FAILURE | STATE OF | TROUBLE | POSSIBLE REASONS | |
CODE | LED | SHOOTING | ||
| ||||
1 |
| Faulty defrost sensor Te | Sensor disconnected, or broken, or short circuit | |
2 |
| Faulty sensor Tao | Sensor disconnected, or broken, or short circuit | |
3 |
| Faulty sensor Ts | Sensor disconnected, or broken, or short circuit | |
4 |
| Faulty sensor Td | Sensor disconnected, or broken, or short circuit | |
|
|
| Over current of the system, or broken of the current | |
5 |
| Input overcurrent | sensor,or malfunction with indoor or outdoor fan | |
|
|
| motors, or faulty PCB. | |
|
| Abnormal communication Wrong connection, or the wires be disconnected, or | ||
6 |
| between indoor and outdoor | wrong address setting of indoor units, or faulty | |
|
| units | PCB, or faulty power supply | |
|
|
| High pressure switch is disconnected, or high | |
|
| System high pressure | pressure switch worked, or Tc too high and faulty | |
9 |
| outdoor fan motor when cooling, or faulty indoor | ||
| protection | |||
|
| fan motors when heating, or refrigerant | ||
|
|
| ||
|
|
| overabundance | |
|
|
| Low pressure switch is disconnected, or low | |
10 |
| System low pressure | pressure switch worked, or Te too low and faulty | |
| protection | outdoor fan motors when heating, or faulty indoor | ||
|
| |||
|
|
| fan motor when cooling, or refrigerant shortage | |
|
|
| IPM over current, or short circuit, or IPM | |
11 |
| IPM protection | temperature too high, or IPM input voltage too | |
|
|
| low,or faulty SPDU(or ISPM). | |
12 |
| EEPROM fault | Faulty outdoor unit PCB | |
|
| Over hot protection of | Serious lack of refrigerant of the system, or the | |
13 |
| ambient temperature too high, or PMVs be | ||
| compressor | |||
|
| blocked | ||
|
|
| ||
14 |
| Over hot protection of SPDU Ambient tempreatrue too high, or outdoor fan be | ||
| (or ISPM) | blocked, or bad air circulation of outdoor unit | ||
|
| |||
15 |
| DC fan motor fault | Fan is blocked, or the terminal is disconnected | |
| from the PCB | |||
|
|
| ||
16 |
| Faulty | Coil of | |
| switching on | outdoor PCB | ||
|
| |||
17 |
| Faulty sensor Tc | Sensor disconnected, or broken, or short circuit | |
21 |
| Faulty sensor Toci | Sensor disconnected, or broken, or short circuit | |
23 |
| Low voltage protection | VDC<194V, too low voltage from power source | |
24 |
| High voltage protection | VDC>400V, too high voltage from power source | |
25 |
| Abnormal communication | Communication cables broken, or not be well | |
| between main PCB and | connected, or faulty main PCB, or faulty SPDU(or | ||
|
| SPDU(or ISPM) | ISPM) | |
26 |
| Compressor be locked | Faulty compressor or SPDU(or ISPM) | |
27 |
| Compressor vibration too big Faulty compressor | ||
28 |
| Compressor lose position | Faulty SPDU(or ISPM) | |
29 |
| Faulty compressor start | Faulty compressor or SPDU(or ISPM) | |
30 |
| Faulty position checking | Faulty SPDU(or ISPM) | |
31 |
| circuit | Faulty compressor or SPDU(or ISPM) | |
| Compressor broken |
Take off the plastic cover on the right side of the unit, you can find the LEDs near the communication terminal. Symbol means the LED is ON, and symbol means the LED is OFF.
17