Panasonic R410A service manual Precautions for Installation Using New Refrigerant

Page 4

Precautions for Installation Using New Refrigerant

1. Care regarding tubing

1-1. Process tubing

Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.”

Tubing size: Be sure to use the sizes indicated in the table below.

Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).

When bending tubing ø5/8" or smaller, use a bending radius that is 4 times the outer diameter of the tubing or larger.

CAUTION

Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt, moisture, or other foreign substances from entering. These substances can result in system malfunction.

 

 

 

 

 

 

Unit: inch

Material

 

 

O

 

Copper tube

Outer diameter

1/4

3/8

 

1/2

5/8

Wall thickness

t0.032

t0.032

 

t0.032

t0.04

 

 

1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.

2. Be sure to recharge the refrigerant only in liquid form.

2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects of the unit.

2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refrigerant and recharge the required total amount of new refrigerant after fixing the leak.

3. Different tools required

3-1. Tool specifications have been changed due to the characteristics of R410A. Some tools for R22- and R407C-type refrigerant systems cannot be used.

 

New

R407C tools

 

Item

compatible

Remarks

tool?

 

with R410A?

 

Manifold gauge

Yes

No

Types of refrigerant, refrigerating machine oil, and

 

 

 

pressure gauge are different.

Charge hose

Yes

No

To resist higher pressure, material must be changed.

Vacuum pump

Yes

Yes

Use a conventional vacuum pump if it is equipped

 

 

 

with a check valve. If it has no check valve,

 

 

 

purchase and attach a vacuum pump adapter.

Leak detector

Yes

No

Leak detectors for CFC and HCFC that

 

 

 

react to chlorine do not function because

 

 

 

R410A contains no chlorine. Leak detector

 

 

 

for HFC134a can be used for R410A.

Flaring oil

Yes

No

For systems that use R22, apply mineral oil (Suniso oil)

 

 

 

to the flare nuts on the tubing to prevent refrigerant

 

 

 

leakage. For machines that use R407C or R410A, apply

 

 

 

synthetic oil (ether oil) to the flare nuts.

* Using tools for R22 and R407C and new tools for R410A together can cause defects.

Manifold gauge

Vacuum pump

Outlet

Inlet

iii

Image 4
Contents Model No Outdoor Units Indoor UnitsFor safe installation and trouble-free operation, you must …In a Room…In Moist or Uneven Locations …In an Area with High WindsCheck of Density Limit Precautions for Installation Using New Refrigerant Configuration and characteristics of cylinders Contents Tentative Specifications Unit Specifications Way Cassette Type Model NoIndoor Unit 36PU1U6 Outdoor Unit 36PE1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PE1U6 Indoor Unit 26PU1U6 Outdoor Unit Indoor Unit 36PU1U6 Outdoor Unit 36PS1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PS1U6 Specifications Unit Specifications Wall Mounted Type Data Subject to Change Without NoticeIndoor Unit 26PK1U6 Outdoor Unit Specifications Unit Specifications Ceiling Type PerformanceIndoor Unit 36PT1U6 Outdoor Unit Indoor Unit 42PT1U6 Outdoor Unit Indoor Unit 26PT1U6 Outdoor Unit 26PS1U6 17˚F BTU / h Moisture removal High Pints / h Indoor Unit 42PT1U6 Outdoor Unit 42PS1U6 Specifications Unit Specifications Low Silhouette Duct Type Net weight Lbs. kg 128 Shipping weight 148 Shipping volumeIndoor Unit 36PF1U6 Outdoor Unit 36PE1U6 RCZ-RTC2 CZ-RWSC1U Major Component Specifications Indoor Unit Fan motorModel No 36PU1U6 Source Model No 42PU1U6 Source Model No 26PK1U6 Source Model No 26PT1U6 Source Model No 36PT1U6 Source Model No 42PT1U6 Source Model No 26PF1U6 Source Model No 36PF1U6 Source Specifications Major Component Specifications Outdoor Unit CompressorCR-CH4872R Microprocessor Lbs. kg R410A 7.9 26PS1U6 230V, 40µF 42PS1U6 Specifications Other Component Specifications Outdoor Unit Model No 26PE1U6, U-26PS1U6Model No 36PE1U6, U-36PS1U6 Model No 42PE1U6, U-42PS1U6 Ø1/8 Hol Page 19/32 31/32 12-7/32 Dimension inch 56-25/32 Air outlet duct flange Thickness more than T1/16 inch Page Page Specifications Temperature Indoor Air Intake Outdoor Air Intake Operating RangePage Specifications Noise Criterion Curves Way Cassette Type SourceSpecifications Noise Criterion Curves Wall Mounted Type Specifications Noise Criterion Curves Ceiling Type Noise Criterion Curves Low Silhouette Duct Type SoundSpecifications Noise Criterion Curves Outdoor Units Specifications Increasing the Fan Speed How to read the diagramIndoor Fan Performance Type TypeModel 26 Type Air throw distance chart Way Cassette TypeModel 36, 42 Type Specifications Air throw distance chart Wall Mounted Type Model 36 Type Air throw distance chart Ceiling TypeModel 42 Type Outdoor Unit Type Time delay fuse or Circuit capacity Wiring System Diagrams How to Connect Wiring to the Terminal For stranded wiring Installation Instructions Ashrae Selecting the Installation Site Air-Discharge Chamber for Top Discharge For U-42PES1U6 unit ① Air discharge chamber ② Air discharge chamber base42PES1U6 unit DirectionFront and both sides must remain open 25-13/32 25/32 30-5/64 Wind direction Obstacle to the front of unit Installation in front-rear rows Routing the Tubing and Wiring Installing the Outdoor UnitDrainage Work Low Silhouette Ducted Type Way Cassette Type Way Cassette Type U1 Type Suspending the Indoor Unit Preparation for SuspendingPlacing the Unit Inside the Ceiling Installing the Drain Piping Checking the Drainage Before Installing the Ceiling Panel Unit bodyInstalling the Ceiling Panel When Removing the Ceiling Panel for ServicingAccessories Installing the ceiling panel Trical wiring or conduits are Selecting and Making a HoleLocated Hole Dia. inchIf Wooden Wall Installing the Rear Panel on the WallIf Block, Brick, Concrete or Similar Type Wall Removing the Grille to Install the Indoor Unit How to remove the grilleHow to replace the grille To mount the indoor unit on the rear panelWiring Instructions General Precautions on Wiring How to remove the cover plateInstalling the Drain Hose Shaping the TubingCeiling Type T1 Type Suspending the Indoor Unit Hinge Slide toward front side Side panel Unit Outside Duct for Fresh Air Good Not goodRequired Minimum Space for Installation and Service Low Silhouette Ducted Type F1 Type26PF1U6 36PF1U6Enough to support the weight It is important that you useExtreme care in supporting Indoor unit inside the ceilingTighten the hose clamps so Their locking nuts face upwardWhen you short the pin on Be careful since the fan will startIndoor control board To mount the tube cover, use 5/16Increasing the Fan Speed Indoor Fan PerformanceWhen Installing the Indoor Unit Checkpoint after installation Checkpoint Symptom RemarkHow to Install Batteries Wireless Remote Controller InstallationIf Wall-mounted Fixed Position Address Switches Room Temperature Sensor SettingSetting the Model Code CZ-RWSU1U Ceiling Type T1 Type Indicator Section Installation Test Run Switch Electrical WiringHow to use the test run setting U1, T1 Types Misoperation Alarm Indicators AlarmCause of Trouble LampIf Wall mounted Fixed Position 107 To avoid placing an Excessive load onEquipment, use this Function only whenTimer Standby Bright Cause of TroubleWiring procedure Will damage the equipmentWiring System Diagram for Group Control Group control using 2 signal receiving unitsSetting method Wireless remote controller transmitter Test Run Procedure Wall mounted Type K1 TypeCheck Items Before the Test Run Indicator Test run Using the controller For S-26PK1U6Controller Precautions Test OFFNos , 2 OFF, No on 26PK1U6Nos , 2, 3 all OFF Cause Diagnosis TableIndoor unit HOW to Install the Timer Wired Remote Controller Tube diameter Tightening torque Tube thickness Precautions for Packed Valve Operation Never grasp the drain or refrigerant connectingInsulating the Refrigerant Tubing Tubing Insulation Tubes arranged togetherFinishing the Installation Taping the TubesManifold gauge Vacuum pump Air Purging with a Vacuum Pump for Test Run PreparationLeak Test Use a cylinder specifically EvacuationDesigned for use with R410A Finishing the Job Charging Additional RefrigerantR410A Processes and Functions Chart Summary and Explanations Processes and functions Room Temperature ControlCooling Processes and functions Heating Cold Draft Prevention Heating Cycle Chart Explanations and notes Automatic Fan Speed Indoor UnitDischarge temperature release control Current release controlOutdoor unit fan control Coil heating controlFreeze prevention low-temperature release control Overcurrent protection controlCurrent release value shift control Heating high-load controlDefrost control Outdoor Unit Control PCB Outdoor Unit Control PCB CR-CH4272R Method of System Address Setting Example of wiringPage Electrical Data Indoor Units Page Electrical data Wall Mounted Type S-26PK1U6 Electrical data Wall Mounted Type S-26PK1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Page Page Outdoor Units Outdoor Units 26PS1U6 Outdoor Units 36PE1U6 Outdoor Units 36PS1U6 Outdoor Units 42PE1U6 Outdoor Units 42PS1U6 Outdoor Units Page Service Procedures Service procedures Meaning of Alarm Messages Contents of remote controller switch alarm displayWireless Remarks Remote Alarm Judgment condition Clear condition Contents CorrectionAlarm Eeprom Alarm P29 Service procedures Details of Alarm MessagesMDC trouble Alarm P26 HIC PCB troubleAlarm E31 HIC-CH4872R HIC-CH2672R26, 36 Type Communications Trouble within unitAlarm P22 Alarms F04, F06, F07, F08, F12 Sensor Temperature Correlation Table Check procedureSensor installation Sensor type Location Check Pin Outdoor Air Temp. TO, Intake Temp. TS, HeatExchanger Temp. C1 Sensor, Heat Exchanger Temp. C2 Sensor Discharge Temp. TD SensorsOutdoor Unit Maintenance Remote Control Outdoor unit maintenance remote control Overview All units start/stop Operation Switching between cooling/heating OperationAll units test run Operation Item code Display contents Sample displaysDisplay for unit Nos Item code Meaning of Code Display of first 3 digits Display of last 3 digits List of Item Codes Item code ParameterOutdoor unit maintenance remote control Figures represent the capacity data for each model Test RUN Preparing for Test Run Test runTest run U1, K1, T1, F1 Type 6-2. Caution Items to Check Before the Test Run Cause Test run Examples of Wiring Diagrams Basic wiring diagramRemote controller crossover wiring for group control Setting the outdoor unit system addresses Automatic address setting using the remote controller2P DIP switch Rotary switch System address NoConnecting 2 remote controllers to control 1 indoor unit Main-sub remote controller controlRemote controller setting mode 201201
Related manuals
Manual 112 pages 20.27 Kb

R410A specifications

Panasonic R410A is a refrigerant that has gained significant popularity in the air conditioning and refrigeration industry due to its favorable environmental properties and performance characteristics. Specifically designed to replace the harmful R22 refrigerant, which is being phased out due to its ozone-depleting potential, R410A offers a more eco-friendly alternative without compromising on efficiency or power.

One of the main features of R410A is its high energy efficiency. It operates at a higher pressure than R22, resulting in better heat transfer capabilities. This increased efficiency translates to lower energy consumption, making units using R410A more cost-effective in the long run. Additionally, R410A is known for its ability to provide excellent cooling performance even in high-temperature environments, making it suitable for a variety of applications, from residential air conditioning systems to commercial refrigeration units.

In terms of composition, R410A is a blend of two hydrofluorocarbons (HFCs), namely R32 and R125. This combination not only minimizes ozone depletion potential (ODP) but also reduces global warming potential (GWP) compared to older refrigerants. Panasonic has emphasized the importance of innovative technologies in its products, and R410A aligns perfectly with the company's commitment to developing sustainable solutions.

Panasonic also integrates advanced technologies to optimize the performance of R410A systems. For example, variable speed compressors, known as inverter technology, enhance system efficiency by adjusting the compressor's speed according to the cooling demand. This ensures that energy is only consumed when needed, further reducing operational costs.

Furthermore, R410A has a wide range of applications, including air conditioning systems, heat pumps, and chillers. Its versatility makes it a popular choice among manufacturers and consumers alike. The refrigerant is also compatible with existing R22 equipment, although specific retrofit procedures must be followed to ensure peak performance and reliability.

In conclusion, Panasonic R410A stands out as an innovative refrigerant choice in the HVAC industry, offering a combination of energy efficiency, environmentally friendly properties, and advanced technologies. As regulatory frameworks continue to tighten on greenhouse gas emissions, R410A and similar refrigerants are expected to play a crucial role in shaping a more sustainable future for air conditioning and refrigeration. Its high performance and lower environmental impact solidify its position as a leading refrigerant in contemporary cooling solutions.