Emerson MP2-115HW user manual Product Warranty Registration, Specifications

Page 19

SPECIFICATIONS

Transfer Time (to and from

< 6 milliseconds

maintenance bypass)

 

 

 

Operating Ambient Temperature

32°F to 104°F (0°C to +40°C)

 

 

Storage Ambient Temperature

-4°F to 140°F (-20°C to +60°C)

 

 

Dimensions with brackets

3.5 x 3.0 x 15.5 (88.0 x 77.0 x 394.0)

W x D x H: in. (mm)

 

Humidity

0 to 95% non-condensing

 

 

Agency/Standards

UL1778, c-UL, ISTA Procedure 1A

 

 

Electrical Rating

See Model Label on POD

 

 

Table 1

Breaker specifications

 

 

 

 

 

 

 

 

 

 

Model

 

Input

Recommended

Recommended

Maximum

 

 

Current

(Maximum)

Wire (including

Wire

Terminal

VA -

 

 

Rating

External

ground wire)

Accepted

Tightening

Volt

 

 

at

Overcurrent

(75°C

by Terminal

Torque

Rating

 

 

120V*

Protection

copper wire)

Block

 

 

 

 

 

 

 

 

 

 

 

MP2-115HW

 

12A

15A

14 AWG

8 AWG

20 in-lb

 

 

 

 

 

 

 

MP2-120HW

 

16A

20A

12 AWG

8 AWG

20 in-lb

 

 

 

 

 

 

 

MP2-130HW

 

24A

30A

10 AWG

8 AWG

20 in-lb

 

 

 

 

 

 

 

* See POD Rating Plate for Alternate Output Voltages

This POD is intended for use with a UPS meeting all of the following requirements:

UPS input cord is compatible with the rating and type of receptacle on the POD labeled “CONNECT UPS LINE CORD HERE.”

UPS output receptacle is compatible with the POD input power con- nector labeled “UPS.”

Available utility is compatible with the POD input connection and an appropriately sized branch circuit breaker has been provided.

Product Warranty Registration

To register for warranty protection:

Visit the Quick Links section of our Web site at: http://www.liebert.com

Click on Product Warranty Registration and fill in the form. If you have any questions, please contact us at:

US: 800-222-5877

Outside the US: 614-841-6755

upstech@liebert.com

15

Image 19
Contents Power Output Distribution Volt Page Table of Contents Figures Important Safety Instructions Page Glossary of Symbols Introduction and System Description System DescriptionLoad Rack Mount InstallationAttaching POD securing brackets to rear of UPS Installation on GXT 2U UPSHardwire Connections Electrical Installation ConsiderationsRear View Electrical ConnectionsWiring Instructions Attaching POD to securing brackets Apply Feed PowerStart Equipment Utility Indicator LampsUPS Available Transfer to UPS Transfer to Maintenance BypassOperation Problem Cause Solution TroubleshootingSpecifications Product Warranty RegistrationPage Page 2U Hardwire POD