Desa VVSR18 Ventilation AIR, Ventilation Air From Inside, Building, Ventilation Air From Outdoors

Page 6

®

VENTED NATURAL GAS LOGS

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills Into Adjoining Room,

Room,

Or

Option 2

Ventilation Air From Inside

Option 1

Remove

Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op- tion 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option 3

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

6

901265

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASFor Use with Log Sets Safety Information Vented Natural GAS LogsRemote Control Ready Millivolt Safety VALVE/ Pilot KIT Product Identification Optional Product FeaturesON/OFF Safety VALVE/ Pilot KIT and PROPANE/LP Conversion Remote Control AccessoriesUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Appliance LocationDetermining if You Have a Confined or Unconfined Space Building Ventilation AIRVentilation Air From Inside Ventilation Air From OutdoorsVenting Specifications for Installation InstallationFlue Opening Specifications Check GAS TypeInstallation Items Needed Installing Damper ClampConnecting to GAS Supply Pressure Testing Gas Supply Piping SystemKit Assembly Hearth KIT Assembly and InstallationOptional GA9000 ON/OFF Safety VALVE/PILOT KIT Assembly Installation and Gas ConnectionPropane/LP Gas Conversion Burner Inlet FittingAdding PAN Material Testing Burner for LeaksInstalling the Grate and Logs Changing Pilot OrificeOperating Appliance Troubleshooting To Turn OFF GAS To ApplianceShutting Off Burner Only pilot stays lit Clean pilot see Cleaning and Mainte Top Gas leak. See Warning statement atIllustrated Parts Breakdown VVSR18, VVSR24, VVDR18, VVDR24, and VVDR30Parts List VVSR18 VVSR24, VVDR18 VVDR24, and VVDR30LOG SET Models VSLR18, VSLR24, VDLCR18, VDLCR24, and VDLCR30 Parts List Cleaning and Maintenance Replacement PartsAccessories Ornamental Grate Enhancer GA9320 Decorative ASH BED Control Cover DabkOrnamental Grate Enhancer GA9310 Ornamental Grate Enhancer GA9330Vented Natural GAS Logs 901265 Warranty Information International