Sensor Activated Fire Extinguishing (S.A.F.E.) System
Theory of Operation
While the dryer is in an idle state or
While a drying cycle is in process and the heat has turned on at least once, the Phase 7 control monitors the exhaust temperature transducer. If the drying cycle temperature set point is set greater than 160°F (71°C) and the control detects an exhaust temperature rise 25°F greater than set point, this will be the trip point and the S.A.F.E. system routine will activate. If set point is below 160°F (71°C) the trip point will be 185°F (85°C).
Once the S.A.F.E. system routine is activated, the control will display “Fire Suppression System Activated” and water will be injected into the basket (tumbler) chamber. Anytime water is being injected into the basket (tumbler); the basket (tumbler) drive will turn the load for
Disabled Sensor Activated Fire Extinguishing (S.A.F.E.) System
In the event that the S.A.F.E. system is not installed properly or if there is a malfunction in the system the Phase 7 coin control will notify the user by displaying the message ‘FSS DISABLED...” If the “PAUSE” and “LO” keys are simultaneously pressed, the control will display one of the following diagnostic messages indicating the fault with the system. If there is more than one issue with the S.A.F.E. system, the control will display one message at a time.
S.A.F.E. System Diagnostic Messages
Open FSS Probe Fault: This message indicates that the S.A.F.E. probe is either not connected or is damaged.
Shorted FSS Probe Fault: This message indicates that the S.A.F.E. probe is damaged or the wiring is shorted.
Open FSS Valve Fault: This indicates that the water valve is open or that it is not connected to the control.
Shorted FSS Valve Fault: This indicates the water valve is shorted or the wiring to the valve is shorted.
Water Not Connected: This indicates that there is no water pressure at the water valve. This will occur if water is not connected to dryer or if there is low water pressure in the water line coming to the dryer. This could also be a defective pressure switch or wiring to the pressure switch.
SYSTEM RESET
To reset the microprocessor once the control displays “FSS Was Activated,” press and hold the “PAUSE” key for
51