Problem: Measured inverter output is too low.

Possible Cause

Solution

Astandard “average-reading” AC voltmeter has been used to measure output voltage, resulting in an apparent reading 5–15 V too low.

The battery voltage is too low.

For accurate measurement, the Digital Inverter modified sine wave output requires a “true RMS” voltmeter for accurate measurements.

Recharge the battery.

Problem: Battery run time is less than expected.

Possible Cause

Solution

The AC product power consumption is higher than rated.

Use a larger battery to make up for the increased power requirement.

The battery is old or defective.

The battery is not being charged properly.

Replace the battery.

Some chargers are not able to fully recharge a battery. Make sure that you use a powerful charger.

Power dissipation in DC cables. Use shorter/heavier DC cables.

29

Image 33
Contents Digital Inverter 200 W, 400 W, 800 W Trademarks About XantrexDisclaimer Date and RevisionContents Maintaining Battery Condition Troubleshooting Introduction About This Guide Important Safety Information Page Additional Safety Guidelines AC Front Panel Digital Inverter FeaturesAC Panel of 400 W unit 2B 2A DC Back PanelFan and Ventilation Openings Digital Display Panel Digital Display Top PanelDigital Display Panel Functions Cable Clamps/Battery Types of ConnectionsProduct Lighter Plug Connection Connections Lighter Plug Cable AccessoriesChoosing a Location Connecting the Digital InverterConnecting for Loads Under 150 W Connecting for Loads Over 150 W Page Page Operating Conditions and Guidelines Operating the Digital InverterShutting the inverter off Operating normal loads Min Max Continuous Surge Rating Product Power RatingOperating loads with high surge requirements Producta Wattsb Unit Wattage of Common AC ProductsInverter Load Sample Appliance Operating Time Maintaining Battery ConditionPage Troubleshooting Common Problems Buzz in audio systemsTelevision interference Possible Cause Solution Troubleshooting ReferenceProblem Measured inverter output is too low Error Possible Cause Unit Unita SpecificationsLow voltage alarm Warranty Warranty and ReturnTelephone 1 Fax Product DisclaimerExclusions Return Material Authorization Policy Page Return Procedure Other Xantrex Products Out of Warranty Service