Panasonic R410A Wiring Instructions General Precautions on Wiring, How to remove the cover plate

Page 93

1. Specifications

6-15. Wiring Instructions

General Precautions on Wiring

(1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.

(2)Provide a power outlet to be used exclusively for each unit. A power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.

(3)To prevent possible hazards from insulation failure, the unit must be grounded.

(4)All wiring must be connected tightly.

(5)Do not allow wiring to touch refrigerant tubing, compressor, or any moving parts of the fan.

Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

6-16. Wiring Instructions for Inter-Unit Connections

(1)Insert the inter-unit wiring (according to local electrical codes) into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 10 inches to extend from the wall face. (Fig. 1-43)

(2)Route the inter-unit wiring from the back of the indoor unit and pull it toward the front for connection. (Figs. 1-44a and 1-44b)

(3)Connect the inter-unit wiring to the corresponding terminals on the terminal plate (Figs. 1-44a and 1-44b) while referring to the wiring diagram.

(4)Be sure to secure the wiring with the provided clamp.

How to remove the cover plate

To access the terminal plate inside the indoor unit, follow these steps.

(1)Using a Phillips head screwdriver, remove the screw on the cover plate. (Figs. 1-44a and 1-44b)

(2)Remove the cover plate.

Rear

Wall

panel

 

Plastic

1

cover

Wiring

10 in.

Fig. 1-43

Terminal plate

Cover plate

 

Fig. 1-44a

Clamping

Connection for Solenoid

strap

Vale Kit (for 3WAY)

Power wiring (field supplied)

Earth screw

 

 

Remote control wiring

Conduit

and Inter-unit control

wiring (field supplied)

(field supplied)

 

Fig. 1-44b

1-87

Image 93
Contents Indoor Units Model No Outdoor Units…In a Room For safe installation and trouble-free operation, you must…In Moist or Uneven Locations …In an Area with High WindsCheck of Density Limit Precautions for Installation Using New Refrigerant Configuration and characteristics of cylinders Contents Tentative Model No Specifications Unit Specifications Way Cassette TypeIndoor Unit 36PU1U6 Outdoor Unit 36PE1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PE1U6 Indoor Unit 26PU1U6 Outdoor Unit Indoor Unit 36PU1U6 Outdoor Unit 36PS1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PS1U6 Data Subject to Change Without Notice Specifications Unit Specifications Wall Mounted TypeIndoor Unit 26PK1U6 Outdoor Unit Performance Specifications Unit Specifications Ceiling TypeIndoor Unit 36PT1U6 Outdoor Unit Indoor Unit 42PT1U6 Outdoor Unit Indoor Unit 26PT1U6 Outdoor Unit 26PS1U6 17˚F BTU / h Moisture removal High Pints / h Indoor Unit 42PT1U6 Outdoor Unit 42PS1U6 Net weight Lbs. kg 128 Shipping weight 148 Shipping volume Specifications Unit Specifications Low Silhouette Duct TypeIndoor Unit 36PF1U6 Outdoor Unit 36PE1U6 RCZ-RTC2 CZ-RWSC1U Fan motor Major Component Specifications Indoor UnitModel No 36PU1U6 Source Model No 42PU1U6 Source Model No 26PK1U6 Source Model No 26PT1U6 Source Model No 36PT1U6 Source Model No 42PT1U6 Source Model No 26PF1U6 Source Model No 36PF1U6 Source Compressor Specifications Major Component Specifications Outdoor UnitCR-CH4872R Microprocessor Lbs. kg R410A 7.9 26PS1U6 230V, 40µF 42PS1U6 Model No 26PE1U6, U-26PS1U6 Specifications Other Component Specifications Outdoor UnitModel No 36PE1U6, U-36PS1U6 Model No 42PE1U6, U-42PS1U6 Ø1/8 Hol Page 19/32 31/32 12-7/32 Dimension inch 56-25/32 Air outlet duct flange Thickness more than T1/16 inch Page Page Specifications Operating Range Temperature Indoor Air Intake Outdoor Air IntakePage Source Specifications Noise Criterion Curves Way Cassette TypeSpecifications Noise Criterion Curves Wall Mounted Type Specifications Noise Criterion Curves Ceiling Type Sound Noise Criterion Curves Low Silhouette Duct TypeSpecifications Noise Criterion Curves Outdoor Units How to read the diagram Specifications Increasing the Fan SpeedIndoor Fan Performance Type TypeAir throw distance chart Way Cassette Type Model 26 TypeModel 36, 42 Type Specifications Air throw distance chart Wall Mounted Type Air throw distance chart Ceiling Type Model 36 TypeModel 42 Type Outdoor Unit Type Time delay fuse or Circuit capacity Wiring System Diagrams How to Connect Wiring to the Terminal For stranded wiring Installation Instructions Ashrae Selecting the Installation Site Air-Discharge Chamber for Top Discharge ① Air discharge chamber ② Air discharge chamber base For U-42PES1U6 unitDirection 42PES1U6 unitFront and both sides must remain open 25-13/32 25/32 30-5/64 Wind direction Obstacle to the front of unit Installation in front-rear rows Installing the Outdoor Unit Routing the Tubing and WiringDrainage Work Low Silhouette Ducted Type Way Cassette Type Preparation for Suspending Way Cassette Type U1 Type Suspending the Indoor UnitPlacing the Unit Inside the Ceiling Installing the Drain Piping Checking the Drainage Unit body Before Installing the Ceiling PanelWhen Removing the Ceiling Panel for Servicing Installing the Ceiling PanelAccessories Installing the ceiling panel Selecting and Making a Hole Trical wiring or conduits areLocated Hole Dia. inchInstalling the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall How to remove the grille Removing the Grille to Install the Indoor UnitHow to replace the grille To mount the indoor unit on the rear panelHow to remove the cover plate Wiring Instructions General Precautions on WiringShaping the Tubing Installing the Drain HoseCeiling Type T1 Type Suspending the Indoor Unit Hinge Slide toward front side Side panel Unit Outside Good Not good Duct for Fresh AirLow Silhouette Ducted Type F1 Type Required Minimum Space for Installation and Service26PF1U6 36PF1U6It is important that you use Enough to support the weightExtreme care in supporting Indoor unit inside the ceilingTheir locking nuts face upward Tighten the hose clamps soBe careful since the fan will start When you short the pin onIndoor control board To mount the tube cover, use 5/16Indoor Fan Performance Increasing the Fan SpeedWhen Installing the Indoor Unit Checkpoint Symptom Remark Checkpoint after installationWireless Remote Controller Installation How to Install BatteriesIf Wall-mounted Fixed Position Room Temperature Sensor Setting Address SwitchesSetting the Model Code CZ-RWSU1U Ceiling Type T1 Type Indicator Section Installation Electrical Wiring Test Run SwitchHow to use the test run setting U1, T1 Types Alarm Misoperation Alarm IndicatorsCause of Trouble LampIf Wall mounted Fixed Position 107 Excessive load on To avoid placing anEquipment, use this Function only whenBright Cause of Trouble Timer StandbyWill damage the equipment Wiring procedureGroup control using 2 signal receiving units Wiring System Diagram for Group ControlSetting method Test Run Procedure Wall mounted Type K1 Type Wireless remote controller transmitterCheck Items Before the Test Run Test run Using the controller For S-26PK1U6 IndicatorController Test OFF Precautions26PK1U6 Nos , 2 OFF, No onNos , 2, 3 all OFF Diagnosis Table CauseIndoor unit HOW to Install the Timer Wired Remote Controller Tube diameter Tightening torque Tube thickness Never grasp the drain or refrigerant connecting Precautions for Packed Valve OperationInsulating the Refrigerant Tubing Tubing Insulation Tubes arranged togetherTaping the Tubes Finishing the InstallationAir Purging with a Vacuum Pump for Test Run Preparation Manifold gauge Vacuum pumpLeak Test Evacuation Use a cylinder specificallyDesigned for use with R410A Charging Additional Refrigerant Finishing the JobR410A Processes and Functions Processes and functions Room Temperature Control Chart Summary and ExplanationsCooling Processes and functions Heating Cold Draft Prevention Heating Cycle Automatic Fan Speed Indoor Unit Chart Explanations and notesCurrent release control Discharge temperature release controlOutdoor unit fan control Coil heating controlOvercurrent protection control Freeze prevention low-temperature release controlCurrent release value shift control Heating high-load controlDefrost control Outdoor Unit Control PCB Outdoor Unit Control PCB CR-CH4272R Example of wiring Method of System Address SettingPage Electrical Data Indoor Units Page Electrical data Wall Mounted Type S-26PK1U6 Electrical data Wall Mounted Type S-26PK1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Page Page Outdoor Units Outdoor Units 26PS1U6 Outdoor Units 36PE1U6 Outdoor Units 36PS1U6 Outdoor Units 42PE1U6 Outdoor Units 42PS1U6 Outdoor Units Page Service Procedures Contents of remote controller switch alarm display Service procedures Meaning of Alarm MessagesWireless Remarks Contents Correction Remote Alarm Judgment condition Clear conditionAlarm Eeprom Service procedures Details of Alarm Messages Alarm P29MDC trouble HIC PCB trouble Alarm P26HIC-CH4872R HIC-CH2672R Alarm E3126, 36 Type Communications Trouble within unitAlarm P22 Alarms F04, F06, F07, F08, F12 Check procedure Sensor Temperature Correlation TableSensor installation Sensor type Location Outdoor Air Temp. TO, Intake Temp. TS, Heat Check PinExchanger Temp. C1 Sensor, Heat Exchanger Temp. C2 Sensor Discharge Temp. TD SensorsOutdoor Unit Maintenance Remote Control Outdoor unit maintenance remote control Overview Switching between cooling/heating Operation All units start/stop OperationAll units test run Operation Sample displays Item code Display contentsDisplay for unit Nos Item code Meaning of Code Display of first 3 digits Display of last 3 digits Item code Parameter List of Item CodesOutdoor unit maintenance remote control Figures represent the capacity data for each model Test RUN Test run Preparing for Test RunTest run U1, K1, T1, F1 Type 6-2. Caution Items to Check Before the Test Run Cause Basic wiring diagram Test run Examples of Wiring DiagramsRemote controller crossover wiring for group control Automatic address setting using the remote controller Setting the outdoor unit system addresses2P DIP switch Rotary switch System address NoMain-sub remote controller control Connecting 2 remote controllers to control 1 indoor unitRemote controller setting mode 201201
Related manuals
Manual 112 pages 20.27 Kb

R410A specifications

Panasonic R410A is a refrigerant that has gained significant popularity in the air conditioning and refrigeration industry due to its favorable environmental properties and performance characteristics. Specifically designed to replace the harmful R22 refrigerant, which is being phased out due to its ozone-depleting potential, R410A offers a more eco-friendly alternative without compromising on efficiency or power.

One of the main features of R410A is its high energy efficiency. It operates at a higher pressure than R22, resulting in better heat transfer capabilities. This increased efficiency translates to lower energy consumption, making units using R410A more cost-effective in the long run. Additionally, R410A is known for its ability to provide excellent cooling performance even in high-temperature environments, making it suitable for a variety of applications, from residential air conditioning systems to commercial refrigeration units.

In terms of composition, R410A is a blend of two hydrofluorocarbons (HFCs), namely R32 and R125. This combination not only minimizes ozone depletion potential (ODP) but also reduces global warming potential (GWP) compared to older refrigerants. Panasonic has emphasized the importance of innovative technologies in its products, and R410A aligns perfectly with the company's commitment to developing sustainable solutions.

Panasonic also integrates advanced technologies to optimize the performance of R410A systems. For example, variable speed compressors, known as inverter technology, enhance system efficiency by adjusting the compressor's speed according to the cooling demand. This ensures that energy is only consumed when needed, further reducing operational costs.

Furthermore, R410A has a wide range of applications, including air conditioning systems, heat pumps, and chillers. Its versatility makes it a popular choice among manufacturers and consumers alike. The refrigerant is also compatible with existing R22 equipment, although specific retrofit procedures must be followed to ensure peak performance and reliability.

In conclusion, Panasonic R410A stands out as an innovative refrigerant choice in the HVAC industry, offering a combination of energy efficiency, environmentally friendly properties, and advanced technologies. As regulatory frameworks continue to tighten on greenhouse gas emissions, R410A and similar refrigerants are expected to play a crucial role in shaping a more sustainable future for air conditioning and refrigeration. Its high performance and lower environmental impact solidify its position as a leading refrigerant in contemporary cooling solutions.