4.3 Control Units

 

 

Free Standing Unit MEP*L

Rack Mounted Unit MEP*R

 

 

Supply:

1: 220/240V ±10%, 50/60Hz

 

 

 

2: 110/120V ±10%, 50/60Hz

 

 

 

 

 

 

 

Power consumption:

Less than 7VA

Less than 6VA

 

 

 

 

 

 

 

Output:

Alarm relay

Fault relay: SPCO, Energises in

 

 

 

DPCO relay, energised in normal

fault mode

 

 

 

mode, releases on fault or alarm

Alarm relay: High current SPCO,

 

 

 

 

Low current DPCO, Energised in

 

 

 

 

normal mode releases on fault or

 

 

 

 

alarm

 

 

 

See Table 2.1 for relay ratings

 

 

 

 

 

 

 

Connections:

Screw terminal in the base of the

Terminal block on the rear of the

 

 

 

case.

rack unit.

 

To take wires up to 1.5mm2

See Figure 2.7 for wiring details

 

Earthing:

Mains input and sensor connections are fully floating with respect to earth.

 

 

The earth terminal on the freestanding unit and the rack must be earthed.

 

 

 

 

 

Intrinsic safety:

Units MEP*L and MEP*R are intrinsically safe.

 

 

See table 2.2 for certificate details.

 

Output to Head Amplifier:

Approximately 11.5V 20mA maximum

 

 

 

 

 

Temperature Range:

-10ºC to 65ºC

 

 

The units must be left to warm up for 15 minutes before being exposed

 

 

to sub-zero temperatures.

 

 

 

 

 

 

Housing:

IP20 enclosure. Optional DIN rail

19” rack unit to hold up to 14

 

 

mounting or wall mounting.

controls.

 

 

 

 

 

Environment:

Maximum altitude : 2000m

 

 

Maximum humidity : 95%

 

 

 

 

 

Installation Category:

CAT II (264V a.c. MAX) Pollution 2

 

 

CAT III (132V a.c. MAX) Pollution 2

 

 

 

 

 

 

Indicators:

 

3 LEDs

 

 

Green = Normal

 

 

Red = Alarm

 

 

Amber = Fault

 

 

At least one LED should be on at any time.

 

 

 

 

 

Fault Indication:

A fault is indicated if too much, or too little current is taken by the head

 

 

amplifier, indicating a short circuit or an open circuit.

 

 

Alarm relay de-energises

Alarm relay de-energises

 

 

 

Fault relay energises

 

Test Switch:

a) Test Alarm Simulates the alarm condition by stopping the pulses.

 

 

Alarm relay de-energises

Alarm relay de-energises

 

 

b) Test Fault simulates a short circuit in the cable between control

 

 

room and the head amplifier, fault and alarm is indicated.

 

 

Alarm relay de-energises

Alarm relay de-energises

 

 

 

Fault relay energises

 

Alarm Delay:

1-10 seconds. Preset on front panel (20 turns span)

 

 

 

 

 

Reset:

Returns to normal approx. 200ms after alarm is cleared.

 

 

 

 

 

E.M.C.

BS EN61326: 1998 (Emissions) for Class B Equipment

 

 

BSEN61326: 1998 (Immunity) for continuous unmonitored operation in

 

 

industrial locations

 

 

 

L.V.D.

EN61010-1

 

 

18

Image 18
Contents Installation ContentsSafety Information Introduction Fault Finding Specification and descriptionProtection of permanently installed equipment Explanation of symbolsSensors Gap sensorsHi-Sens cylindrical sensors Interface detection Attenuation method Figure Reflection Method FigureSolids Density Detection Head Amplifier UnitsNormal acting head amplifiers Sensor State Output Ii Inverse acting head amplifiersType Industrial Case Marine Control UnitsInstallation 2.1 Calibration Head amplifier internalsCalibration procedure by sensor type Hi-Sens Sensors Ii Gap SensorsIii Interface Sensors Attenuation Method Iv Interface Sensors Reflection Method Sludge SensorSensor and head amplifier installation Adjacent head amplifier mounting detailsPage Control unit installation Wiring CableIi Head Amplifier Unit Iii Control unitRelay Ratings Control Unit Connections Intrinsically safe installation Certificates of ConformityII 1 G EExia IIC EN 50014 & EN Unit not switching Fault FindingFault indicated Relay contacts not changingSensor specification Head AmplifiersTemperature Range Power consumptionIntrinsic safety HousingRecommended Spare Parts 5.1 Sensor and head amplifier Standard Control UnitRack Mounted Unit Options Intrinsic Safety Mounting Sensor Type Test SwitchAppendix I Part Numbers Sensor ConnectionIntrinsic Safety Mounting Mains Voltage Output Relay RacksAppendix II List of illustrations Section Title Appendix III List of tables Section TitleMaintenance / Inspection Abcdef International Americas