Intel SC450NX manual Equipment Rack Precautions

Page 7

Equipment Rack Precautions

WARNINGS

ANCHOR THE EQUIPMENT RACK: The equipment rack must be anchored to an unmovable support to prevent it from falling over when one or more servers are extended in front of it on slide assemblies. The anchors must be able to withstand a force of up to 113 kg (250 lbs). You must also consider the weight of any other device installed in the rack.

MAIN AC POWER DISCONNECT: You are responsible for installing an AC power disconnect for the entire rack unit. This main disconnect must be readily accessible, and it must be labeled as controlling power to the entire unit, not just to the server(s).

GROUNDING THE RACK INSTALLATION: To avoid the potential for an electrical shock hazard, you must include a third wire safety grounding conductor with the rack installation. If server power cords are plugged into AC outlets that are part of the rack, then you must provide proper grounding for the rack itself. If server power cords are plugged into wall AC outlets, the safety grounding conductor in each power cord provides proper grounding only for the server. You must provide additional, proper grounding for the rack and other devices installed in it.

Overcurrent protection: The server is designed for an AC line voltage source with up to 20 amperes of overcurrent protection. If the power system for the equipment rack is installed on a branch circuit with more than 20 amperes of protection, you must provide supplemental protection for the server. If more than one server is installed in the rack, the power source for each server must be from a separate branch circuit. The overall current rating of a server configured with three power supplies is under 12 amperes.

CAUTIONS

Temperature: The operating temperature of the server, when installed in an equipment rack, must not go below 5 °C (41 °F) or rise above 35 °C (95 °F). Extreme fluctuations in temperature can cause a variety of problems in your server.

Ventilation: The equipment rack must provide sufficient airflow to the front of the server to maintain proper cooling. It must also include ventilation sufficient to exhaust a maximum of 4,100 Btu's per hour for the server. The rack selected and the ventilation provided must be suitable to the environment in which the server will be used.

vii

Image 7
Contents SC450NX MP Server Rack/Pedestal Kit Installation Guide Page Copyright ã 1998, Intel Corporation. All Rights Reserved Page Server Precautions Safety GuidelinesPage Equipment Rack Precautions Viii Contents Page Introduction Tools You Need SC450NX MP Server Physical SpecificationsPrepare the Slide Assemblies Configuring for Rack MountAttaching the Bezel Frame and Door Prepare the ServerAttach the Small Bar of the Slide Assembly to the Server Right-angle Bracket and Vertical Rail Prepare the Equipment RackCenter Bar and Large Outer Bar Assembly Install the Server in the Rack Installing the Server in the Rack Page Install Chassis Feet Configuring for Pedestal MountInstall the Top and Side Covers Install Bezel Frame and Door Remove the Covers Changing from Pedestal to RackExchange the Bezel Frame