3.NORMAL OPERATION (summary)
When a signal is received from the thermostat supplying 24 volts to the W terminal of the HSI module, the control will reset, perform a self check routine, flash the diagnostic L.E.D. for up to four (4) seconds and a
Should the main burner fail to light, or a flame is not detected during the first trial for ignition period, the Gas Valve is
Recovery from LOCKOUT requires a manual reset by either resetting the thermostat or removing the 24 volts for a period of five (5) seconds.
If the computer is still calling for heat after one (1) hour the HSI Module (controller) will automatically reset and attempt to ignite the burner again.
D. TROUBLESHOOTING
The troubleshooting information provided in this manual is intended for use only by QUALIFIED SERVICE TECHNICIANS. Observe ALL safety precautions displayed on the equipment or specified in the Installation/Operator’s Manual included with the dryer.
IMPORTANT: UNDER NO CIRCUMSTANCES SHOULD ANY SAFETY OR HEAT CIRCUIT DEVICE EVER BE DISABLED.
The following troubleshooting guide provides systematic procedures for isolating equipment problems, and again, is intended for use by a QUALIFIED SERVICE TECHNICIAN.