EM3555 | |
11/2011 | Modbus Point Map |
|
|
REGISTER | R/W NV | Format | Units | Scale | Range |
142 | R/W NV UInt | % |
143 | R/W NV UInt | % |
|
|
| 10000, | |
144 | R/W NV UInt | Wh | 1000, | |
100, | ||||
|
|
| ||
|
|
| 10 |
|
|
|
| 500, | |
|
|
|
| 250, | |
145 | R | NV UInt | msec | 100, | |
50, | |||||
|
|
|
| ||
|
|
|
| 25, | |
|
|
|
| 10 |
146 | R | UInt |
147 | R | NV UInt | |
148 | R | UInt |
|
Description
Phase Loss Voltage Threshold in percent of system |
| |
voltage (register 134). Default value is 10 (%). Any |
| |
phase (as configured in register 130) whose level |
| |
drops below this threshold triggers a phase loss alert, |
| |
i.e., if the system voltage is set to 480 V |
| |
voltage for each phase should be 277 V. When the |
| |
threshold is set to 10%, if any phase drops more |
| |
than 10% below 277 V, (less than 249 V), or if any | Phase Loss Output | |
| ||
than 432 V) the corresponding phase loss alarm bit in | Note: The phases tested are determined by the | |
register 146 will be true. | system type. | |
Phase Loss Imbalance Threshold in Percent. Default | ||
| ||
is 25% phase to phase difference. For a |
|
+N) system type (40 in register 130), both
Wh (& VARh, if equipped) |
| |
Energy per Pulse Output |
| |
Contact Closure. If the meter |
| |
cannot find a pulse duration |
| |
that will keep up with the |
| |
max. system power (register |
| |
135), it will reject the new |
| |
value. Check the meter |
| |
configuration and/or try a | kWh (& VARh, if equipped) Pulse Contacts | |
larger value. | ||
| ||
Pulse Contact Closure | Note: The kWh pulse contact can keep up with a maximum power (Watts) | |
Duration in msec. | ||
of 1800000 x Wh pulse weight ÷ contact closure duration (in msec). | ||
Set to the slowest duration |
| |
that will keep up with the |
| |
theoretical max. system |
| |
power (register 135). The |
| |
open time ≥ the closure |
| |
time, so the max. pulse |
| |
rate (pulses per sec) is the |
| |
inverse of double the pulse |
| |
time. |
| |
|
|
Error Bitmap. 1 = Active:
Bit 0: Phase A Voltage out of range
Bit 1: Phase B Voltage out of range
Bit 2: Phase C Voltage out of range
Bit 3: Phase A Current out of range
Bit 4: Phase B Current out of range
Bit 5: Phase C Current out of range
Bit 6: Frequency out of the range of 45 to 65 Hz
Bit 7: Reserved for future use
Bit 8: Phase Loss A
Bit 9: Phase Loss B
Bit 10: Phase Loss C
Bit 11: Low Power Factor on A with one or more phases having a PF less than 0.5 due to
Bit 12: Low Power Factor on B
Bit 13: Low Power Factor on C
Bit 14: Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power (registers 3 and 261/262). To fix, increase the pulse energy register (register 144) and reset the energy accumulators (see reset register 129).
Bit 15: Energy pulse output configuration error (present pulse energy setting may not keep up with the theoretical max. system power; see register 135). To fix, increase the pulse energy (register 144).
Count of Energy Accumulator resets
Reserved (returns 0)
© 2011 Schneider Electric All Rights Reserved. | 31 |