Miele T 9822 installation instructions How to calculate the effective duct length

Page 19

Ducting

How to calculate the effective duct length

The overall duct length will determine the duct diameter (see the "Additional duct lengths" table). In Canada the exhaust duct must be 4" (102 mm) in diameter.

￿Measure the actual duct length needed to go from the dryer’s exhaust connection to the vent outlet:

1.Establish the number of elbows or bends necessary, noting the type of bend, angle and radius involved (see the "Additional duct lengths" table).

2.Add the additional duct length (as derived by using the values specified in the "Additional duct lengths" table) to the actual duct length to get the effective length.

Note:

Maximum effective duct lengths:

4" (100 mm) diameter

66 ft (20 m)

5" (125 mm) diameter

131 ft (40 m)

6" (150 mm) diameter

328 ft (100 m)

If using flexible metal duct the total length must not exceed 7' 10" (2.4 m).

See the "Additional duct lengths" table for more information on maximum duct lengths and number of bends.

Effective duct lengths over 66 ft (20 m) require a larger duct diameter.

Longer ducts may lead to decreases in dryer efficiency if the next larger duct diameter is not followed.

19

Image 19
Contents Installation Instructions T 9822 Gas Dryer Page What to do if YOU Smell GAS Contents Massachusetts Installation and connectionSave These Instructions Front view InstallationStand Rear InstallationInstallation site Confined door openings Confined space installationLevel the dryer Transporting the dryer to the installation siteChanging the position of the exhaust connection Determining the position of the exhaust connectionGrounding Instructions Electrical connectionGas type Gas connectionGas connection distances Gas supply Do not Overtighten Never USE AN Open Flame to Test for GAS Leaks Exhaust ducting and connections DuctingHow to calculate the effective duct length Tips about the ductwork Concertina bend Additional duct lengths 4 100 mm rigid pipe onlySmooth metal duct Elbow 90 sharpLength ExampleRigid pipe Duct length Total ductExhaust connection on left or right Wall connection example Window connection exampleDryer top view Direct wall connectionDisposal of the packing materials Caring for the environmentDisposal of an appliance