ADC ML-96 To Test and Adjust Gas Water Column Pressure, To Convert Natural Gas to L.P. Gas

Page 23

To Test and Adjust Gas (Water Column) Pressure

There are two (2) types of devices commonly used to measure column pressure. They are spring and mechanical- type gauges and manometers. The spring and mechanical-type gauge is not recommended, because it is easily damaged and not always accurate. A manometer is simply a glass or transparent plastic tube with a scale in inches. When filled with water and pressure applied, the water in the tube rises showing the exact water column pressure.

NOTE: Manometers are available from the factory by ordering ADC P/N 122804.

1. To test gas water column (W.C.) Pressure:

a. Connect water column test gauge connection to gas valve pressure tap (1/8” NPT). This pressure tap is located on the outlet (manifold) side of the valve.

b. Start dryer. With burner on, the correct water column reading in inches would be:

Natural Gas - 3.5 Inches Water Column (8.7 mb). L.P. Gas - 10.5 Inches Water Column (26.1 mb).

2.To adjust water column pressure (natural gas only, L.P. gas must be regulated at source):

a. Remove the slotted vent cap on the top of the valve.

b. Turn the slotted adjustment screw located on the top of the valve next to the terminals. Turn clockwise (CW) to increase manifold pressure and counterclockwise (CCW) to decrease.

NOTE: If correct W.C. pressure cannot be achieved, problems may be due to an undersized gas supply line, a faulty or underrated gas meter, etc.

To Convert Natural Gas to L.P. Gas

NOTE: ALL dryers are sold as natural gas, unless otherwise specified at the time the dryer order was placed. For L.P. gas the dryer must be converted as follows.

1.Refer to “Replace Gas Valve” and follow Step #1 through Step #6. a. For models with 3/4” White-Rodgers valve.

1)Remove top vent cap.

2)Insert spring and pin.

3)Replace vent cap.

2.Unscrew main burner orifices and replace with L.P. orifices.

NOTE: Use extreme care when removing orifices. They are made of brass and are easily damaged.

19

Image 23
Contents ML-96 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Important Information Safety PrecautionsPage MATERIALS, Gasoline and Other Flammable Vapors Routine MaintenanceCleaning Lubrication AdjustmentsElectrical and GAS Requirements Installation RequirementsENCLOSURE, AIR SUPPLY, and Exhaust Requirements Operational Service Check Procedure Page Reversing Relay Panel Description of PartsDrive Motor GAS Burner AssemblyHSI HOT Surface Ignition Module Gas Models Only Tumbler Basket Drive Shaft AssemblyIdler Shaft Assembly Burner HI-LIMIT Gas Models Only Main Door SwitchSail Switch Gas Models Only Lint Screen Manual Reset ThermostatLint Drawer Switch Introduction Computer Board ReplacementServicing Microprocessor Temperature Sensor Probe Replacement Keyboard Touchpad Label Assembly ReplacementHot Surface Ignitor Flame Sensor Probe Flame Sensor Probe ReplacementIgnition Controls Main Burner Orifices Replacement Gas Valve Replacement Refer to burner illustration onTo Convert Natural Gas to L.P. Gas To Test and Adjust Gas Water Column PressureHSI Hot Surface Ignition Module Replacement Burner Tubes ReplacementDisconnect electrical power to the dryer Open lint door To Adjust Sail Switch Sail Switch Assembly Gas Models OnlySail Switch Replacement To Install New Main Door Glass Main Door Assembly ReplacementMain Door Hinge Block Replacement Front Panel ReplacementDrive Motor Pulley Replacement Drive Shaft Pulley ReplacementPage 15/16 Flange Bearing Replacement Basket AssemblyRotational Sensor Assembly Belt Adjustment Motor to Drive Axle Idler Shaft Pillow Block Bearing ReplacementDrive Shaft Pillow Block Bearing Replacement Motors Drive Motor V-Belts ReplacementDrive Motor Replacement Lint Door Switch Replacement Motorized Impellor Blower ReplacementComputer will not accept keypad touchpad entries TroubleshootingDryer operates but is taking too long to dry Overload for impellor fan motor is tripping Burner hi-limit safety thermostat is trippingThermal overload for drive motor is tripping There is excessive vibration coming from the tumbler basket Diagnostic L.E.D. Light Emitting Diode Display Failure Codes Phase 6 OPL System DiagnosticsPage E.D. Display Indicator Number E.D. Light Emitting Diode Display IndicatorsE.D. Display Indicator Number HT1 Heat Output L.E.D. light emitting diode Indicator FAN Blower Output L.E.D. light emitting diode IndicatorMain Main Door Input L.E.D. light emitting diode Indicator Fuse Main Fuse Input L.E.D. light emitting diode IndicatorLint Lint Door Input L.E.D. light emitting diode Indicator Power Supply Input L.E.D. light emitting diode Indicator E.D. Codes 1. Display Codes GAS only Ignition Attempt Failure GAS Models only Power 24 VAC is not Evident AT GAS ValveGAS/ELECTRIC only BURNER/OVEN Open HI-LIMIT Circuit Computer Logic and Wiring Diagram Page Drive motor reverses but does not forward, blower motor runs No Display ConditionLint Door Condition Blower motor does not operate, drive motor runsMicroprocessor Computer Main Door ConditionFor Phase 6 Models Manual Reset HI-LIMIT InstructionsMotor Plate High and LOW Voltage Technical InformationInformation on the Data Label Data LabelHOW to USE a Manometer ML-96 Tool List ADC450406 1- 02/09/00-25
Related manuals
Manual 26 pages 45.33 Kb

ML-96 specifications

The ADC ML-122 and ML-96 are two advanced communication devices designed for efficient data collection and transmission in various applications. Both models are renowned for their robust performance and user-friendly features, which cater to a diverse range of industries.

The ADC ML-122 is a high-performance data logger that excels in multi-channel monitoring. It supports various input types, making it versatile for applications such as environmental monitoring, industrial process control, and research. One of its standout features is its ability to accommodate both analog and digital signals, allowing users to gather a wealth of data from different sources. The device supports a wide temperature range, ensuring reliability in diverse environmental conditions. Moreover, its built-in memory can store extensive data logs, which are easily downloadable for analysis.

On the other hand, the ADC ML-96 is designed primarily for telecommunication and network monitoring. It features advanced signal processing technologies that allow it to analyze and troubleshoot communication lines efficiently. The device is equipped with real-time monitoring capabilities, enabling users to detect issues as they arise, which is crucial in maintaining network integrity. The ML-96's compact design makes it an ideal choice for installation in tight spaces without sacrificing performance.

Both models are built with cutting-edge technologies that enhance their functionality. They integrate wireless communication protocols, such as Wi-Fi and Bluetooth, enabling seamless connectivity to cloud services for data backup and remote access. This feature empowers users to monitor conditions from anywhere, ensuring that critical information is always at hand.

The user interface for both the ML-122 and ML-96 is designed for ease of use. Equipped with a clear display and intuitive controls, users can navigate through settings and view data with minimal training. The devices also offer customizable alerts that notify users of any anomalies, adding an additional layer of security and responsiveness.

In terms of power management, both models utilize energy-efficient components, allowing for extended battery life. This is particularly advantageous in remote sensing applications where power sources may be limited. Furthermore, the ability to integrate with other systems makes these models adaptable to various operational needs.

In conclusion, the ADC ML-122 and ML-96 stand out in their respective markets due to their innovative features, reliable technologies, and user-friendly designs. With their flexibility and performance, they continue to set the standard for data logging and communication monitoring technologies.