IMPORTANTVENTINGREMINDERS

1.Ductwork size and installation should be done by a qualified professional.

2.The dryer must be exhausted to the outdoors.

3.Ductwork should be routed as short as possible to the outdoors with as few elbows as possible.

4.Avoid 90° turns, use 30° or 45° turns instead.

5.For single dryer venting, the size of the ductwork must be a minimum of 8-inches (20.32 cm) for short runs (refer to the illustration on page 15). For longer runs, the diameter must be increased.

6.The inside of the ductwork should be as smooth as possible with no projections from sheet metal screws.

7.Ducts added should overlap the duct to which it is to be connected.

8.ALL ducts should be taped to prevent moisture and lint from escaping into the building.

9.Inspection (cleaning) doors should be installed throughout strategic points in the ductwork for periodic inspection and cleaning.

10.Whenever the ductwork passes through combustible materials, the opening must be 2-inches (5.08 cm) larger than the duct (all the way around). The duct must be centered within this opening.

11.The outside of the ductwork must be protected from the weather. A 90° elbow must be used for horizontal run and when vertically through a roof by using a 180° turn to point the opening downward. The distance between the exhaust duct and the nearest obstruction (i.e., roof or ground) must be twice the diameter of the duct.

12.DO NOT use screens, louvers, or caps on the outside opening of the exhaust ductwork.

13.Exhaust back pressure measured by a manometer at the dryer’s exhaust duct area must be no less than 0 and must not exceed 0.7 inches (1.74 mb) of water column (W.C.).

14.Exhaust ductwork outlets should not be located in an area directly where make-up air openings are located.

WARNING: DRYER MUST NEVER BE OPERATED WITHOUT THE LINT FILTER/ SCREEN IN PLACE, EVEN IFAN EXTERNAL LINT COLLECTION SYSTEM IS USED.

15. It is recommended that exhaust or booster fans not be used in the exhaust ductwork system.

113394 - 8

Maytag Co.

17

Image 21
Contents MDG75PNH and MDG75MNV Installation Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Procedure for Functional Check Section Safety PrecautionsMaytag Co 113394 Specifications SpecificationsSpecifications Gas Component Identification Maytag Co 113394 Location Requirements Installation ProceduresUNPACKING/SETTING UP Dryer Enclosure Requirements Fresh AIR Supply Requirements General Exhaust Ductwork Information Exhaust RequirementsOutside Ductwork Protection Maytag Co Multiple Common Dryer Venting Importantventingreminders Electrical Requirements Electrical InformationNON-REVERSING GAS Single-Phase Electrical Lead Connections For 110V Applications GAS Information Type of GAS Maytag Co 113394 Maytag Co Preparation for OPERATION/START-UP Preoperational Tests Basket Tumbler Coating Preoperational Instructions Dual Timer DryersShutdown Instructions Reversing Timer SPIN/DWELL AdjustmentsSERVICE/PARTS Information ServiceParts Routine Maintenance CleaningSuggested Cleaning Schedule Lubrication AdjustmentsLint Drawer Removal Data Label Information Sectionvii Procedure for Functional Check Replacement ComponentsMaytag Co Manual Reset Burner HI-LIMIT Instructions PhaseDual Timer Sensoractivated Fire Extinguishing S.A.F.E. System F.E. System In ActionInstallation Typical Water Supply F.E. System Theory of Operation F.E. System Water Valve Check F.E. System Diagnostics Messages Maytag Co 10/30/08