SPECIFICATIONS
Transfer Time (to and from | < 6 milliseconds | |
maintenance bypass) | ||
| ||
|
| |
Operating Ambient Temperature | 32°F to 104°F (0°C to +40°C) | |
|
| |
Storage Ambient Temperature | ||
|
| |
Dimensions with brackets | 3.5 x 3.0 x 15.5 (88.0 x 77.0 x 394.0) | |
W x D x H: in. (mm) | ||
| ||
Humidity | 0 to 95% | |
|
| |
Agency/Standards | UL1778, | |
|
| |
Electrical Rating | See Model Label on POD | |
|
|
Table 1 | Breaker specifications |
|
|
| ||
|
|
|
|
|
|
|
Model |
| Input | Recommended | Recommended | Maximum |
|
| Current | (Maximum) | Wire (including | Wire | Terminal | |
VA - |
| |||||
| Rating | External | ground wire) | Accepted | Tightening | |
Volt |
| |||||
| at | Overcurrent | (75°C | by Terminal | Torque | |
Rating |
| |||||
| 120V* | Protection | copper wire) | Block |
| |
|
|
| ||||
|
|
|
|
|
|
|
| 12A | 15A | 14 AWG | 8 AWG | 20 | |
|
|
|
|
|
|
|
| 16A | 20A | 12 AWG | 8 AWG | 20 | |
|
|
|
|
|
|
|
| 24A | 30A | 10 AWG | 8 AWG | 20 | |
|
|
|
|
|
|
|
* See POD Rating Plate for Alternate Output Voltages
This POD is intended for use with a UPS meeting all of the following requirements:
•UPS input cord is compatible with the rating and type of receptacle on the POD labeled “CONNECT UPS LINE CORD HERE.”
•UPS output receptacle is compatible with the POD input power con- nector labeled “UPS.”
•Available utility is compatible with the POD input connection and an appropriately sized branch circuit breaker has been provided.