W415-0120 / E / 01.11.05
- clean the glass with a recommended gas fireplace glass cleaner. DO NOT CLEAN GLASS WHEN HOT.
If deposits are not cleaned off regularly, the glass may be- come permanently marked.
White / grey film forms.
Sulphur from fuel is being depos- ited on glass, logs or combus- tion chamber surfaces.
- check that the logs are correctly positioned. - open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifice size as specified by the rating plate values.
Carbon is being de- Flame is impinging on the logs posited on glass, logs or combustion chamber.
or combustion cham- ber surfaces.
- check for chimney blockage.
- check that chimney is installed to building code.
- room is in negative pressure; increase fresh air supply.
fumes Fireplace is spilling. room,
Exhaust smelled in headaches.
Faulty valve.
- replace.
Remote wall switch wire is grounding.
- check for ground (short); repair ground or replace wire.
Remote wall switch is grounding.
- replace.
Wall switch is mounted upside down.
Remote wall switch is in off position; main burner comes on when gas knob is turned to "ON" posi- tion.
- reverse.
Flame is impinging on the logs or combustion chamber.
- ensure air shutter opening is free of lint or other obstruc- tions.
- check that the logs are correctly positioned. - open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifice size as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that the seal is tight.
- check that both 4" and 7" vent liners are free of holes and well sealed at all joints.
- check that minimum rise per foor has been adhered to for any horizontal venting.
Air shutter has become blocked
Carbon is being de- posited on glass, logs or combustion chamber surfaces.
Thermopile shorting.
- clean thermopile and thermopile connection to valve.
Main burner goes out; Pilot flame is not large enough
pilot stays on. or not engulfing the thermopile.
- replace.
- turn on pilot flame. Gently twist the pilot head to improve the flame pattern aroung the thermopile.
Faulty spill switch.
Liner disconnected from insert. - re-attach liner.
Chimney is blocked
- check for chimney blockage.
- wait ten minutes. Shut off all exhaust fans in the house (ie: kitchen and bathrooms), furnace, and clothes dryer. Open windows and/or doors. Start fireplace and monitor its opera- tion.
Close doors and windows and start appliances as before; room is in negative pressure; increase fresh air supply.
Chimney down-drafting
Main burner goes out; Refer to "Main burner goes out; pilot stays on" pilot goes out.
PROBLEM
SYMPTOM
TEST SOLUTION
14
Image 14
Contents GAS Inserts Table of Contents Conditions and Limitations Care of Glass and Plated General InstructionsGeneral Information Installation Wire Size MAX. Length Fibre Firebrick Panels LOG Placement FinishingOperation / Maintenance Logo PlacementMaintenance For Your Safety Read Before LightingVenturi Adjustment AdjustmentsPilot Burner Adjustment Blower SystemReplacements Replacement PartsW415-0120 / E Trouble Shooting Guide Symptom Problem Test SolutionPage Fireplace Service History W415-0120 / E

CBI 360-N, CBI 360-P specifications

The Continental CBI 360-N and CBI 360-P represent cutting-edge advancements in the realm of continental industrial solutions, designed specifically to meet the diverse needs of modern industries. These models stand out due to their innovative technologies, robust performance, and versatility, making them essential tools for various applications.

One of the defining features of the CBI 360-N and CBI 360-P is their exceptional durability. Built with high-quality materials, these models are engineered to withstand tough industrial environments, ensuring longevity and consistent performance even under extreme conditions. The robust construction not only enhances their lifespan but also reduces maintenance costs, offering a cost-effective solution for users.

Another significant aspect is the advanced monitoring and diagnostic technologies integrated into these models. They come equipped with smart sensors that provide real-time data on operating conditions, allowing for proactive maintenance and troubleshooting. This feature not only optimizes performance but also enhances safety by minimizing the risk of unexpected breakdowns.

The CBI 360-N and CBI 360-P also boast energy-efficient designs. With a focus on reducing energy consumption, these models are equipped with high-performance motors and intelligent control systems that optimize power usage. This not only contributes to lower operational costs but also aligns with global sustainability goals, making them an environmentally friendly choice.

Versatility is another hallmark of the CBI 360 series. The CBI 360-N is particularly suited for standard applications, while the CBI 360-P offers enhanced power capabilities for more demanding tasks. This flexibility allows operators to select the appropriate model based on their specific requirements, making these machines suitable for a wide range of industrial sectors, including manufacturing, logistics, and more.

Furthermore, user-friendly interfaces and intuitive controls are central to the design of the CBI 360-N and CBI 360-P. Operators can easily configure settings and monitor performance through streamlined control panels, enhancing productivity and reducing the learning curve for new users.

In conclusion, the Continental CBI 360-N and CBI 360-P stand at the forefront of industrial innovation, offering a blend of durability, efficiency, and versatility. Their advanced technologies and practical features make them invaluable assets for businesses looking to improve operational efficiency and reliability in an ever-evolving industrial landscape. With these models, Continental continues to lead the way in providing high-quality, dependable industrial solutions.