Schneider Electric EM4800 manual You can set the display format to IEC

Page 22

PowerLogicTM EM4800 Series

930-112-01-B.00

PowerLogic configuration tool

01/2011

 

 

Figure 10: Power Factor tab in the Report section

Table 6: Power Factor tab configuration parameters

Parameter

Description

 

 

Format

You can set the display format to IEC

 

or IEEE by selecting the radial button.

 

 

IEEE

This sign indicates leading (+) or

 

lagging (-) power. The direction of

 

active power is not indicated.

 

 

IEC

The sign (+ or -) indicates the direction

 

of active power and provides an

 

additional indicator for capacitive or

 

inductive (leading or lagging) power.

 

 

Method of Calculation

You can set the power factor method of

 

calculation to Arithmetic or Vector by

 

selecting the radial button.

 

 

16

© 2011 Schneider Electric All Rights Reserved

Image 22
Contents PowerLogicTM Series EM4800 Procedure PowerLogicTM EM4800 Series 930-112-01-B.00 01/2011PowerLogicTM EM4800 Series PowerLogicTM EM4800 Series 930-112-01-B.00 01/2011 Table of Contents Schneider Electric All Rights Reserved EM4805 meters Configuration tool supports the PowerLogic EM4833, EM4880Configuration and Programming PointProgramming access to meter parameters Parameter Read access Write access Activation timeManufacturing Meter and probe pointsDiagnostics Mode Normal ModeDisplay Navigation Direct Connection Ethernet Requirements Communications ConnectionsInjury Network Connection Ethernet Requirements Login Used with meters on a different network Available for configuration. See FigureTo connect to a meter on the same network Proceed to Unit Field Configuration Tab on Discovered Units dialog boxConfiguration tab Unit Field Configuration tab parameters Field Parameter DescriptionReport Parameters 930-112-01-B.00 Parameter Description By selecting the check box930-112-01-B.00 You can set the display format to IEC You can set the BACnet device ID by PowerLogic EM4805 PowerLogic EM4833 PowerLogic EM4880 List of supported metering configurationsManufacturing Tab Meter Points Circuits Tab Meter Point ConfigurationSee Completing the Meter Configuration on To change the Current, enter the required number. To changeBadge Numbering Badge Numbering pane Pulse Probes Tab Completing the Meter Configuration EM4800 Series meter is ready to be programmedSending the configured settings to the meter Window. See Figure930-112-01-B.00 01/2011
Related manuals
Manual 40 pages 36.12 Kb

EM4800 specifications

Schneider Electric, a global leader in energy management and automation, offers advanced power monitoring solutions that enhance energy efficiency and operational effectiveness. The EM4800 and EM400 series are prominent products in Schneider Electric’s energy monitoring line, designed specifically for efficient energy consumption management in various industrial and commercial applications.

The EM4800 is a comprehensive energy meter that caters to larger facilities and energy-intensive operations. One of its main features is its ability to monitor multiple electrical parameters, including voltage, current, frequency, power factor, and total active/reactive energy. The device supports diverse communication protocols such as Modbus, Ethernet, and BACnet, allowing seamless integration into existing building management systems. This diversity in communication enhances visibility into energy usage and supports real-time monitoring, enabling facility managers to make informed decisions.

On the other hand, the EM400 series is designed for smaller applications while still delivering robust functionality. This series is tailored for monitoring power consumption in smaller commercial buildings or branch offices. EM400 meters focus on essential energy metrics but do so with a compact, easy-to-install design. With features like demand forecasting and peak load management, the EM400 provides valuable insights that help organizations optimize their energy usage.

Both models come equipped with advanced technologies such as harmonic analysis, which is crucial for understanding power quality and mitigating potential risks associated with harmonic distortion. The user-friendly interface of these devices facilitates quick access to energy data, making it simple for users to analyze consumption patterns and identify opportunities for energy savings.

In concurrence with Schneider Electric’s commitment to sustainability, both the EM4800 and EM400 series emphasize energy conservation by promoting efficient energy practices. Users can leverage the collected data to reduce energy costs, enhance equipment performance, and contribute to environmental sustainability efforts.

In summary, Schneider Electric’s EM4800 and EM400 energy meters combine innovative technology with practical features aimed at improving energy management. Their advanced monitoring capabilities, versatile communication options, and focus on power quality make them essential tools for organizations seeking to enhance operational efficiency while reducing their carbon footprint. By investing in these cutting-edge energy solutions, businesses can take significant strides towards sustainable energy management and operational excellence.