Desa (V)VC36NE Series, (V)VC36PE Series Troubleshooting, Observed Problem Possible Cause Remedy

Page 26

26

TROUBLESHOOTING

TROUBLESHOOTING

Note: Before troubleshooting the system, make sure the gas shutoff valve is ON.

The two most common causes of a malfunctioning gas appliance are:

1.Loose wiring connections

2.Construction debris clogging the pilot and/or gas control valve filter

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle or similar object to clean pilot. This can damage pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

 

Ignitor will not spark or pilot will not light

1.

No gas supply or shutoff valve is OFF

1.

Check to see if you have gas supply and

 

 

 

 

that equipment shutoff valve is opened

 

2.

Air in gas line

2.

Repeat lighting procedure several times

 

 

 

 

to purge all air out of lines. If after re-

 

 

 

 

peated attempts appliance does not light,

 

 

 

 

call for qualified service and repair.

 

3.

Construction debris clogging pilot orifice

3.

Remove debris and dirt, inspect and

 

 

 

 

clean any other possible obstructions

 

4.

Low gas pressure

4.

Contact your gas supplier to check

 

 

 

 

pressure

 

5.

Kinked pilot line

5.

Have a qualified technician replace pilot

 

 

 

 

line

 

6.

Control valve is not opeining

6.

Replace control valve (Refer to Replace-

 

 

 

 

ment Parts, page 28)

 

7.

No power to unit or the ignition module

7.

Check that main power is on and that all

 

 

or power transformer is bad

 

wire connections are made correctly to

 

 

 

 

the ignition model (see Wiring Diagram,

 

 

 

 

page 23). Check for 24 VAC at the

secondary side of the transformer. If 24 VAC is present and the module does not operate, have the module replaced oth- erwise have the transformer replaced

Pilot will not stay lit

1.

Loose wiring on ignitor wire to ignition

 

 

module and/or poor ground to ignition

 

 

module

 

2.

Pilot flame too low to sense

1.Check wiring connection. Refer to wir- ing diagram (see Wiring Diagram, page 23) and/or check ground wire to ignition module

2.Clean and adjust pilot burner and check gas supply and inlet pressure to unit

Note: Have a qualified technician replace pilot assembly if broken or corroded

No gas to burner, although wall switch is

1.

Wall switch wires defective or too

1.

Check electrical connections

set to the ON position

 

long

 

 

 

 

 

 

 

Frequent pilot outage

1.

Pilot flame may be too low, causing

1.

Clean and adjust pilot flame for maximum

 

 

safety pilot to “drop out”

 

flame impingement on thermopile

 

2.

Improper venting or excessive blockage

2.

Have the vent system inspected, includ-

 

 

 

 

ing the termination cap. Remove any

 

 

 

 

restriction or obstruction

www.desatech.com

116235-01B

Image 26
Contents For Your Safety For Your Safety What to do if YOU Smell GASTable of Contents Safety InformationControl Valve Safety Information Product IdentificationLocal Codes BlowerLocation and Space Requirements Product FeaturesPRE-INSTALLATION Preparation 35 3/4 133/4 10 3/8 49 5/8 ClearancesFraming and Finishing 681/2Location of Termination CAP Termination CAP AIR Supply Inlet GAS MeterVenting Installation Instructions Installation PrecautionsMale Female Slots Locking Lugs Installation PlanningHorizontal Termination Installation CenterHorizontal Vent Cap Wood ScrewInterior Wall Surface Firestop Vent Cap Vent PipeHorizontal Termination Configurations Snorkel Termination Minimum Vertical30 max Venting with Two 90 Elbows Roof Flashing Wall Strap Elbow Ceiling Firestop Installation for Vertical TerminationFlat Ceiling Installation If area above is a room orVertical Termination Configurations Elbow Into inner collar fireplace as shownHigh Altitude Installation Installing Optional Blower Accessory Venting InstallationFireplace Installation Check GAS Type Desa 5/8 Pipe & Vent KitsFireplace Installation Model BKT InstallationInstallation Items Needed Installing GAS Piping to Fireplace LocationBlower Wiring Diagram Checking GAS Connections Connecting Fireplace to GAS SupplyPressure Testing Gas Supply Piping System Removing Louver Panels Pressure Testing Fireplace Gas ConnectionsREMOVING/REPLACING Glass Door Removing Glass Door Installing Lava Rock and Glowing EmbersCleaning Glass Door Optional Remote Control Installing Brick Liner Models BL36DASA and BL36DHASAWall Switch Installation Operating Fireplace Wiring DiagramFor Your Safety Read Before Lighting Lighting InstructionsOptional Remote Operating Optional Blower AccessoryTo Turn OFF GAS To Appliance OperationPilot and Burners Cleaning MaintenanceGlass Door LogsTroubleshooting Observed Problem Possible Cause RemedyGas leak. See Warning statement at Technical Service Replacement PartsService Hints Parts Under WarrantySpecifications Illustrated Parts Breakdown Models VC36NE, VVC36NE, VC36PE and VVC36PEParts List KEY Part Number Description QTY2827 19 18 KEY Part Number Description Accessories Date Purchased Serial Number BrandModel Industrial Drive Box Bowling Green, KY 116235-01B Industrial Drive P.O. Box Warranty InformationModel Serial No Date Purchased