American Dryer Corp MDG30PCC installation manual Single Dryer Venting

Page 15

SINGLE DRYER VENTING

HORIZONTAL VENTING

When horizontal single 8-inch (20.32 cm) venting is used, the ductwork to the outlet cannot exceed 30 feet (9.14 meters) refer to Illus. A below. This calculation of 30 feet (9.14 meters) compensates or allows for the use of a maximum of only one (1) elbow.

Illus. A

VERTICAL VENTING

When vertical single venting is used the minimum duct size is 10-inches (25.4 cm) refer to Illus. B below, the ductwork from the dryer to the outside outlet cannot exceed 60 feet (18.3 meters) refer to Illus. B below. This calculation compensates for the use of a maximum of three (3) elbows including the two (2) elbows creating the 180° (turned downward) outside outlet.

Illus. B

If the length of the duct run or quantity of elbows used exceeds the above noted specifications, the cross section area of the ductwork must be increased in proportion to the number of elbows or duct run added.

IMPORTANT: For extended ductwork runs, the cross section area of the duct can only be increased to an extent. For extended ductwork runs, a professional heating, ventilating, and air-conditioning (HVAC) firm should be consulted for proper venting information.

113201 - 7

Maytag Co.

11

Image 15
Contents MDG30PCC Installation Manual MDG30PCC PH7 For Your Safety Page Table of Contents Section Safety PrecautionsMaytag Co 20.32 cm SpecificationsSpecifications Unpacking and Setting UP Installation ProceduresLocation Requirements Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Single Dryer Venting Multiple Dryer Common Venting Multiple Dryer Venting Vertical Electrical Requirements Electrical InformationFor 110V Applications GAS Information Type of GAS This Pipe Size Requirement Preparation for Operation and START-UP Preoperational Tests Basket Tumbler Coating Preoperational InstructionsShutdown Instructions SERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsWarranty Routine Maintenance CleaningSuggested Cleaning Schedule Lubrication AdjustmentsData Label Information Sectionviii Procedure for Functional Check Replacement ComponentsMaytag Co Manual Reset Burner HI-LIMIT Instructions PhaseDual Timer Maytag Co 09/16/08