Troubleshooting

 

 

TROUBLESHOOTING

Table 10 Troubleshooting

Problem

Cause

Solution

The maintenance wrench

There is a problem with the

See the Alert sub-menu or the Diagnostic Alert Modbus Register 146

icon appears in the power

inputs to the power meter.

 

meter display.

 

 

The display is blank after

The meter is not receiving

Verify that the meter control power is receiving the required voltage.

applying control power to

adequate power.

Verify that the heart icon is blinking.

the meter.

 

Check the fuse.

 

 

 

 

Incorrect setup values

Verify the values entered for power meter setup parameters (CT and PT

 

 

ratings, system type, etc., see Setup section).

The data displayed is

Incorrect voltage inputs

Check power meter voltage input terminals to verify adequate voltage.

inaccurate.

 

 

Power meter is wired

Check all CTs and PTs to verify correct connection to the same service,

 

 

improperly.

CT and PT polarity, and adequate powering (see Wiring Diagrams

 

 

section).

 

Power meter address is

Verify that the meter is correctly addressed (see Setup section).

 

incorrect.

 

 

 

 

 

Power meter baud rate is

Verify that the baud rate of the meter matches that of all other devices

Cannot communicate with

incorrect.

on its communications link (see Setup section).

 

 

power meter from a remote

Communications lines are

Verify the power meter communications connections (see

personal computer.

improperly connected.

Communications section).

 

 

Verify the terminating resistors are properly installed on both ends

 

 

of a chain of units. Units in the middle of a chain should not have a

 

 

terminator.

 

 

Verify the shield ground is connected between all units.

 

 

 

Sign of one phase (real

CT orientation reversed

Remove CT, reverse orientation, reconnect (qualified personnel only)

power) is incorrect

 

 

 

 

 

CHINA ROHS COMPLIANCE INFORMATION (EFUP TABLE)

 

 

 

产品中有毒有害物质或元素的名称及含量Substances

 

部件名称

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

铅 (Pb)

汞 (Hg)

镉 (Cd)

六价铬 (Cr(VI))

多溴联苯(PBB)

 

多溴二苯醚(PBDE)

 

 

 

 

 

 

 

 

电子线路板

X

O

O

O

O

 

O

 

 

 

 

 

 

 

 

O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下. X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.

Z000057-0A

© 2011 Schneider Electric All Rights Reserved.

41

Image 45 Contents
EM3555 Hazard Categories Special Symbols Please NoteFCC Notice Contents EM3555 ZL0093-0A Contents 11/2011 Installation Overview Safety PrecautionsDIN Rail Mounting Screw MountingType Description SpecificationsSafety Environmental ConditionsMetering Category Observe correct CT orientation when installing the device IntroductionParts of the EM Series EM Series Dimensions DimensionsData Output Data Output Full Data Set FDSData Logging Attach mounting clips for DIN Rail InstallationThree-Phase Wiring Single-Phase WiringSupported System Types Supported system typesWiring Symbol DescriptionWiring Symbols Diagram Wiring DiagramsDiagram Phase 4-Wire Wye Connection 3 CT 3 PT Use System Type 11 2LWiring Notes Control PowerFuse Recommendations L1 L2 L3Display Screen Display Screen DiagramQuick Setup Instructions Solid State Pulse Outputs SOLID-STATE Pulse OutputMain Menu UI Menu Abbreviations DefinedIEC and Ieee Abbreviations DescriptionFor Data Configuration EM3555 User Interface for Data Configuration Ploss Lowpf ERR OVR Pulse ALERT/RESET InformationFrom User Interface for SetupEM3555 ZL0093-0A User Interface for Setup 11/2011 RS-485 Communications Daisy-chaining Devices to the Power MeterData Logging ConfigurationReading Data Read/Write CollisionStandard Modbus Default Settings Setting Value Modbus RegisterModbus Default Settings Command Description Supported Modbus CommandsSupported Commands Modbus Point MAPSunSpec Alliance Interoperability Specification Compliance Format Units Scale Range Description Integer Data Summary of Active PhasesFormat Units Scale Range 055 ULong KVARh Accumulated Q1 Reactive 079 ULong KVAh Accumulated Apparent Register 142 NV UInt 143 10000 144 500 250 145 Msec 146 LSB Logging Configuration and Status161 UInt 32767 162 163 164 0xFFFF ULong KWh 165 166 Month Floating Point Data Summary of Active Phases Floating Point Data Per Phase Logging Interface Register Format Units Scale Range Sunspec Compliant Common and Meter Model Register BlocksSunSpec Description Name SunSpec 1.0 Common ModelName SunSpec DescriptionSunSpecCompliantCommonandMeterModelRegisterBlocks Event Bit Description Problem Cause Solution TroubleshootingTroubleshooting China Rohs Compliance Information Efup TableEM3555 Installation Guide Schneider Electric