Trane WSHP-DS-6 manual General Data, Table G-1 Physical Data English

Page 8

General

Data

Table G-1: Physical Data (English)

 

Model: WPWD

024

036

042

048

060

072

 

Width of cabinet (in)

23

23

23

23

23

23

Unit Size

Width of cabinet and connections (in)

24.8

24.8

24.8

24.8

24.8

24.8

Height (in)

24.3

24.3

24.3

24.3

24.3

24.3

 

 

Depth (in)

23.3

23.3

23.3

23.3

23.3

23.3

Compressor

Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

R-22

Refrigerant (lbs)

3.25

3.375

3.50

4.00

4.25

4.25

Approximate Weight

With crate (lbs)

163

183

203

214

244

277

(lbs)

 

 

 

 

 

 

 

Table G-2: Specifications (English)

 

Model: WPWD

024

036

042

048

060

072

Source and Load

GPM

 

4.0

6.0

7.0

7.50

10

10

 

 

 

 

 

 

 

 

 

Source and Load

Ft. Hd.

 

1.4

3.2

4.4

5.0

9.2

9.2

Cooling

Load EWT 45

F (MBH)

18.24

26.74

31.3

35.55

45.98

51.01

Cooling

Load EWT 45

F (EER)

15.0

15.7

15.7

15.4

15.5

14.9

Heating

Load EWT 100 F (MBH)

25.38

33.34

39.69

42.87

57.15

67.47

Heating

Load EWT 100 F (COP)

3.64

3.62

3.7

3.45

3.62

3.62

Note:

θSource EWT (entering water temperature) is at 75 F

θUnit selection should be based upon extended specifications at lowest or highest expected source and load EWT (entering water temperature)

θRefer to pages 19-25 for extended performance tables.

8

Image 8
Contents WSHP-DS-6 March Water Source Heat Pump Water-to-Water Model WpwdIntroduction Table of Contents Features General Benefits Features Controls Benefits Circulating Pump Features Heat Recovery BenefitsDesuperheater Option Digit 8 Voltage / Hertz / Phase Model Number DescriptionGeneral Data Table G-1 Physical Data EnglishApplication Considerations Closed Loop SystemOpen Loop System Cooling Tower/Boiler SystemApplication Source Side Considerations Load Side Source vs. LoadTypical Benefits Application Closed Loop Considerations GeothermalGeothermal Integrated System Application Fresh Air Considerations Ventilation Water-to-Water Fresh Air VentilationApplication Fresh Air Considerations Ventilation Mechanical Application Central Considerations Pumping System Central Pump ApplicationApplication Well Water Considerations Systems Well Water ApplicationApplication Distributed Considerations Pumping System Earth Coupled ApplicationElectrical Data Table E-1 Electrical Data

WSHP-DS-6 specifications

The Trane WSHP-DS-6, or Water Source Heat Pump - Design Series 6, is a highly efficient and versatile solution designed to meet the complex heating and cooling needs of commercial buildings. With a firm reputation for reliability and performance, the WSHP-DS-6 integrates advanced technologies to optimize energy consumption and enhance climate control.

One of the standout features of the WSHP-DS-6 is its exceptional efficiency ratings. The unit boasts a high Coefficient of Performance (COP) and Energy Efficiency Ratio (EER), ensuring that it delivers cost-effective heating and cooling while minimizing energy usage. This not only lowers operational costs but also contributes to reduced environmental impact.

The heat pump is equipped with a hermetically sealed scroll compressor, known for its durability and quiet operation. This technology allows for smooth operation under a variety of conditions, making the WSHP-DS-6 suitable for different environments. The compressor, combined with a robust heat exchanger, ensures optimal heat transfer, resulting in enhanced overall system performance.

Another notable characteristic of the WSHP-DS-6 is its compact design, which facilitates easy installation in a variety of settings, including tight spaces often found in urban environments. Additionally, the unit comes with advanced controls that allow for precise temperature management, ensuring the indoor environment remains comfortable year-round.

The WSHP-DS-6 also supports water heating capabilities, providing hot water on demand. This flexibility makes it a cost-effective solution for facilities that require both space heating and hot water supply, such as hotels, schools, and healthcare facilities.

Moreover, the unit features integrated zone control options, which enable the customization of heating and cooling for different areas within a building. By allowing targeted climate control, the WSHP-DS-6 enhances occupant comfort while further improving overall energy efficiency.

In terms of sustainability, the WSHP-DS-6 is designed to work effectively with environmentally friendly refrigerants, aligning with current regulations and promoting eco-friendly practices. This commitment to sustainability, combined with superior performance features, makes the Trane WSHP-DS-6 a top choice for building managers seeking reliable and efficient climate control solutions.

Overall, the Trane WSHP-DS-6 represents a perfect blend of technology, efficiency, and adaptability, making it an excellent investment for commercial property owners focused on sustainable building management.