Desa (V)TC36NE Series, (V)TC36GPE Series installation manual Connecting Fireplace to GAS Supply

Page 19

FIREPLACE INSTALLATION

Installing Gas Piping to Fireplace Location (Cont.) Connecting Fireplace To Gas Supply Checking Gas Connections

19

FIREPLACE INSTALLATION

Continued

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" inside diameter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.

Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 31).

IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas con- trols. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.

CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap*

 

 

Natural - From

 

 

Gas Meter (5.5"

 

 

W.C. to 10.5"

Approved Flexible

 

W.C. Pressure)

Gas Line

 

Propane/LP

 

 

From External

 

 

Regulator (11"

 

 

W.C. to 14" W.C.

3" Minimum

Pressure)

 

 

Cap

Pipe Nipple Tee Joint

Figure 31 - Gas Connection

Sediment Trap/Drip Leg

 

 

*The CSAdesign-certified equipment shutoff valve may be supplied with the appliance or you can purchase it from your retailer.

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

 

Red Surface Indicates

Equipment

For Propane/LP Use Only

Flexible Gas Line

Shutoff Valve

Do NOT Kink

1/2" NPT Incoming

 

 

Gas Line

Inlet Pressure Tap

Outlet Pressure Tap

 

Note: Wire Connections Not Shown for Clarity

Figure 32 - Connecting Flexible Gas Line to Electronic Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air.

4.Check all joints of gas supply piping system. Apply noncor- rosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

116234-01A

www.desatech.com

Image 19
Contents For Your Safety What to do if YOU Smell GAS For Your SafetySafety Information Table of ContentsLocal Codes Safety Information Product IdentificationPRE-INSTALLATION Preparation Product FeaturesLocation and Space Requirements Specific venting clearances ClearancesFraming and Finishing VentTermination CAP AIR Supply Inlet GAS Meter Location of Termination CAPInstallation Precautions Venting Installation InstructionsCenter Installation PlanningHorizontal Termination Installation Male Female Slots Locking LugsVent Pipe Vent Cap Wood ScrewInterior Wall Surface Firestop Vent Cap HorizontalHorizontal Termination Configurations Over 12 horizontal pipe Recommended Applications Corner ground floor installationTermination is possible Venting with Two 90 Elbows Roof Flashing Wall Strap Elbow Ceiling Firestop Installation for Vertical TerminationFlat Ceiling Installation Connect a section of pipe and extend up through the holeElbow Into inner collar fireplace as shown Vertical Termination ConfigurationsHigh Altitude Installation Desa 5/8 Pipe & Vent Kits Venting InstallationFireplace Installation Check GAS Type Installing Optional Blower AccessoryDecal on the firebox bottom approximately 12 in front Fireplace InstallationModel BKT Installation By turning knob fully counterclockwise before continuingBlower Wiring Diagram Installing GAS Piping to Fireplace LocationInstallation Items Needed Pressure Testing Gas Supply Piping System Connecting Fireplace to GAS SupplyChecking GAS Connections Bubbles forming show a leak. Correct all leaks at once Pressure Testing Fireplace Gas ConnectionsREMOVING/REPLACING Glass Door Removing Louver PanelsCleaning Glass Door Installing Lava Rock and Glowing EmbersRemoving Glass Door Extension Cord Ignition Installing Brick Liner Models BL36DASA and BL36DHASAWall Switch Installation Optional Remote ControlEquipment Pilot Wiring DiagramOperating Fireplace Lighting InstructionsOperation Operating Optional Blower AccessoryTo Turn OFF GAS To Appliance Optional RemoteLogs Cleaning MaintenanceGlass Door Pilot and BurnersTroubleshooting Restrictions or obstruction PositionBL36DHASA for log/grate removal Improper vent configurationParts Under Warranty Replacement PartsService Hints Technical ServiceSpecifications Models TC36NE, VTC36NE, TC36PE and VTC36PE Illustrated Parts BreakdownKEY Part Number TC36NE/PE VTC36NE/PE Description QTY Parts List19 18 2827 116234-01A KEY Part Number Description Accessories Model BrandDate Purchased Serial Number Industrial Drive Box Bowling Green, KY 116234-01A Model Serial No Date Purchased Warranty InformationIndustrial Drive P.O. Box