Emerson IP221 appendix Sensor specification, Head Amplifiers

Page 17

4.Specification and Description 4.1 Sensors

Sensor

Minimum

Maximum

Maximum

Fitting

Frequency

Type

Temperature

Temperature

Pressure

 

 

 

ºC

ºC

Kg/cm2

 

 

 

 

 

 

 

 

302S

-70

150

56

R¾”

1

30HS

0

250

50

R1½”

1

312S

-70

130

21

R1”

1

312SP

-70

130

20

R1”

1

323S

-70

130

21

R¾”

1

352S

-70

150

56

R¾”

1

362S

-210

65

70

R¾”

3.75

366S

-210

65

3.5

M6

3.75

373S

-70

150

56

R¾”

1

393S

-70

150

56

R¾”

1

39HS

0

250

50

R¾”

1

402S

-70

150

103

R¾”

3.75

420S

-70

150

280

¾” NPT

3.75

433S

-70

150

105

R¾”

1.20

442S

-70

150

105

R¾”

3.75

HL*S

-70

130

100

Flange

1

 

 

 

 

or screw

 

* Note that 1 kg/cm2 = 100kPa

Table 4.1 - Sensor specification

4.2 Head Amplifiers

Power supply:

Operating frequency:

Gain:

Output:

Temperature Range:

Test Switches:

Normal 11.5V, 12-16mA from the control unit

1 or 3.7 MHz

Potentiometer adjustable, switchable ranges on MEP**I

Current pulses transmitted to control unit in ‘Normal’ mode (270 Hz)

-25 to 85ºC

Optional: MEP* AI, ***S*PI**, ***S*PM** simulates a break in the sensor cables (fault test)

MEP*XI simulates active sensor, stopping pulses (alarm test)

Housing:

i) ***S*PI**: IP54 Aluminium housing, mounted on sensor, Pg 16 cable entries

 

ii) ***S*PM**: IP68 Gunmetal or Stainless steel, mounted on sensor, M20 cable

 

entries, holds up to two head amplifier circuits.

 

iii) MEP*AI: IP65 Polycarbonate, mounted adjacent to sensor

 

MEP*XI

 

Cable:

i) Head amplifier

Not supplied, see Section 2.4 (i) for specification.

 

 

to control sensor

 

ii) Sensor to head

MEP* (AI, XI) only, supplied with sensors.

 

 

amplifier

Earthing:

Head amplifier must not be connected to the screen of the control unit cable.

 

On adjacent amplifier, the screens of the sensor cables must be connected to the

 

head amplifier.

 

Intrinsic Safety:

Units type MEP3 are intrinsically safe, see table 2.3 for certificate details

17

Image 17
Contents Safety Information Introduction ContentsInstallation Fault Finding Specification and descriptionExplanation of symbols Protection of permanently installed equipmentHi-Sens cylindrical sensors SensorsGap sensors Reflection Method Figure Interface detection Attenuation method FigureNormal acting head amplifiers Solids Density DetectionHead Amplifier Units Type Industrial Case Marine Ii Inverse acting head amplifiersSensor State Output Control UnitsHead amplifier internals Installation 2.1 CalibrationIii Interface Sensors Attenuation Method Calibration procedure by sensor type Hi-Sens SensorsIi Gap Sensors Sludge Sensor Iv Interface Sensors Reflection MethodAdjacent head amplifier mounting details Sensor and head amplifier installationPage Wiring Cable Control unit installationRelay Ratings Ii Head Amplifier UnitIii Control unit Control Unit Connections II 1 G EExia IIC EN 50014 & EN Intrinsically safe installationCertificates of Conformity Fault indicated Fault FindingUnit not switching Relay contacts not changingHead Amplifiers Sensor specificationIntrinsic safety Power consumptionTemperature Range HousingRack Mounted Unit Recommended Spare Parts 5.1 Sensor and head amplifierStandard Control Unit Appendix I Part Numbers Intrinsic Safety Mounting Sensor Type Test SwitchOptions Sensor ConnectionRacks Intrinsic Safety Mounting Mains Voltage Output RelayAppendix III List of tables Section Title Appendix II List of illustrations Section TitleMaintenance / Inspection International Americas Abcdef