Panasonic R410A service manual Eeprom

Page 171

 

 

 

 

 

4. Service procedures

 

 

 

 

 

 

 

 

 

 

 

 

Remote

Alarm

 

 

 

 

 

 

 

 

controller

Judgment condition

Clear condition

Judgment and correction

 

 

 

 

contents

 

 

 

alarm display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F31

EEPROM trouble

Reading/writing failure

Recovery at power

1. Check EEPROM (IC007).

 

 

 

 

 

 

reset

2. Check outdoor unit control

 

 

 

 

 

 

 

PCB.

 

 

 

 

 

 

 

 

 

 

 

L02

Mismatch of indoor

Indoor unit judges that type

Recovery at power

1. Check indoor unit EEPROM.

 

 

 

 

and outdoor unit types

does not match outdoor unit

reset

2. Check indoor unit control

 

 

 

 

(Espacio, Multi )

type.

 

PCB.

 

 

 

 

 

 

 

 

 

 

 

L04

Settings failure

Duplicated outdoor unit

Automatic recovery

1. Check outdoor unit

 

 

 

 

 

address (system address)

 

system address.

 

 

 

 

 

 

 

2. Check inter-unit control

 

 

 

 

 

 

 

wiring.

 

 

 

 

 

 

 

 

 

 

 

L07

Settings failure

Group control wiring is

Recovery at power

1. Check inter-unit control

 

 

 

 

 

connected to an

reset

wiring.

 

 

 

 

 

independent-control indoor

 

2. Check indoor unit

 

 

 

 

 

 

 

EEPROM.

 

 

 

 

 

 

 

 

 

 

 

L10

Settings failure

Outdoor unit capacity not set.

Recovery at power

Check outdoor unit EEPROM.

 

 

 

 

 

 

reset

 

 

 

 

 

 

L13

Indoor-outdoor unit

Outdoor unit judges that type

Recovery at power

1. Check indoor unit

 

 

 

 

types

does not match indoor unit

reset

EEPROM.

 

 

 

 

 

type.

 

2. Check outdoor unit control

 

 

 

 

 

 

 

PCB.

 

 

 

 

 

 

 

 

 

 

 

E06

Outdoor unit detected

Serial signal receiving failure

Automatic

1. Check inter-unit control

 

 

 

 

abnormal signal from

(including failure to verify No.

recovery

wiring.

 

 

 

 

indoor unit.

of units)

 

2. Check outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

E07

Outdoor unit sending

Serial signal sending failure

Automatic

1. Check inter-unit control

 

 

 

 

failure to indoor unit

 

recovery

wiring.

 

 

 

 

 

 

 

2. Check outdoor unit control

 

 

 

 

 

 

 

PCB.

 

 

 

 

E14

Settings failure

Duplicated master unit in

Recovery at power

1. Check inter-unit control

 

 

 

 

 

simultaneous-operation multi

reset

wiring.

 

 

 

 

 

control

 

2. Check indoor unit

 

 

 

 

 

(Detected by outdoor unit)

 

combination.

 

 

 

 

 

 

 

 

 

 

 

 

E15

Automatic address

Indoor unit capacity too low.

Recovery at power

1. Check inter-unit control

 

 

 

 

setting failure

 

reset

wiring.

 

 

 

 

 

 

 

2. Check outdoor unit control

 

 

 

 

 

 

 

PCB.

 

 

 

 

 

 

 

 

 

 

 

 

E16

Automatic address

Indoor unit capacity too high.

Recovery at power

1. Check inter-unit control

 

 

 

 

setting failure

 

reset

wiring.

 

 

 

 

 

 

 

 

2. Check outdoor unit control

 

 

 

 

 

 

 

PCB.

 

 

4

 

 

 

 

 

 

 

 

E20

Automatic address

Outdoor unit cannot receive

Recovery at power

1. Check inter-unit control

 

 

setting failure

any serial signals from indoor

reset

wiring.

 

 

 

 

 

units.

 

2. Check outdoor unit control

 

 

 

 

 

 

 

PCB.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E31

Communications

No communication possible

Automatic recovery

Check outdoor unit control

 

 

 

 

trouble within unit

with MDC for 3 minutes or

 

PCB.

 

 

 

 

 

longer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H01

Overcurrent

Inverter stops after alarm is

Recovery at restart

1. Refrigerant cycle trouble,

 

 

 

 

 

detected.

 

overload operation

 

 

 

 

 

 

 

2. Loose screws between HIC

 

 

 

 

 

 

 

control PCB and radiating

 

 

 

 

 

 

 

plate

 

 

 

 

 

 

 

3. Cooling failure of radiating

 

 

 

 

 

 

 

plate

 

 

 

 

 

 

 

4. Check outdoor unit PCB

 

 

 

 

 

 

 

wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

4-7

Image 171
Contents Indoor Units Model No Outdoor Units…In an Area with High Winds For safe installation and trouble-free operation, you must…In a Room …In Moist or Uneven LocationsCheck of Density Limit Precautions for Installation Using New Refrigerant Configuration and characteristics of cylinders Contents Tentative Model No Specifications Unit Specifications Way Cassette TypeIndoor Unit 36PU1U6 Outdoor Unit 36PE1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PE1U6 Indoor Unit 26PU1U6 Outdoor Unit Indoor Unit 36PU1U6 Outdoor Unit 36PS1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PS1U6 Data Subject to Change Without Notice Specifications Unit Specifications Wall Mounted TypeIndoor Unit 26PK1U6 Outdoor Unit Performance Specifications Unit Specifications Ceiling TypeIndoor Unit 36PT1U6 Outdoor Unit Indoor Unit 42PT1U6 Outdoor Unit Indoor Unit 26PT1U6 Outdoor Unit 26PS1U6 17˚F BTU / h Moisture removal High Pints / h Indoor Unit 42PT1U6 Outdoor Unit 42PS1U6 Net weight Lbs. kg 128 Shipping weight 148 Shipping volume Specifications Unit Specifications Low Silhouette Duct TypeIndoor Unit 36PF1U6 Outdoor Unit 36PE1U6 RCZ-RTC2 CZ-RWSC1U Fan motor Major Component Specifications Indoor UnitModel No 36PU1U6 Source Model No 42PU1U6 Source Model No 26PK1U6 Source Model No 26PT1U6 Source Model No 36PT1U6 Source Model No 42PT1U6 Source Model No 26PF1U6 Source Model No 36PF1U6 Source Compressor Specifications Major Component Specifications Outdoor UnitCR-CH4872R Microprocessor Lbs. kg R410A 7.9 26PS1U6 230V, 40µF 42PS1U6 Model No 26PE1U6, U-26PS1U6 Specifications Other Component Specifications Outdoor UnitModel No 36PE1U6, U-36PS1U6 Model No 42PE1U6, U-42PS1U6 Ø1/8 Hol Page 19/32 31/32 12-7/32 Dimension inch 56-25/32 Air outlet duct flange Thickness more than T1/16 inch Page Page Specifications Operating Range Temperature Indoor Air Intake Outdoor Air IntakePage Source Specifications Noise Criterion Curves Way Cassette TypeSpecifications Noise Criterion Curves Wall Mounted Type Specifications Noise Criterion Curves Ceiling Type Sound Noise Criterion Curves Low Silhouette Duct TypeSpecifications Noise Criterion Curves Outdoor Units Type Specifications Increasing the Fan SpeedHow to read the diagram Indoor Fan Performance TypeAir throw distance chart Way Cassette Type Model 26 TypeModel 36, 42 Type Specifications Air throw distance chart Wall Mounted Type Air throw distance chart Ceiling Type Model 36 TypeModel 42 Type Outdoor Unit Type Time delay fuse or Circuit capacity Wiring System Diagrams How to Connect Wiring to the Terminal For stranded wiring Installation Instructions Ashrae Selecting the Installation Site Air-Discharge Chamber for Top Discharge ① Air discharge chamber ② Air discharge chamber base For U-42PES1U6 unitDirection 42PES1U6 unitFront and both sides must remain open 25-13/32 25/32 30-5/64 Wind direction Obstacle to the front of unit Installation in front-rear rows Installing the Outdoor Unit Routing the Tubing and WiringDrainage Work Low Silhouette Ducted Type Way Cassette Type Preparation for Suspending Way Cassette Type U1 Type Suspending the Indoor UnitPlacing the Unit Inside the Ceiling Installing the Drain Piping Checking the Drainage Unit body Before Installing the Ceiling PanelWhen Removing the Ceiling Panel for Servicing Installing the Ceiling PanelAccessories Installing the ceiling panel Hole Dia. inch Trical wiring or conduits areSelecting and Making a Hole LocatedInstalling the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall To mount the indoor unit on the rear panel Removing the Grille to Install the Indoor UnitHow to remove the grille How to replace the grilleHow to remove the cover plate Wiring Instructions General Precautions on WiringShaping the Tubing Installing the Drain HoseCeiling Type T1 Type Suspending the Indoor Unit Hinge Slide toward front side Side panel Unit Outside Good Not good Duct for Fresh Air36PF1U6 Required Minimum Space for Installation and ServiceLow Silhouette Ducted Type F1 Type 26PF1U6Indoor unit inside the ceiling Enough to support the weightIt is important that you use Extreme care in supportingTheir locking nuts face upward Tighten the hose clamps soTo mount the tube cover, use 5/16 When you short the pin onBe careful since the fan will start Indoor control boardIndoor Fan Performance Increasing the Fan SpeedWhen Installing the Indoor Unit Checkpoint Symptom Remark Checkpoint after installationWireless Remote Controller Installation How to Install BatteriesIf Wall-mounted Fixed Position Room Temperature Sensor Setting Address SwitchesSetting the Model Code CZ-RWSU1U Ceiling Type T1 Type Indicator Section Installation Electrical Wiring Test Run SwitchHow to use the test run setting U1, T1 Types Lamp Misoperation Alarm IndicatorsAlarm Cause of TroubleIf Wall mounted Fixed Position 107 Function only when To avoid placing anExcessive load on Equipment, use thisBright Cause of Trouble Timer StandbyWill damage the equipment Wiring procedureGroup control using 2 signal receiving units Wiring System Diagram for Group ControlSetting method Test Run Procedure Wall mounted Type K1 Type Wireless remote controller transmitterCheck Items Before the Test Run Test run Using the controller For S-26PK1U6 IndicatorController Test OFF Precautions26PK1U6 Nos , 2 OFF, No onNos , 2, 3 all OFF Diagnosis Table CauseIndoor unit HOW to Install the Timer Wired Remote Controller Tube diameter Tightening torque Tube thickness Tubes arranged together Precautions for Packed Valve OperationNever grasp the drain or refrigerant connecting Insulating the Refrigerant Tubing Tubing InsulationTaping the Tubes Finishing the InstallationAir Purging with a Vacuum Pump for Test Run Preparation Manifold gauge Vacuum pumpLeak Test Evacuation Use a cylinder specificallyDesigned for use with R410A Charging Additional Refrigerant Finishing the JobR410A Processes and Functions Processes and functions Room Temperature Control Chart Summary and ExplanationsCooling Processes and functions Heating Cold Draft Prevention Heating Cycle Automatic Fan Speed Indoor Unit Chart Explanations and notesCoil heating control Discharge temperature release controlCurrent release control Outdoor unit fan controlHeating high-load control Freeze prevention low-temperature release controlOvercurrent protection control Current release value shift controlDefrost control Outdoor Unit Control PCB Outdoor Unit Control PCB CR-CH4272R Example of wiring Method of System Address SettingPage Electrical Data Indoor Units Page Electrical data Wall Mounted Type S-26PK1U6 Electrical data Wall Mounted Type S-26PK1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Page Page Outdoor Units Outdoor Units 26PS1U6 Outdoor Units 36PE1U6 Outdoor Units 36PS1U6 Outdoor Units 42PE1U6 Outdoor Units 42PS1U6 Outdoor Units Page Service Procedures Contents of remote controller switch alarm display Service procedures Meaning of Alarm MessagesWireless Remarks Contents Correction Remote Alarm Judgment condition Clear conditionAlarm Eeprom Service procedures Details of Alarm Messages Alarm P29MDC trouble HIC PCB trouble Alarm P26Communications Trouble within unit Alarm E31HIC-CH4872R HIC-CH2672R 26, 36 TypeAlarm P22 Alarms F04, F06, F07, F08, F12 Check procedure Sensor Temperature Correlation TableSensor installation Sensor type Location Discharge Temp. TD Sensors Check PinOutdoor Air Temp. TO, Intake Temp. TS, Heat Exchanger Temp. C1 Sensor, Heat Exchanger Temp. C2 SensorOutdoor Unit Maintenance Remote Control Outdoor unit maintenance remote control Overview Switching between cooling/heating Operation All units start/stop OperationAll units test run Operation Sample displays Item code Display contentsDisplay for unit Nos Item code Meaning of Code Display of first 3 digits Display of last 3 digits Item code Parameter List of Item CodesOutdoor unit maintenance remote control Figures represent the capacity data for each model Test RUN Test run Preparing for Test RunTest run U1, K1, T1, F1 Type 6-2. Caution Items to Check Before the Test Run Cause Basic wiring diagram Test run Examples of Wiring DiagramsRemote controller crossover wiring for group control System address No Setting the outdoor unit system addressesAutomatic address setting using the remote controller 2P DIP switch Rotary switchMain-sub remote controller control Connecting 2 remote controllers to control 1 indoor unitRemote controller setting mode 201201
Related manuals
Manual 112 pages 20.27 Kb

R410A specifications

Panasonic R410A is a refrigerant that has gained significant popularity in the air conditioning and refrigeration industry due to its favorable environmental properties and performance characteristics. Specifically designed to replace the harmful R22 refrigerant, which is being phased out due to its ozone-depleting potential, R410A offers a more eco-friendly alternative without compromising on efficiency or power.

One of the main features of R410A is its high energy efficiency. It operates at a higher pressure than R22, resulting in better heat transfer capabilities. This increased efficiency translates to lower energy consumption, making units using R410A more cost-effective in the long run. Additionally, R410A is known for its ability to provide excellent cooling performance even in high-temperature environments, making it suitable for a variety of applications, from residential air conditioning systems to commercial refrigeration units.

In terms of composition, R410A is a blend of two hydrofluorocarbons (HFCs), namely R32 and R125. This combination not only minimizes ozone depletion potential (ODP) but also reduces global warming potential (GWP) compared to older refrigerants. Panasonic has emphasized the importance of innovative technologies in its products, and R410A aligns perfectly with the company's commitment to developing sustainable solutions.

Panasonic also integrates advanced technologies to optimize the performance of R410A systems. For example, variable speed compressors, known as inverter technology, enhance system efficiency by adjusting the compressor's speed according to the cooling demand. This ensures that energy is only consumed when needed, further reducing operational costs.

Furthermore, R410A has a wide range of applications, including air conditioning systems, heat pumps, and chillers. Its versatility makes it a popular choice among manufacturers and consumers alike. The refrigerant is also compatible with existing R22 equipment, although specific retrofit procedures must be followed to ensure peak performance and reliability.

In conclusion, Panasonic R410A stands out as an innovative refrigerant choice in the HVAC industry, offering a combination of energy efficiency, environmentally friendly properties, and advanced technologies. As regulatory frameworks continue to tighten on greenhouse gas emissions, R410A and similar refrigerants are expected to play a crucial role in shaping a more sustainable future for air conditioning and refrigeration. Its high performance and lower environmental impact solidify its position as a leading refrigerant in contemporary cooling solutions.