Schneider Electric EM3555 manual Logging Configuration and Status, Lsb

Page 36

EM3555

ZL0093-0A

Modbus Point Map

11/2011

 

 

REGISTER

R/W

NV

Format

Units

Scale

Range

149

R/W

NV

UInt

 

 

1-6

150

R/W

NV

UInt

Seconds

 

0, 10-32767

151

R/W

 

UInt

 

 

1-32767

152

R

NV

UInt

 

 

0-32767

153

R

NV

UInt

 

 

0-32767

154

R

 

UInt

 

 

 

 

 

 

 

 

 

 

Description

Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals

 

that make a single demand interval. For block demand, set this to 1. Default is

 

1. When sub-interval length register #150 is set to 0 (sync-to-comms mode), this

Demand

register is ignored.

Calculation

 

Sub-Interval Length in seconds. For sync-to-comms, set this to 0 and use the reset register (129) to externally re-start the sub-interval. This is also the logging interval.

Reserved (returns 0)

Power Up Counter

Output Configuration. EM3555 units have a N.O. energy contact and N.C. (Form B) phase loss contact, so this register will always return a “0”.

Reserved (returns 0)

Logging Configuration and Status

 

 

 

 

 

 

 

Most Significant Byte (MSB)

Least Significant Byte

 

 

 

155

R/W

NV

UInt

Day /

 

See Bytes

(LSB)

 

 

 

 

 

 

 

 

 

Month

 

Day 1-31 (0x01-0x1F)

Month 1-12

Date / Time Clock. Following a power cycle, resets

 

 

 

 

 

 

 

 

 

 

 

 

 

(0x01-0x0C)

to:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Day 01

Month

01

 

 

 

 

Hour /

 

 

 

Year 0-199

156

R/W

NV

UInt

 

See Bytes

Hour 0-23 (0x00-0x17)

Hour 00

Year

(20) 00

Year

 

(0x00-0xC7)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Seconds

 

 

 

Minutes 0-59

 

 

 

157

R/W

NV

UInt

/

 

See Bytes

Seconds 0-59 (0x00-0x3B)

 

 

 

 

(0x00-0x3B)

 

 

 

 

 

 

 

Minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Logging Read Page Register. Selects which of the register logs to read (see registers 169-178). 1-10

 

 

 

 

 

 

 

are valid entries that put the meter into log reading mode, temporarily pausing logging. When set to 0

 

 

 

 

 

 

 

(no variable selected for reading), normal logging resumes. The meter will buffer one set of log entries

 

 

 

 

 

 

 

while in reading mode if a sub-interval timeout occurs (read/write collision). Default is 0.

158

R/W

NV

UInt

 

 

0-10

Note: this buffered data will be written to the log, and logging will resume on the following sub-interval

 

 

 

 

 

 

 

timeout whether the page register has been cleared or not, resulting in the appearance of data moving

 

 

 

 

 

 

 

in the buffer during reads. To avoid this, log buffer reads should be completed and this register set back

 

 

 

 

 

 

 

to 0 in less time than the demand sub-interval (preferred) or logging should be halted by setting Bit 1 in

 

 

 

 

 

 

 

register 158 (logs may be missed).

 

 

 

 

 

 

 

 

 

 

Logging Configuration Register (Bit Mapped):

 

 

 

159

R/W

NV

UInt

 

 

 

Bit 0: Clear to 0 for circular log buffer mode. Set to 1 for single shot logging mode. Default is 0 (Circular).

 

 

 

 

 

 

 

Bit 1: Clear to 0 to enable Logging. Set to 1 to halt logging. Default is 0 (Log).

 

 

 

 

 

 

 

Logging Status Register (Bit Mapped):

 

 

 

 

 

 

 

 

 

 

Bit 0: Log buffer full – Set to 1 when one single shot mode has filled the log buffer. In this condition,

 

 

 

 

 

 

 

the Logged Entry Count will continue to increment. Cleared to 0 when logging is restarted (see reset

 

 

 

 

 

 

 

command register 129).

 

 

 

 

 

 

 

 

 

 

 

Bit 1: Log Buffer Read Collision 1 – Set to 1 if the meter tried to save log data while the user was

 

 

 

 

 

 

 

reading the log (Logging Page Register has been set to something other than 0). On the first collision,

 

 

 

 

 

 

 

the meter holds the data until the next sub-interval and then writes the saved data to the log as well as

 

 

 

 

 

 

 

the data for that interval. This bit is cleared to 0 on the first demand interval with Logging Page Register

 

 

 

 

 

 

 

= 0.

 

 

 

 

160

R

NV

UInt

 

 

 

Bit 2: Log Buffer Read Collision 2 – Set to 1 on the 2nd attempt to save log data while the user is

 

 

 

 

 

 

 

reading the log (Logging Page Register is set to something other than 0). At this point the meter ignores

 

 

 

 

 

 

 

the read condition and does a double write, first of the values saved from the previous cycle, and then

 

 

 

 

 

 

 

the present values. If the read condition is not removed the meter continues to write the log data as it

 

 

 

 

 

 

 

normally would. This bit is cleared to 0 on the first demand interval with Logging Page Register = 0.

 

 

 

 

 

 

 

Bit 3: Logging Reset – The log has been reset during the previous demand sub-interval.

 

 

 

 

 

 

 

Bit 4: Logging Interrupted – logging has been interrupted (power cycled, log configuration change, etc.)

 

 

 

 

 

 

 

during the previous demand sub-interval.

 

 

 

 

 

 

 

 

 

 

Bit 5: RTC Changed – The real time clock had been changed during the previous demand sub-interval.

 

 

 

 

 

 

 

Bit 6: RTC Reset - The real time clock has been reset to the year 2000 and needs to be re-initialized.

 

 

 

 

 

 

 

 

 

 

 

 

32

© 2011 Schneider Electric All Rights Reserved.

Image 36
Contents EM3555 Hazard Categories Special Symbols Please NoteFCC Notice Contents EM3555 ZL0093-0A Contents 11/2011 Safety Precautions Installation OverviewDIN Rail Mounting Screw MountingSpecifications Type DescriptionSafety Environmental ConditionsMetering Category Observe correct CT orientation when installing the device IntroductionParts of the EM Series Dimensions EM Series DimensionsData Output Data Output Full Data Set FDSData Logging Installation Attach mounting clips for DIN RailSingle-Phase Wiring Three-Phase WiringSupported System Types Supported system typesWiring Symbol DescriptionWiring Symbols Wiring Diagrams DiagramDiagram Phase 4-Wire Wye Connection 3 CT 3 PT Use System Type 11 2LControl Power Wiring NotesFuse Recommendations L1 L2 L3Display Screen Diagram Display ScreenQuick Setup Instructions SOLID-STATE Pulse Output Solid State Pulse OutputsUI Menu Abbreviations Defined Main MenuIEC and Ieee Abbreviations DescriptionFor Data Configuration EM3555 User Interface for Data Configuration ALERT/RESET Information Ploss Lowpf ERR OVR PulseUser Interface for Setup FromEM3555 ZL0093-0A User Interface for Setup 11/2011 Daisy-chaining Devices to the Power Meter RS-485 CommunicationsConfiguration Data LoggingReading Data Read/Write CollisionStandard Modbus Default Settings Setting Value Modbus RegisterModbus Default Settings Supported Modbus Commands Command DescriptionSupported Commands Modbus Point MAPSunSpec Alliance Interoperability Specification Compliance Integer Data Summary of Active Phases Format Units Scale Range DescriptionFormat Units Scale Range 055 ULong KVARh Accumulated Q1 Reactive 079 ULong KVAh Accumulated Apparent Register 142 NV UInt 143 10000 144 500 250 145 Msec 146 Logging Configuration and Status LSB161 UInt 32767 162 163 164 0xFFFF ULong KWh 165 166 Month Floating Point Data Summary of Active Phases Floating Point Data Per Phase Logging Interface Sunspec Compliant Common and Meter Model Register Blocks Register Format Units Scale RangeSunSpec Description Name SunSpec 1.0 Common ModelSunSpec Description NameSunSpecCompliantCommonandMeterModelRegisterBlocks Event Bit Description Troubleshooting Problem Cause SolutionTroubleshooting China Rohs Compliance Information Efup TableEM3555 Installation Guide Schneider Electric

EM3555 specifications

Schneider Electric EM3555 is a highly efficient energy monitoring device that plays a crucial role in optimizing energy management across various applications. As part of Schneider Electric’s extensive range of products, the EM3555 is designed for professionals who seek robust solutions for monitoring energy usage and improving operational efficiency.

One of the main features of the EM3555 is its advanced energy consumption monitoring capabilities. It provides real-time data on electrical parameters, including voltage, current, frequency, power factor, and active/reactive power. This level of detailed information helps organizations understand their energy consumption patterns, identify inefficiencies, and take corrective actions to enhance energy performance.

The EM3555 is equipped with a user-friendly display that allows for easy access and navigation through various metrics. This display offers visibility into key performance indicators and alerts users to any anomalies in energy consumption. Enhanced energy visibility is critical for effective decision-making and is particularly beneficial in environments where energy management is paramount.

In terms of technology, the EM3555 incorporates the latest communication protocols, including Modbus RTU. This feature facilitates seamless integration with existing systems, enabling users to collect and analyze data efficiently. Furthermore, the EM3555 can be connected to Schneider's EcoStruxure platform, which offers advanced analytics and insights into energy usage, harnessing the power of IoT for smarter energy management.

Another notable characteristic of the EM3555 is its compact design, making it suitable for various installation environments, including electrical panels and equipment rooms. The device is built to withstand harsh industrial conditions, ensuring long-term reliability and durability.

In conclusion, the Schneider Electric EM3555 is an exemplary energy monitoring solution that combines advanced features, cutting-edge technology, and robust characteristics. By providing real-time insights into energy consumption, the EM3555 empowers organizations to improve their energy efficiency, reduce costs, and contribute to sustainability goals. Its integration capabilities with other systems further underline its value in contemporary energy management practices. With the EM3555, Schneider Electric continues to lead the way in developing innovative solutions for a more sustainable future.