Desa CHDV41N/P PRE-INSTALLATION Preparation General Venting, Location of Vent Termination

Page 5

OWNER’S MANUAL

PRE-INSTALLATION PREPARATION

Continued

GENERAL VENTING

These models are approved for use with Simpson Dura-Vent 6 5/8" direct-vent pipe components and terminations as well as both flex and rigid Comfort Glow vent components.

13"

 

 

9 1/4"

 

41"

 

 

 

Your fireplace is approved to be vented either

29"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

through the side wall, or vertically using the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

following guidelines:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Only use Comfort Glow or Simpson Dura-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent GS venting components or kits spe-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cifically approved for this fireplace.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Minimum clearance between vent pipes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 1/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and combustible materials is 1" (25 mm),

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8 3/4"

 

 

37"

 

 

 

 

 

 

 

 

except where stated otherwise.

 

 

 

 

 

 

 

 

 

 

• Combustible material may be flush with

 

 

 

 

41"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

37

1

/2"

 

 

 

 

 

Nailing Tabs

the top front of fireplace with a maxi-

 

 

 

 

 

 

 

 

 

 

mum thickness of 3/4".

 

 

 

 

41 1/2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58"

 

 

 

 

 

 

 

 

• Do not recess venting terminals into a

 

 

 

 

 

 

 

 

 

 

 

 

 

wall or siding.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Where two numbers are given the top number

 

 

• Install horizontal venting with a 1/4" rise

is exclusive to the 37" Fireplace and the bottom

 

 

 

for every 12" of run toward the termination.

number is exclusive to the 41" Fireplace

 

 

 

 

 

 

 

You may paint the vent terminal with

Figure 6 - Framing Clearances for Corner Installation

 

 

 

 

 

450ºF (232ºC) heat-resistant paint to co-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

ordinate with the exterior finish.

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

There must not be any obstruction such

Note: There must be a

 

 

 

 

 

 

 

 

 

 

 

as bushes, garden sheds, fences, decks,

 

 

 

 

 

 

 

 

 

 

 

 

minimum clearance of 18"

 

 

 

 

 

3

 

 

 

 

 

 

or utility buildings within 24" from the

above top of louver

 

 

 

 

 

 

 

 

 

 

 

front of the termination cap.

A

 

 

 

 

 

 

Wall

opening when installing a

 

 

 

 

 

4

 

 

 

 

 

television or entertainment

 

 

 

 

 

 

 

 

 

 

• Do not locate termination cap where ex-

 

 

 

 

 

 

 

 

 

 

 

 

cessive snow or ice build up may occur.

center above the fireplace.

 

B

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Be sure to clear vent termination area af-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

6

 

 

 

 

 

 

ter snow falls to prevent accidental block-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

age of venting system. When using snow

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

7

 

 

 

 

 

 

blowers, do not direct snow towards vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

 

termination area.

 

 

 

 

 

 

 

 

 

G

 

 

 

 

Location of Vent Termination

 

 

 

Top of Louver Opening

 

 

 

 

 

Ref.

Mantel Depth

Ref.

Mantel from Top

 

 

 

 

of Louver Opening

 

 

 

 

 

 

1

14" (356mm)

A

16" (406mm)

 

 

 

 

 

 

2

12" (305mm)

B

14" (356mm)

 

3

10" (254mm)

C

12" (305mm)

 

 

 

 

 

 

4

8" (203mm)

D

10" (254mm)

 

 

 

 

 

 

5

6" (152mm)

E

8" (203mm)

 

 

 

 

 

 

6

4" (101mm)

F

6" (152mm)

 

 

 

 

 

 

7

2" (51mm)

G

4" (101mm)

 

 

 

 

 

 

When locating vent termination, it is impor- tant to observe the minimum clearances shown in Figure 8, page 6. You will avoid extra framing by positioning your fireplace against an already existing framing mem- ber. The sides of the fireplace may be posi- tioned directly against combustible walls.

*Check with local codes or with the current CAN/CGA B149[.1 or .2] Installation Codes for Canada or the USA Installations follow the current National Fuel Gas Code, ANS Z223.1, also known as NFPA 54.

Figure 7 - Clearances for Combustible Mantels

105542

5

Image 5
Contents CHDV37N/PA,B and CHDV41N/PA,B For Your SafetyFor Your Safety What to do if YOU Smell GAS DIRECT-VENT Fireplace NATURAL/PROPANE/LP Safety InformationProduct Identification Product FeaturesLocal Codes Glossary TermsLocation and Space Requirements PRE-INSTALLATION PreparationClearances Framing and FinishingLocation of Vent Termination PRE-INSTALLATION Preparation General VentingGeneral Venting Installation Precautions Venting InstallationInstallation Planning Installing Vent System in a ChaseSnorkel Termination Installation for Horizontal TerminationVent Pipe Connections Horizontal Termination Configuration for Rigid Venting Horizontal Termination ConfigurationsVenting with Two 90 Elbows Cathedral Ceiling Installation Installation for Vertical TerminationFlat Ceiling Installation Venting with One 90 Elbow Vertical Termination ConfigurationsVertical Venting Parts Lists for Venting Kits and Components High Altitude InstallationComfort Glow Rigid Venting Comfort Glow Flexible VentingInstalling Optional Blower Accessory Fireplace InstallationInstalling GA3750/CDA3620T Blowers Check GAS TypeIf your fireplace system is installed Installation Items Needed Installing GAS Piping to Fireplace LocationInstallation Items Needed Connecting Fireplace to GAS SupplyPressure Testing Gas Supply Piping System Checking GAS ConnectionsClose manual shutoff valve see Fig- ure Pressure Testing Fireplace Gas ConnectionsIncluded Installing Battery into Receiver Wireless HAND-HELD Remote ControlInstalling 9-Volt Battery in Hand- Held Remote Control Unit REMOVING/REPLACING Glass DoorAttaching Magnetic Decorative Brass Strips Installing Optional Brick Liner CD8037A/ CD8041Fireplace Models CHDV37N/P and CHDV41N/P Installing LOGS, Lava Rock and Glowing EmbersManual Lighting Procedure For Your Safety Read Before LightingOperating Fireplace Lighting InstructionsHAND-HELD Remote Operation Operating Optional Blower AccessoryBurner Flame Pattern Pilot AssemblyInspecting Burners Glass Door Cleaning and MaintenancePilot and Burners LogsObserved Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Gas leak. See Warning statement Wiring Diagram Replacement PartsService Hints Technical ServiceCHDV37NA,B CHDV37PA,B CHDV41NA,B CHDV41PA,B SpecificationsManual Blower KIT GA3750 AccessoriesTHERMOSTATICALLY- Controlled Blower KIT CDA3620T GMC41F41 Walnut Stained Hardwood VeneerCHDV37NA,B CHDV41NA,B Illustrated Parts BreakdownDIRECT-VENT Fireplace CHDV37NA,B CHDV41NA,B Parts ListCHDV37PA,B CHDV41PA,B DIRECT-VENT Fireplace CHDV37PA,B CHDV41PA,B Warranty Information