EM3555 |
|
User Interface for Setup | 11/2011 |
|
|
To Setup p. 1 “S PWR” |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| VOLTS |
|
|
|
| IMBAL | ||
Back |
| SPLOS |
|
|
|
| |||||
|
|
| |||||||||
|
|
|
| 0.10 |
|
| 0.25 | ||||
Phase | |||||||||||
|
|
|
|
|
|
| |||||
Loss |
|
|
|
|
|
|
| ||||
|
|
|
|
| Next |
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system voltage below which Phase Loss Alarm is on. For system types with neutral, the Line to Neutral voltage is also calculated and tested. If the System Voltage is 600 and the fraction is set to 0.10, then the Phase Loss threshold will be 60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference in Line to Line voltages above which Phase Loss Alarm is on. For system types with neutral, the Line to Neutral voltages are also tested. For system types 1+N (10) and 2 (11) , imbalance is not tested.
Set Pulse:
Back To SETUP
|
|
|
| Wh/P |
|
|
|
| |
|
|
|
| 10000 |
Back |
| SPULS | ||
|
| 1000 | ||
|
| |||
|
|
|
| |
Pulse |
| 100 | ||
Output |
| 10 |
mS/P | Max | |
PPS | ||
500 | ||
1 | ||
250 | ||
2 | ||
100 | ||
5 | ||
50 | ||
10 | ||
25 | ||
20 | ||
10 | ||
50 | ||
| ||
Next |
|
The System Type , CT size, PT Ratio, and System Voltage must all be configured before setting the Pulse Energy. If any of these parameters are changed, the meter will hunt for a new Pulse Duration, but will not change the Pulse Energy. If it cannot find a solution, the meter will display the wrench, show “ConF” in the ALARM
Wh/P - Set Pulse Energy: In Watt Hours (& VAR Hours, if present) per Pulse. When moving down to a smaller energy, the meter will not allow the selection if it cannot find a pulse duration that will allow the pulse output to keep up with Theoretical Maximum System Power (see S_PWR screen). When moving up to a larger energy, the meter will jump to the first value where it can find a valid solution.
mS/P – Minimum Pulse Duration Time: This read only value is set by the meter to the slowest duration (in mS per closure) that will keep up with the Theoretical Maximum System Power. The open time is greater than or equal to the closure time. The maximum Pulses Per Second (PPS) is shown in yellow.
|
|
|
|
|
|
|
| INTRV |
| |
|
|
|
|
|
| |||||
|
|
|
|
| 6 |
| ||||
|
|
|
|
|
|
| 5 |
| ||
Back |
| SDMND |
| |||||||
| 4 |
| ||||||||
|
|
|
|
|
| |||||
Demand |
|
| 3 |
| ||||||
|
| 2 |
| |||||||
|
|
|
|
|
| |||||
|
|
|
|
| 1 |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| UNITS |
| |
|
|
|
|
|
|
| ||||
Back |
| S DIS |
|
|
|
| ||||
|
|
|
| IEEE |
| |||||
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||
Display |
|
|
|
|
| IEC |
| |||
|
|
|
|
| ||||||
Units |
|
|
|
|
|
|
|
| ||
|
|
|
| Next |
| |||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SETUP |
| |
Back |
| SPASS |
|
|
|
| ||||
|
|
| ||||||||
Setup |
|
|
|
| 00000 |
| ||||
|
|
|
| |||||||
Passwords |
|
|
|
|
|
|
SEC
00900
Next
RESET
00000
Next
Set Demand Interval:
INTRV - The number of
SEC -
Set Display Units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units.
IEC - U V P Q S Units.
Set Passwords:
SETUP - The Password to enter the SETUP menu. RESET - The Password to enter the RESET menu.
To Setup page 1 “S COM”
20 | © 2011 Schneider Electric All Rights Reserved. |