Electrical Installation

Important

Electrical ratings are subject to changes. Refer to serial plate decal for electrical ratings information specific to your machine.

WARNING

Hazardous Voltage. Can cause shock, burn or cause death. Allow machine power to remain off for two minutes prior to working in and around AC inverter drive.

WARNING

Hazardous Voltage. Can cause shock, burn or death. Verify that a ground wire from a proven earth ground is connected to the lug near the input power block on this machine.

The AC inverter drive requires a clean power supply free from voltage spikes and surges. If a transformer or generator is connected to the building's power supply, always install line reactors before the terminal block connections to the machine. A voltage monitor should be used to check incoming power. The customer’s local power company may provide such a monitor.

If input voltage measures above 240V for a 220V drive or above 480V for a 400V drive, ask the power company to lower the voltage. As an alternative, a step-down transformer kit is available from the distributor.

The AC drive provides overload protection for the drive motor. However, a separate single or three-phase circuit breaker must be installed for complete electrical overload protection. This prevents damage to the motor by disconnecting all legs if one should be lost accidentally. Check the data plate on the back of the washer-extractor or consult Table 2 through 7 for circuit breaker requirements.

IMPORTANT: Do NOT use fuses in place of a circuit breaker.

For installation in the United States or Canada, branch circuit protection must be provided according to National and Local Codes. The branch circuit breaker must be of the inverse time or instantaneous trip type at the values given in the technical specifications for each machine.

Use a circuit breaker of the minimal type of 10kA interrupt current.

CAUTION

Do not use a voltage or phase converter on any variable speed machine.

The washer-extractor should be connected to an individual branch circuit not shared with lighting or another electrical device.

-In accordance with legal regulations, every machine must be protected with an earth leakage circuit breaker of 30mA.

-The earth leakage circuit breaker, which one uses, must be of the type SI.

-For countries outside the European Community, the usual safety instructions must be observed.

35

Image 35
Contents Washer Extractors Page Contents Internal connections of the electrical heating  Page Build-up Model numbers Model NumbersPage Safety Safety and Environmental InformationsDisposal of Unit EnvironmentalExplanation of Safety Messages Important Safety Instructions Page Operator Safety Technical data HC60, IHC012, IHC060 Technical data and dimensionsDimensions HC60, IHC012, IHC060 Technical data HC65, IHC014, IHC065 Dimensions HC65, IHC014, IHC065 Technical data HC75, IHC018, CHC018, IHC075 Dimensions HC75, IHC018, CHC018, IHC075 Technical data HC100, IHC025, CHC025, IHC100 Dimensions HC100, IHC025, CHC025, IHC100 Technical data HC135, IHC030, IHC135 Dimensions HC135, IHC030, IHC135 Technical data HC165, IHC035, CHC035, IHC165 Dimensions HC165, IHC035, CHC035, IHC165 Surface Installation and Connection InstructionsOut of balance switch Removal of the transport safety 485 545 530 660 590 650 530 660 590 650 530 660 690 750 530 660 36.5 665 738 648 780 36.5 765 838 648 Water drain Water connectionImportant Do not use fuses in place of a circuit breaker Electrical InstallationGrounding Instructions Connection label Main power connectionMachine Power Cable Connections Page Alternative Electric Heat Options Electrical Specifications HC60, IHC012, IHC060Boiler Fed/Steam Heat Electric Heat Liters / 14 pounds Electrical Specifications HC65, IHC014, IHC065Liters / 18 pounds Electrical Specifications HC75, IHC018, CHC018, IHC075Liters / 25 pounds Electrical Specifications HC100, IHC025, CHC025, IHC100Liters / 30 pounds Electrical Specifications HC135, IHC030, IHC135Liters / 35 pounds Electrical Specifications HC165, IHC035, CHC035, IHC165Connection of the liquid soap hoses Liquid soap connection optionWith an external tension 24V DC See Label Label With direct steam injection into the machine See Table Steam connectionInternal connections of the electrical heating Technical remarksEnd of day Maintenance instruction of the machineGeneral maintenance Periodical maintenance Annual maintenance Nameplate Location Contact InformationNameplate Replacement Parts Repair and after-sales service