Xantrex Technology 800 W, 400 W, 200 W manual Error Possible Cause

Page 34

Problem: The AC load will not operate, error code shows on digital display and alarm is sounding.

Error

Possible Cause

Solution

E01 Low voltage shutdown because

battery is discharged.

E02 Over-voltage shutdown because

of high input voltage.

E03 The AC product(s) connected are rated at more than the inverter’s continuous power rating; overload shutdown has occurred.

Recharge battery.

Shorten cables or use heavier cables.

Verify the charging system is properly regulated and the battery is 12 V nominal.

Use a product with a power rating within the inverter’s continuous power rating (see Table 3).

E04 The inverter has overheated due to poor ventilation. Overheating shutdown has occurred.

E05 The AC products connected have a surge power that exceeds the Digital Inverter’s surge capability or the AC products connected are short-circuited and shutdown has occurred.

Turn inverter off and allow to cool for 15 minutes. Clear blocked fan or remove objects covering unit.

Move the inverter to a cooler place. Reduce load if continuous operation is required.

The products exceed the inverter’s surge capability. Use a product with a starting surge power within the Digital Inverter’s capability.

30

Image 34
Contents Digital Inverter 200 W, 400 W, 800 W Disclaimer About XantrexTrademarks Date and RevisionContents Maintaining Battery Condition Troubleshooting Introduction About This Guide Important Safety Information Page Additional Safety Guidelines Digital Inverter Features AC Front PanelAC Panel of 400 W unit DC Back Panel 2B 2AFan and Ventilation Openings Digital Display Top Panel Digital Display PanelDigital Display Panel Functions Types of Connections Cable Clamps/BatteryProduct Lighter Plug Connection Connections Accessories Lighter Plug CableConnecting the Digital Inverter Choosing a LocationConnecting for Loads Under 150 W Connecting for Loads Over 150 W Page Page Operating the Digital Inverter Operating Conditions and GuidelinesShutting the inverter off Min Max Continuous Surge Rating Product Power Rating Operating normal loadsOperating loads with high surge requirements Wattage of Common AC Products Producta Wattsb UnitMaintaining Battery Condition Inverter Load Sample Appliance Operating TimePage Troubleshooting Buzz in audio systems Common ProblemsTelevision interference Troubleshooting Reference Possible Cause SolutionProblem Measured inverter output is too low Error Possible Cause Specifications Unit UnitaLow voltage alarm Warranty and Return WarrantyTelephone 1 Fax Disclaimer ProductExclusions Return Material Authorization Policy Page Return Procedure Out of Warranty Service Other Xantrex Products