Desa VP325E(B) installation manual Checking for Proper Venting, Min Roof Pitch

Page 9

VENTING INSTALLATION

Checking for Proper Venting

9

VENTING INSTALLATION

Continued

Vent terminations must be located in accordance with height and proximity rules of NFPA No. 54 or CAN/CSA B149. These rules apply to vents at 12 in. diameter or less and require a minimum height in accordance with the roof pitch and a minimum of 8 ft. distance from a vertical wall or obstruction (see Figure 10).

If venting horizontally through a side wall becomes necessary, a listed thimble approved for use with B-type vent must be used. Check with your local codes before venting through a side wall.

Some codes areas allow the use of existing B-type vent systems if the system is at or above the recommended diameter of the flue.

The flue connection must be made using listed B-type connectors and the existing system must be code inspected for damage and proper installation.

It is not recommended that this appliance be common vented with an existing gas burning appliance. However, if it becomes necessary to common vent this appliance, the venting system must be sized and configured in accordance with the common venting guides Appendix G of the current National Fuel Gas Code NFPA No. 54/ ANSI Z223.1 and in Canada with CAN/CSA B149.

Note: Before connecting this appliance to an existing vent system or a common venting system consult with your local architect, planner, or building official.

WARNING: This appliance must be properly con- nected to a system and must not be connected to a chimney flue servicing a separate solid fuel burning appliance.

CHECKING FOR PROPER VENTING

After completing and checking the electrical, gas and vent connec- tions, follow the lighting instructions and allow the main burner to run for approximately 5 minutes. Hold a lighted match or cigarette near the top edge of the fireplace opening and play it along the entire length of the opening (see Figure 11). Proper venting should tend to draw the flame or smoke into the appliance. Improper venting or escaping of spillage of burned gas, is indicated when the match flickers or goes out. Smoke from a cigarette will also tend to disperse away from the appliance.

Lowest Listed

Discharge Vent Cap

Opening

8 Ft. Min.

Listed Gas

Vent

12

H(Min) Height From Roof

x

Roof Pitch x/12 Listed Clearance

If the appliance is found to be improperly venting, shut it off and notify your installer or a qualified service agency to inspect the venting system.

NOTICE: This appliance is equipped with a vent safety shutoff switch which will shut down the appli- ance in the case of a venting problem. Do not bypass the vent safety switch. If the appliance should shut down, contact a qualified installer, service agency, or your gas supplier to have the vent inspected before operating.

 

H (Min.)

 

Roof Pitch

Ft.

m

 

 

 

Flat to 6/12

1.0

0.30

6/12 to 7/12

1.25

0.38

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2.0

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4.0

1.22

Over 12/12 to 14/12

5.0

1.52

Over 14/12 to 16/12

6.0

1.83

Over 16/12 to 18/12

7.0

2.13

Over 18/12 to 20/12

7.5

2.27

Over 20/12 to 21/12

8.0

2.44

 

 

 

Figure 10 - B-Vent Terminations

Check this area along the entire top edge of the fireplace opening. Smoke or flame should be drawn into the appliance opening.

Figure 11 - Checking for Spillage

For more information, visit www.desatech.com

108794-01D

Image 9
Contents Vent Decorative GAS Fireplace For Your SafetyNatural GAS What to do if YOU Smell GASSafety Information Table of ContentsUnpacking Before YOU Begin IntroductionSelecting Location Product SpecificationsPRE-INSTALLATION Preparation ClearancesMantel Clearances and Wall Details Framing Corner Installation GuidelinesTypical B-Vent Configuration Venting InstallationMin Roof Pitch Checking for Proper VentingWall Switch Installation InstallationOptional Remote Control GAS Line HOOK-UPNot Supplied Grate PlacementLOG Placement for P324E/VP324E Models Ember and PAN Material PlacementInstalling Log LOG Placement for P325EB/VP325EB ModlesInstalling Optional Glass Door Accessory Combustion AIR KIT Model AK4 OptionalAppliance Enclosure For Your Safety Read Before Lighting Operating FireplaceLighting Instructions Inspecting Burners Pilot AssemblyTo Turn OFF GAS To Appliance Optional Remote OperationBurner Flame Pattern Cleaning MaintenancePilot and Burner LogsTechnical Service Service HintsWiring Diagram Replacement Parts Parts Under WarrantyObserved Problem Possible Cause Remedy TroubleshootingGas leak. See Warning statement at Accessories Illustrated Parts Breakdown P324E and VP324E Models Parts ListP325EB and VP325EB Models Illustrated Parts BREAKDOWN44108866-01 Pilot Natural Gas 901157-01 Lava Rock Illustrated Parts Breakdown LOG AssemblyOwners Registration Form Postage Required 108794-01D Warranty Information