Trane WPVJ manual WPHF057

Page 24

Electrical

Requirements

Table E3: WPHF Electrical Performance (Standard Static Blower Option-continued)

 

 

Blower Motor

Blower Motor

Compr.

Compr.

Compr.

Minimum Cir-

UL Max Fuse

CSA

CASE

Model No.

Volts/Hz/Ph

HP

FLA

RLA

MCC

LRA

cuit Amps

or HACR

Max. Fuse

Max.

 

 

 

 

 

 

 

 

 

Size

Circuit Brkr

WPHF057

208/60/1

1/2

4.1

22.3

34.8

122

32.0

50

60

50

WPHF057

230/60/1

1/2

4.1

22.3

34.8

122

32.0

50

60

50

WPHF057

208/60/3

1/2

4.1

14.4

25.5

101

22.1

35

50

45

WPHF057

230/60/3

1/2

4.1

14.4

25.5

101

22.1

35

50

45

WPHF057

460/60/3

1/2

1.8

7.1

11.1

51

10.7

15

20

20

Table E4: WPHF Electrical Performance (High Static Blower Option)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor

Blower Motor

Compr.

Compr.

Compr.

Minimum Cir-

UL Max Fuse

CSA

CASE

Model No.

Volts/Hz/Ph

HP

FLA

RLA

MCC

LRA

cuit Amps

or HACR

Max. Fuse

Max.

 

 

 

 

 

 

 

 

 

Size

Circuit Brkr

WPHF047

208/60/1

1/2

4.6

14.6

22.8

92

22.9

35

50

40

WPHF047

230/60/1

1/2

4.6

14.6

22.8

92

22.9

35

50

40

WPHF047

208/60/3

1/2

4.6

10.6

16.5

101

17.9

25

50

45

WPHF047

230/60/3

1/2

4.6

10.6

16.5

101

17.9

25

50

45

WPHF047

460/60/3

1/2

2.2

4.2

6.6

51

7.5

15

25

20

WPHF057

208/60/1

1/2

4.6

22.3

34.8

122

32.5

50

60

50

WPHF057

230/60/1

1/2

4.6

22.3

34.8

122

32.5

50

60

50

WPHF057

208/60/3

1/2

4.6

14.4

22.5

101

22.6

35

50

45

WPHF057

230/60/3

1/2

4.6

14.4

22.5

101

22.6

35

50

45

WPHF057

460/60/3

1/2

2.2

7.1

11.1

51

11.1

15

25

20

24

WSHP-SVX04A-EN

Image 24
Contents Installation Owner Diagnostics Later Design SequenceResponsible Refrigerant Practices Contents Pre-installation Checklist Fiberglass WoolMicrobial Growth General Information Dimensions/Weights/ Clearance Improper Unit LiftDimensions Wpvj 018-024 LH Wpvj 018-024 RH Wpvj 030-042 LH Wpvj 030-042 RH Wpvj 048-072 LH Wpvj 048-072 RH Installation General Installation ChecksLow Voltage Wiring AC & DC Requirements Filter InstallationUnit Installation Wpvj Water ConnectionUnit Installation Wphf Connecting a Distributed Pump Kit to a Closed Loop System Using AntifreezeCleaning and Flushing Water Loop Field Installed Power Wiring Control Power TransformerInstallation Low Voltage Wiring Thermostat LocationElectrical Requirements Ampacity DeviceRLA FLA RLA CSA Case WPHF057 Pre-Start Checklist Pre-Start-up ChecklistSequence Operation Operating Pressures WpvjOperating Pressure Water Volume Start-up Checklist and LogWater Pressure Drop Flow ChecksStart-up Checklist Log Job Name Model Number Date Serial NumberMaintenance Preventive MaintenanceHazardous Chemicals Warranty Information Warranty Information Standard WarrantyTroubleshooting Hazardous Service ProceduresGeneral Operation Operation with a Conventional ThermostatTroubleshooting Checklist Unit short cyclesUnit Wiring Wpvj Basic 24V Diagram Unit Wiring Wpvj Tracer ZN510 Diagram Unit Wiring Wphf Basic 24V Diagram Unit Wiring Wphf Tracer ZN510 Diagram Trane