American Dryer Corp ML-96HS installation manual Fresh AIR Supply

Page 17

D. FRESH AIR SUPPLY

When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and sail switch "fluttering" problems may result, as well as premature motor failure from overheating.

Air supply (makeup air) must be given careful consideration to assure proper performance of each dryer. An unrestricted source of air is necessary for each dryer. An air flow of 2,700 cfm (cubic feet per minute) must be supplied to each dryer. As a general rule, an unrestricted air entrance from the outdoors (atmosphere) of a minimum of 3 square feet is required for each dryer.

To compensate for the use of registers or louvers used over the openings, this makeup air must be increased by approximately thirty-three percent (33%). Makeup air openings should not be located in an area directly near where exhaust vents exit the building.

It is not necessary to have a separate makeup air opening for each dryer. Common makeup air openings are acceptable. However, they must be set up in such a manner that the makeup air is distributed equally to ALL the dryers.

EXAMPLE: For a bank of six (6) dryers, two (2) unrestricted openings measuring 3 feet by 3 feet (18 square feet) is acceptable.

Allowances must be made for remote or constricting passageways or where dryers are located at excessive altitudes or predominantly low pressure areas.

IMPORTANT: Makeup air must be provided from a source free of dry cleaning solvent fumes. Make- up air that is contaminated by dry cleaning solvent fumes will result in irreparable damage to motors and other dryer components.

NOTE: Component failure due to dry cleaning solvent fumes will VOID THE WARRANTY.

13

Image 17
Contents ML-96HS Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Important Information SectionWhat to do if YOU Smell GAS Safety PrecautionsPage Specifications SPECIFICATIONS/COMPONENT IdentificationObligation Component Identification Dryer Rear View Location Requirements Installation ProceduresUNPACKING/SETTING UP Page Dryer Enclosure Requirements Fresh AIR Supply Create a Potential Fire Hazard Exhaust RequirementsSingle Dryer Venting Page Page Electrical Information G 9 6 H S Page GAS Information Type of GAS Piping and Connections Preparation for Operation and START-UP Supply Voltage Must Match the Electric Service ExactlyHeat Circuit Operational Test Preoperational TestsOperating Instructions Shut Down Instructions Parts ServiceReturning Warranty Parts Warranty InformationReturning Warranty Cards Page Cleaning Routine MaintenanceLubrication AdjustmentsHot Surface Ignition HSI System Procedure for Functional Check Replacement Components