Schneider Electric RS232/ASCII user manual Connecting status information and RS232 links

Page 14

Connecting status information and RS232 links

The status information (see figure 2) is available on the DB9 socket connectors. The pins are as follows:

1.earth,

4.operation on mains (as opposed to battery),

5.common,

6.operation on bypass (static switch or manual bypass),

7.low battery warning,

8.operation on UPS,

9.operation on battery.

A remote stopping signal can be transmitted on pin 3 of each DB9: a high status (4 V to 20 V) of a minimum duration of 100 ms causes the time-delayed stopping of the

Relay breaking capacity: Vmax = 30 V

lmax = 200 mA

n.o. : normally open,

n.c. : normally closed

5 4 3 2 1

9 8 7 6

n.o. n.c. n.o. n.o. n.o.

Connecting the RS232 links

See detail B of figure 1 (page 9), jumpers JMP1 and JMP2 placed on the right.

RX TX

0V

5

4

3

2

1

9 8 7 6

UPS (absorbed current: 0.5 mA under 5 V).

Caution: the remote stopping signal is taken into account only if the UPS is operating on battery. This remote stopping function is not available on all the UPS.

common

Fig. 2

Fig. 3

See detail B of figure 1 (page 9),

jumpers JMP1 and JMP2 placed on the left.

TX RX

0V

5

4

3

2

1

9 8 7 6

Fig. 4

Page 6 - 51029073XT/AE

Image 14 Contents
RS232/ASCII communication system English version Version française 5102907300/AE 5102907300-AE 990-5102907300AE Sicherheitshinweise Safety guidelinesConsignes de sécurité Regras de segurança Consegne di sicurezzaConsignas de seguridad Veiligheidsvoorschriften SikkerhedsforskrifterSäkerhetsföreskrifter TurvallisuusohjeetContents Description CheckingOverview Configuration of RS232 link direction on channel J4 Configuration of the RS232/ASCII cardConfiguration of RS232 link direction on channel J3 Installation / startup Connecting status information and RS232 links Connecting the RS232 links
Related manuals
Manual 14 pages 11.69 Kb