Desa (V)VC36NE Series, (V)VC36PE Series installation manual Installation for Vertical Termination

Page 13

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination

13

VENTING INSTALLATION INSTRUCTIONS

Continued

INSTALLATION FOR VERTICAL TERMINATION

Note: Vertical restrictor must be installed in all vertical installations.

1.Determine the route your vertical venting will take. If ceiling joists, roof rafters or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insu- lation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations.

2.Set the fireplace in desired location. Drop a plumb line down from the ceiling to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Roof Flashing

Wall Strap

45° Elbow

Ceiling Firestop

Figure 19 - Offset with Wall Strap and 45° Elbows

Flat Ceiling Installation

1.Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4"x10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 8 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

2.Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Figure 8, page 8).

3.Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4"x10 3/4" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 8.

4.Connect a section of pipe and extend up through the hole.

Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

5.Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 19. There must be a 1" clearance from the vent pipe to combustible materials.

6.Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 7 on page 6. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.

7.Twist-lock the vent cap onto the last section of vent pipe.

Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure and meet the minimum allow- able clearances to combustibles. Do not fill any of the required air spaces with insulation.

If area above is a room or

If area above is not a room, install

insulated area, install firestop

firestop below framed hole.

above framed hole.

 

Figure 20 - Installing Firestop

116235-01B

www.desatech.com

Image 13
Contents For Your Safety What to do if YOU Smell GAS For Your SafetySafety Information Table of ContentsLocal Codes Safety Information Product IdentificationControl Valve BlowerPRE-INSTALLATION Preparation Product FeaturesLocation and Space Requirements Framing and Finishing Clearances35 3/4 133/4 10 3/8 49 5/8 681/2Termination CAP AIR Supply Inlet GAS Meter Location of Termination CAPInstallation Precautions Venting Installation InstructionsHorizontal Termination Installation Installation PlanningMale Female Slots Locking Lugs CenterInterior Wall Surface Firestop Vent Cap Vent Cap Wood ScrewHorizontal Vent PipeHorizontal Termination Configurations 30 max VerticalSnorkel Termination Minimum Venting with Two 90 Elbows Flat Ceiling Installation Installation for Vertical TerminationRoof Flashing Wall Strap Elbow Ceiling Firestop If area above is a room orElbow Into inner collar fireplace as shown Vertical Termination ConfigurationsHigh Altitude Installation Fireplace Installation Check GAS Type Venting InstallationInstalling Optional Blower Accessory Desa 5/8 Pipe & Vent KitsModel BKT Installation Fireplace InstallationBlower Wiring Diagram Installing GAS Piping to Fireplace LocationInstallation Items Needed Pressure Testing Gas Supply Piping System Connecting Fireplace to GAS SupplyChecking GAS Connections REMOVING/REPLACING Glass Door Pressure Testing Fireplace Gas ConnectionsRemoving Louver Panels Cleaning Glass Door Installing Lava Rock and Glowing EmbersRemoving Glass Door Wall Switch Installation Installing Brick Liner Models BL36DASA and BL36DHASAOptional Remote Control For Your Safety Read Before Lighting Wiring DiagramOperating Fireplace Lighting InstructionsTo Turn OFF GAS To Appliance Operating Optional Blower AccessoryOptional Remote OperationGlass Door Cleaning MaintenancePilot and Burners LogsObserved Problem Possible Cause Remedy TroubleshootingGas leak. See Warning statement at Service Hints Replacement PartsTechnical Service Parts Under WarrantySpecifications Models VC36NE, VVC36NE, VC36PE and VVC36PE Illustrated Parts BreakdownKEY Part Number Description QTY Parts List2827 19 18 KEY Part Number Description Accessories Model BrandDate Purchased Serial Number Industrial Drive Box Bowling Green, KY 116235-01B Model Serial No Date Purchased Warranty InformationIndustrial Drive P.O. Box