Panasonic R410A Specifications Increasing the Fan Speed, Indoor Fan Performance Type

Page 62

1. Specifications

1-9 Increasing the Fan Speed

Electrical component box

If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure:

(1)Remove 4 screws on the electrical component box and remove the cover plate.

(2)Disconnect the fan motor sockets in the box.

(3)Take out the jumper cable (sockets at both ends) clamped in the box.

(4)Securely connect the jumper cable sockets

between the disconnected fan motor sockets in step 2.

(5)Place the cable neatly in the box and reinstall the cover plate.

1

Indoor Fan Performance

 

26 Type

36 Type

Fan motor

Jumper cable

Fan motor socket

(At shipment)

Jumper cable

(Jumper cable installed)

2159_M_I

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Pa)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(inAq)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(inAq)

 

 

 

 

line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

line

 

 

 

 

 

 

 

 

150

 

 

Limit

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PressureStaticExternal

(Pa)

Limit

 

 

 

 

 

 

 

 

0.5

PressureStaticExternal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

0.4

 

100

 

 

 

 

line

 

 

 

 

 

 

 

 

0.4

 

 

line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit

 

 

 

 

 

 

 

 

 

 

0.3

 

 

 

 

 

 

 

 

 

 

0.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

0.2

 

50

 

 

 

 

 

 

 

 

 

 

 

HT

 

 

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

H

 

 

 

 

 

 

 

 

 

H

 

 

 

 

0.1

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

0.1

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

0

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

500

 

700

900

 

500

 

 

 

1000

 

 

 

 

 

 

 

 

 

Air Flow (CFM)

 

 

 

 

 

 

 

 

 

Air Flow (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1982_U_I

 

 

 

 

 

 

 

 

 

 

 

 

 

1983_U_I

 

NOTE

 

 

HT

: Using the booster cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H : At shipment

How to read the diagram

The vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (CFM). The characteristic curves for “HT”, “H”, “M” and “L” fan speed control are shown.

The nameplate values are shown based on the “H” air flow. For the 26 type, the air flow is 636 CFM, while the external static pressure is 49 Pa at “H” position. If external static pressure is too great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet.

This problem may be solved by increasing the fan speed as explained above.

1-56

Image 62
Contents Model No Outdoor Units Indoor Units…In Moist or Uneven Locations For safe installation and trouble-free operation, you must…In a Room …In an Area with High WindsCheck of Density Limit Precautions for Installation Using New Refrigerant Configuration and characteristics of cylinders Contents Tentative Specifications Unit Specifications Way Cassette Type Model NoIndoor Unit 36PU1U6 Outdoor Unit 36PE1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PE1U6 Indoor Unit 26PU1U6 Outdoor Unit Indoor Unit 36PU1U6 Outdoor Unit 36PS1U6 Indoor Unit 42PU1U6 Outdoor Unit 42PS1U6 Specifications Unit Specifications Wall Mounted Type Data Subject to Change Without NoticeIndoor Unit 26PK1U6 Outdoor Unit Specifications Unit Specifications Ceiling Type PerformanceIndoor Unit 36PT1U6 Outdoor Unit Indoor Unit 42PT1U6 Outdoor Unit Indoor Unit 26PT1U6 Outdoor Unit 26PS1U6 17˚F BTU / h Moisture removal High Pints / h Indoor Unit 42PT1U6 Outdoor Unit 42PS1U6 Specifications Unit Specifications Low Silhouette Duct Type Net weight Lbs. kg 128 Shipping weight 148 Shipping volumeIndoor Unit 36PF1U6 Outdoor Unit 36PE1U6 RCZ-RTC2 CZ-RWSC1U Major Component Specifications Indoor Unit Fan motorModel No 36PU1U6 Source Model No 42PU1U6 Source Model No 26PK1U6 Source Model No 26PT1U6 Source Model No 36PT1U6 Source Model No 42PT1U6 Source Model No 26PF1U6 Source Model No 36PF1U6 Source Specifications Major Component Specifications Outdoor Unit CompressorCR-CH4872R Microprocessor Lbs. kg R410A 7.9 26PS1U6 230V, 40µF 42PS1U6 Specifications Other Component Specifications Outdoor Unit Model No 26PE1U6, U-26PS1U6Model No 36PE1U6, U-36PS1U6 Model No 42PE1U6, U-42PS1U6 Ø1/8 Hol Page 19/32 31/32 12-7/32 Dimension inch 56-25/32 Air outlet duct flange Thickness more than T1/16 inch Page Page Specifications Temperature Indoor Air Intake Outdoor Air Intake Operating RangePage Specifications Noise Criterion Curves Way Cassette Type SourceSpecifications Noise Criterion Curves Wall Mounted Type Specifications Noise Criterion Curves Ceiling Type Noise Criterion Curves Low Silhouette Duct Type SoundSpecifications Noise Criterion Curves Outdoor Units Indoor Fan Performance Type Specifications Increasing the Fan SpeedHow to read the diagram TypeModel 36, 42 Type Air throw distance chart Way Cassette TypeModel 26 Type Specifications Air throw distance chart Wall Mounted Type Model 42 Type Air throw distance chart Ceiling TypeModel 36 Type Outdoor Unit Type Time delay fuse or Circuit capacity Wiring System Diagrams How to Connect Wiring to the Terminal For stranded wiring Installation Instructions Ashrae Selecting the Installation Site Air-Discharge Chamber for Top Discharge For U-42PES1U6 unit ① Air discharge chamber ② Air discharge chamber base42PES1U6 unit DirectionFront and both sides must remain open 25-13/32 25/32 30-5/64 Wind direction Obstacle to the front of unit Installation in front-rear rows Drainage Work Installing the Outdoor UnitRouting the Tubing and Wiring Low Silhouette Ducted Type Way Cassette Type Way Cassette Type U1 Type Suspending the Indoor Unit Preparation for SuspendingPlacing the Unit Inside the Ceiling Installing the Drain Piping Checking the Drainage Before Installing the Ceiling Panel Unit bodyInstalling the Ceiling Panel When Removing the Ceiling Panel for ServicingAccessories Installing the ceiling panel Located Trical wiring or conduits areSelecting and Making a Hole Hole Dia. inchIf Block, Brick, Concrete or Similar Type Wall Installing the Rear Panel on the WallIf Wooden Wall How to replace the grille Removing the Grille to Install the Indoor UnitHow to remove the grille To mount the indoor unit on the rear panelWiring Instructions General Precautions on Wiring How to remove the cover plateInstalling the Drain Hose Shaping the TubingCeiling Type T1 Type Suspending the Indoor Unit Hinge Slide toward front side Side panel Unit Outside Duct for Fresh Air Good Not good26PF1U6 Required Minimum Space for Installation and ServiceLow Silhouette Ducted Type F1 Type 36PF1U6Extreme care in supporting Enough to support the weightIt is important that you use Indoor unit inside the ceilingTighten the hose clamps so Their locking nuts face upwardIndoor control board When you short the pin onBe careful since the fan will start To mount the tube cover, use 5/16Increasing the Fan Speed Indoor Fan PerformanceWhen Installing the Indoor Unit Checkpoint after installation Checkpoint Symptom RemarkIf Wall-mounted Fixed Position Wireless Remote Controller InstallationHow to Install Batteries Setting the Model Code Room Temperature Sensor SettingAddress Switches CZ-RWSU1U Ceiling Type T1 Type Indicator Section Installation How to use the test run setting U1, T1 Types Electrical WiringTest Run Switch Cause of Trouble Misoperation Alarm IndicatorsAlarm LampIf Wall mounted Fixed Position 107 Equipment, use this To avoid placing anExcessive load on Function only whenTimer Standby Bright Cause of TroubleWiring procedure Will damage the equipmentWiring System Diagram for Group Control Group control using 2 signal receiving unitsSetting method Check Items Before the Test Run Test Run Procedure Wall mounted Type K1 TypeWireless remote controller transmitter Controller Test run Using the controller For S-26PK1U6Indicator Precautions Test OFFNos , 2, 3 all OFF 26PK1U6Nos , 2 OFF, No on Indoor unit Diagnosis TableCause HOW to Install the Timer Wired Remote Controller Tube diameter Tightening torque Tube thickness Insulating the Refrigerant Tubing Tubing Insulation Precautions for Packed Valve OperationNever grasp the drain or refrigerant connecting Tubes arranged togetherFinishing the Installation Taping the TubesLeak Test Air Purging with a Vacuum Pump for Test Run PreparationManifold gauge Vacuum pump Designed for use with R410A EvacuationUse a cylinder specifically R410A Charging Additional RefrigerantFinishing the Job Processes and Functions Cooling Processes and functions Room Temperature ControlChart Summary and Explanations Processes and functions Heating Cold Draft Prevention Heating Cycle Chart Explanations and notes Automatic Fan Speed Indoor UnitOutdoor unit fan control Discharge temperature release controlCurrent release control Coil heating controlCurrent release value shift control Freeze prevention low-temperature release controlOvercurrent protection control Heating high-load controlDefrost control Outdoor Unit Control PCB Outdoor Unit Control PCB CR-CH4272R Method of System Address Setting Example of wiringPage Electrical Data Indoor Units Page Electrical data Wall Mounted Type S-26PK1U6 Electrical data Wall Mounted Type S-26PK1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Electrical data Ceiling Type S-26PT1U6, S-36PT1U6, S-42PT1U6 Page Page Outdoor Units Outdoor Units 26PS1U6 Outdoor Units 36PE1U6 Outdoor Units 36PS1U6 Outdoor Units 42PE1U6 Outdoor Units 42PS1U6 Outdoor Units Page Service Procedures Service procedures Meaning of Alarm Messages Contents of remote controller switch alarm displayWireless Remarks Remote Alarm Judgment condition Clear condition Contents CorrectionAlarm Eeprom MDC trouble Service procedures Details of Alarm MessagesAlarm P29 Alarm P26 HIC PCB trouble26, 36 Type Alarm E31HIC-CH4872R HIC-CH2672R Communications Trouble within unitAlarm P22 Alarms F04, F06, F07, F08, F12 Sensor installation Sensor type Location Check procedureSensor Temperature Correlation Table Exchanger Temp. C1 Sensor, Heat Exchanger Temp. C2 Sensor Check PinOutdoor Air Temp. TO, Intake Temp. TS, Heat Discharge Temp. TD SensorsOutdoor Unit Maintenance Remote Control Outdoor unit maintenance remote control Overview All units test run Operation Switching between cooling/heating OperationAll units start/stop Operation Item code Display contents Sample displaysDisplay for unit Nos Item code Meaning of Code Display of first 3 digits Display of last 3 digits List of Item Codes Item code ParameterOutdoor unit maintenance remote control Figures represent the capacity data for each model Test RUN Preparing for Test Run Test runTest run U1, K1, T1, F1 Type 6-2. Caution Items to Check Before the Test Run Cause Test run Examples of Wiring Diagrams Basic wiring diagramRemote controller crossover wiring for group control 2P DIP switch Rotary switch Setting the outdoor unit system addressesAutomatic address setting using the remote controller System address NoRemote controller setting mode Main-sub remote controller controlConnecting 2 remote controllers to control 1 indoor unit 201201
Related manuals
Manual 112 pages 20.27 Kb

R410A specifications

Panasonic R410A is a refrigerant that has gained significant popularity in the air conditioning and refrigeration industry due to its favorable environmental properties and performance characteristics. Specifically designed to replace the harmful R22 refrigerant, which is being phased out due to its ozone-depleting potential, R410A offers a more eco-friendly alternative without compromising on efficiency or power.

One of the main features of R410A is its high energy efficiency. It operates at a higher pressure than R22, resulting in better heat transfer capabilities. This increased efficiency translates to lower energy consumption, making units using R410A more cost-effective in the long run. Additionally, R410A is known for its ability to provide excellent cooling performance even in high-temperature environments, making it suitable for a variety of applications, from residential air conditioning systems to commercial refrigeration units.

In terms of composition, R410A is a blend of two hydrofluorocarbons (HFCs), namely R32 and R125. This combination not only minimizes ozone depletion potential (ODP) but also reduces global warming potential (GWP) compared to older refrigerants. Panasonic has emphasized the importance of innovative technologies in its products, and R410A aligns perfectly with the company's commitment to developing sustainable solutions.

Panasonic also integrates advanced technologies to optimize the performance of R410A systems. For example, variable speed compressors, known as inverter technology, enhance system efficiency by adjusting the compressor's speed according to the cooling demand. This ensures that energy is only consumed when needed, further reducing operational costs.

Furthermore, R410A has a wide range of applications, including air conditioning systems, heat pumps, and chillers. Its versatility makes it a popular choice among manufacturers and consumers alike. The refrigerant is also compatible with existing R22 equipment, although specific retrofit procedures must be followed to ensure peak performance and reliability.

In conclusion, Panasonic R410A stands out as an innovative refrigerant choice in the HVAC industry, offering a combination of energy efficiency, environmentally friendly properties, and advanced technologies. As regulatory frameworks continue to tighten on greenhouse gas emissions, R410A and similar refrigerants are expected to play a crucial role in shaping a more sustainable future for air conditioning and refrigeration. Its high performance and lower environmental impact solidify its position as a leading refrigerant in contemporary cooling solutions.