Problem: The AC load will not operate, error code shows on digital display and alarm is sounding.
Error | Possible Cause | Solution |
E01 Low voltage shutdown because
battery is discharged.
E02
of high input voltage.
E03 The AC product(s) connected are rated at more than the inverter’s continuous power rating; overload shutdown has occurred.
Recharge battery.
Shorten cables or use heavier cables.
Verify the charging system is properly regulated and the battery is 12 V nominal.
Use a product with a power rating within the inverter’s continuous power rating (see Table 3).
E04 The inverter has overheated due to poor ventilation. Overheating shutdown has occurred.
E05 The AC products connected have a surge power that exceeds the Digital Inverter’s surge capability or the AC products connected are
Turn inverter off and allow to cool for 15 minutes. Clear blocked fan or remove objects covering unit.
Move the inverter to a cooler place. Reduce load if continuous operation is required.
The products exceed the inverter’s surge capability. Use a product with a starting surge power within the Digital Inverter’s capability.