Cisco Systems UCS C420 Rack Requirements, Equipment Requirements, Slide Rail Adjustment Range

Page 22

Chapter 2 Installing the Server

Preparing for Server Installation

Rack Requirements

This section provides the requirements for the standard open racks, assuming an external ambient air temperature range of 41° F to 95° F (5° C to 35° C).

The rack must be of the following type:

A standard 19-in. (48.3-cm) wide, four-post EIA rack, with mounting posts that conform to English universal hole spacing, per section 1 of ANSI/EIA-310-D-1992.

The rack post holes can be square 0.38-inch (9.6 mm), round 0.28-inch (7.1 mm), #12-24 UNC, or #10-32 UNC when you use the supplied slide rails.

The minimum vertical rack space per server must be two RUs, equal to 3.5 in. (88.9 mm).

Equipment Requirements

The slide rails supplied by Cisco Systems for this server do not require tools for installation if you install them in a rack that has square 0.38-inch (9.6 mm), round 0.28-inch (7.1 mm), or #12-24 UNC threaded holes. The inner rails (mounting brackets) are preattached to the sides of the server.

However, if you install the slide rails in a rack that has #10-32 round holes, a flat-bladed screwdriver is required to remove the larger square or round mounting pegs from the front of the slide rails.

Slide Rail Adjustment Range

The slide rails for this server have an adjustment range of 26 to 36 inches (660 to 914 mm).

Cisco UCS C420 Server Installation and Service Guide

2-4

OL-27640-01

 

 

Image 22
Contents Cisco UCS C420 Server Installation and Service Guide Americas HeadquartersPage N T E N T S Special Considerations for Cisco UCS Virtual Interface Cards For More Information C-6 OL-24342-01 Organization AudienceChapter Title Description Conventions Bewaar Deze InstructiesAvvertenza Importanti Istruzioni Sulla Sicurezza Warnung Wichtige SicherheitshinweiseAviso Instruções Importantes DE Segurança Guarde Estas Instrucciones GEM Disse Anvisninger Xii Xiii Related Documentation Documentation FeedbackOverview of the Cisco UCS C420 Server 2shows the rear panel features of the server 1lists the features of the server StandardCisco UCS C420 Server Features Installing the Server StatementServer Documentation Power cord up to two KVM cable Unpacking and Inspecting the ServerPreparing for Server Installation Installation GuidelinesRack Requirements Slide Rail Adjustment RangeEquipment Requirements Installing the Server In a Rack This section describes how to install the server in a rackInserting the Server into the Slide Rails Attaching the Cable Management Arm Connecting and Powering On the Server Standalone Mode Initial Server SetupThis section includes the following topics Installing the Server Initial Server Setup OL-27640-01 NIC Modes and NIC Redundancy Settings System Bios and Cimc Firmware Updating the Bios and Cimc FirmwareAccessing the System Bios Service DIP Switch DIP Switch Location on the I/O RiserUsing the Bios Recovery DIP Switch If These Steps do not Recover the BiosInstalling the Server Service DIP Switch Server Monitoring and Management Tools Server Configuration UtilityCisco Integrated Management Interface Status LEDs and Buttons Front-Panel LEDsLED Name State Rear-Panel LEDs and Buttons Rear-Panel LEDs and ButtonsRear-Panel LED States LED Name State Internal Diagnostic LEDs LED Name StateShutting Down and Powering Off the Server Preparing for Server Component InstallationRequired Equipment Removing and Replacing the Server Top Cover Release buttons Front cover panelReplaceable Component Locations See also -23 on page 3-40for detailsInstalling or Replacing Server Components Color-Coded Touch PointsReplacing Hard Drives or Solid State Drives Drive Population GuidelinesDrive Replacement Procedure Release button Drive tray securing screws Ejector leverReplacing a Modular Drive Bay Assembly Drive Bay Assembly and Transition Card Two VersionsOL-27640-01 Removing and Replacing the Drive-Bay Module Replacing Fan Modules FAN11 Removing and Replacing Fan Modules Replacing a Fan Tray 12 Removing and Replacing a Fan Tray Replacing DIMMs Dimm Performance Guidelines and Population RulesCPU Socket Color Black# of DIMMs Memory Mirroring Mode Dimm Replacement Procedure Replacing CPUs and Heatsinks CPU Replacement Procedure Open the hinged CPU cover plate. See Figure14 CPU Retaining Latches 16 Removing or Inserting a CPU Icon. See -14 on 18 Thermal Grease Application Pattern Replacing the Motherboard RTC Battery 19 Removing and Replacing the Motherboard RTC Battery Replacing a PCIe Riser Assembly 20 Removing and Replacing the PCIe Riser Assembly Replacing an I/O Riser 21 I/O Riser, Including SD Card SlotsRiser in designated motherboard socket Riser securing screw 22 Removing and Replacing an I/O RiserReplacing an Internal SD Card Replacing a PCIe Card PCIe SlotsNCSI3 Support Slot Number Lane Width Connector LengthElectrical Card Length1 Primary Slot Secondary Slot Alternate SlotsPCIe card socket on PCIe riser assembly Card retaining clip 24 PCIe Riser Assembly Side ViewReplacing a PCIe Card in a Motherboard Slot 25 Hinged PCIe Card Retainer on Rear of Chassis Supported Cisco Card NIC Server VICs Mode Firmware Integration Fabric InterconnectMinimum Firmware for Nexus OS on an Use With UCS Upstream NexusResolving Insufficient Memory Space to Execute Option ROMs Resolving Insufficient 16-Bit I/O Space 27 vNIC Properties Dialog Replacing the Supercap Power Module RAID Backup Unit 28 Removing the Scpm Installing a Trusted Platform Module 29 TPM Socket Location on Motherboard Set TXT Support to Enabled Replacing Power Supplies 30 Removing and Replacing Power SuppliesEnabling or Disabling the Internal USB Port OL-27640-01 Table A-1lists the physical specifications for the server Physical SpecificationsDescription Specification Environmental Specifications Power SpecificationsSupported Power Cords and Plugs Length Power Cord Description Feet MetersPower Cord, 250 VAC 13 a IEC60320 Plug North America Power Cord, 250 VAC 10 a CEI 23-16 Plug ItalyPower Cord, 250 VAC 10 a MP232 Plug Switzerland Power Cord, 250 VAC 13 a Nema 6-15 Plug North AmericaAC Power Cord Illustrations CAB-9K10A-AUCAB-9K10A-EU CAB-9K10A-SW CAB-N5K6A-NA Figure B-13 CAB-C13-CBN, Jumper Power Cord 0.68 m OL-24342-01 RAID Levels Supported RAID Controllers and Required CablesMaximum Optional Required Cables1 Controller Style Drives With expander3 Two controllers with two nonexpandersRAID Controller Cabling Supercap Power Modules RAID Backup UnitsMixing Drive Types in RAID Groups Mix of Drive Types RAID Group Allowed?334371 334646 334373 Foreign configurations found on adapter For More InformationPage OL-27640-01 Installation for Cisco UCS Integration OL-24342-01