Trane WPVJ, WPHF manual Installation Low Voltage Wiring, Thermostat Location

Page 19

Installation

Low Voltage Wiring

Low Voltage Wiring for Field Provided Thermostats/Zone Sensors

Ensure that the AC control wiring be- tween the controls and the unit’s ter- mination point does not exceed three

(3)ohms/conductor for the length of the run.

Note: Resistance in excess of 3-ohms per conductor may cause component failure due to insufficient AC voltage supply.

Check all loads and conductors for grounds, shorts, and mis-wiring.

Use copper conductors unless other- wise specified.

Do not run the AC low voltage wiring in the same conduit with the high volt- age power wiring.

Table 3: 24V AC conductors

Distance

Recommended

from unit to Control

Wire Size

 

 

000-460 feet

18 gauge

 

 

461-732 feet

16 gauge

 

 

733-1000 feet

14 gauge

 

 

Thermostat Location

Location of the room thermostat/zone sensor cis an important element of effec- tive room control.

Areas where the thermostat or zone sensor should not be located include : be- hind doors, or corners; Near hot or cold air ducts; Near radiant heat (heat emitted from appliances or the sun); Near concealed pipes or chimneys; On outside walls or other non conditioned surfaces; In airflows from adjacent zones or other units (Figure 7).

Figure 7: Thermostat/sensor location

WSHP-SVX04A-EN

19

Image 19
Contents Later Design Sequence Installation Owner DiagnosticsResponsible Refrigerant Practices Contents Fiberglass Wool Pre-installation ChecklistMicrobial Growth General Information Improper Unit Lift Dimensions/Weights/ ClearanceDimensions Wpvj 018-024 LH Wpvj 018-024 RH Wpvj 030-042 LH Wpvj 030-042 RH Wpvj 048-072 LH Wpvj 048-072 RH Filter Installation InstallationGeneral Installation Checks Low Voltage Wiring AC & DC RequirementsWater Connection Unit Installation WpvjUnit Installation Wphf Using Antifreeze Connecting a Distributed Pump Kit to a Closed Loop SystemCleaning and Flushing Water Loop Control Power Transformer Field Installed Power WiringThermostat Location Installation Low Voltage WiringAmpacity Device Electrical RequirementsRLA FLA RLA CSA Case WPHF057 Pre-Start-up Checklist Pre-Start ChecklistSequence Operation Wpvj Operating PressuresOperating Pressure Flow Checks Water VolumeStart-up Checklist and Log Water Pressure DropJob Name Model Number Date Serial Number Start-up Checklist LogPreventive Maintenance MaintenanceHazardous Chemicals Warranty Information Standard Warranty Warranty InformationOperation with a Conventional Thermostat TroubleshootingHazardous Service Procedures General OperationUnit short cycles Troubleshooting ChecklistUnit Wiring Wpvj Basic 24V Diagram Unit Wiring Wpvj Tracer ZN510 Diagram Unit Wiring Wphf Basic 24V Diagram Unit Wiring Wphf Tracer ZN510 Diagram Trane