Emerson MP2-115HW Installation on GXT 2U UPS, Attaching POD securing brackets to rear of UPS

Page 10

INSTALLATION ON GXT 2U UPS

NOTE

This manual provides instructions for the 2U POD only. Refer to your UPS manual for UPS operation and installation instructions.

1.Unpack the 2U POD carefully, noting the packing method. Retain the box and packing material for possible future shipments.

2.Visually inspect the 2U POD for freight damage. Report damage to the carrier and your local dealer or Liebert representative.

3.Verify that the 2U POD UPS input cord and receptacle for the UPS are the same type of configuration as the UPS to be con- nected.

4.If you already have a UPS installed, turn off all connected UPS loads. Turn off the UPS and disconnect the input cord.

Figure 4 Attaching POD securing brackets to rear of UPS

5.Attach the two POD securing brackets (this is optional for GXT 2U UPS) to the rear of the UPS (see Figure 4). You will need a 7-in. (177.8mm) long #1 Phillips head screwdriver for this procedure (torque is 7 in-lb, or 0.8 Nm). The POD brackets have a hole to allow the screwdriver to reach the screw.

6

Image 10
Contents Power Output Distribution Volt Page Table of Contents Figures Important Safety Instructions Page Glossary of Symbols System Description Introduction and System DescriptionRack Mount Installation LoadInstallation on GXT 2U UPS Attaching POD securing brackets to rear of UPSElectrical Installation Considerations Hardwire ConnectionsElectrical Connections Rear ViewWiring Instructions Apply Feed Power Attaching POD to securing bracketsStart Equipment Utility Indicator LampsUPS Available Transfer to UPS Transfer to Maintenance BypassOperation Troubleshooting Problem Cause SolutionProduct Warranty Registration SpecificationsPage Page 2U Hardwire POD