Limitations on the installation

3. Limitations values on the piping work .

L1

A

L2

L3

L4

h

B

H +

C

H -

D

The piping length information, please refer the following table.

Item

Unit

Descriptions

 

Standard

Maximum

 

A, B, C,D liquid pipe

mm

Size of the liquid side connection pipe

 

6.35

/

A, B, C,D Gas pipe

mm

Size of the gas side connection pipe

 

9.52

/

 

 

 

 

 

 

 

L1

(one way)

m

Pipe length when the compressor connects with two indoor units

 

10

25

 

 

 

 

 

 

 

L2

(one way)

m

Pipe length when the compressor connects with two indoor units

 

10

25

 

 

 

 

 

 

 

L3

(one way)

m

Pipe length when the compressor connects only one indoor unit

 

10

25

 

 

 

 

 

 

 

L4

(one way)

m

Pipe length when the compressor connects only one indoor unit

 

10

25

 

 

 

 

 

 

L1+L2+L3+L4

m

Total liquid piping length(It is no need to charge additional

 

40

60

 

 

 

refrigerant within this value)

 

 

 

h

 

m

Drop between every two indoor units

 

1

5

 

 

 

 

 

 

 

H +

 

m

Drop between the outdoor unit and the indoor unit

 

5

15

H -

 

m

Drop between the outdoor unit and the indoor unit

 

5

10

9

Image 11
Contents Outdoor Unit Installation Manual Contents Disposal of the old air conditioner Specifications Safety precautions Installation dimensionsmm Installation accessoriesChoose the installation place Installation drawings of indoor and outdoor units Matching of the indoor and outdoor units For AU342XHERA Limitations on the installation Power sourceDescriptions Standard Maximum Refrigerant piping work Too outside Purging method to use vacuum pump Way valve Valve rod cap Service port capCorrect Pressing Wrong Pressing Terminal Block Clamps Wiring workWiring work Indoor unit a Items to confirm Test runningFailure State Trouble Possible Reasons Code Haier Group