) x 0.8mm

 

 

2. Connection of pipe

Apply refrigerant oil on half union and flare nut.

To bend a pipe, give the roundness as large as possible not to crush the pipe.

Connecting the pipe of gas side firstly makes working easier.

Half union

 

 

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spanner

Torque wrench

Forced fastening without careful centering may damage the threads and cause a leakage of gas.

Pipe Diameter ( )

Fastening Torque

 

 

Liquid Side 6.35mm (1/4'')

18N.m

 

 

Gas Side 9.52mm (3/8'')

50N.m

 

 

3. Attaching Drain-Elbow

If the drain-elbow is used, please attach it as figure.

10

Image 12
Contents Outdoor Unit Installation Manual Contents Disposal of the old air conditioner Specifications Safety precautions Installation accessories Choose the installation placeInstallation dimensionsmm Installation drawings of indoor and outdoor units Matching of the indoor and outdoor units For AU342XHERA Power source Limitations on the installationDescriptions Standard Maximum Refrigerant piping work Too outside Way valve Valve rod cap Service port cap Purging method to use vacuum pumpWiring work Correct Pressing Wrong Pressing Terminal Block ClampsWiring work Indoor unit a Test running Items to confirmFailure State Trouble Possible Reasons Code Haier Group