Panasonic CU-4KE31NBU, CS-MKE9NB4U How to Install the Indoor Unit, Preparation for Suspending

Page 85

3. How to Install the Indoor Unit

3-1. Preparation for Suspending

This unit uses a drain pump. Use a carpenter’s level to check that the unit is level.

3-2. Suspending the Indoor Unit

(1)Fix the suspension bolts securely in the ceiling using the method shown in the diagrams, by attaching them to the ceiling support structure, or by any other method that ensures that the unit will be securely and safely suspended. (Fig. 6-1)

(2)Follow the diagram to make the holes in the ceiling.

(3)Determine the pitch of the suspension bolts using the supplied full-scale installation diagram. The dia- gram shows the relationship between the positions of the suspension fitting, unit, and panel. (Fig. 6-2)

3-3. Placing the Unit Inside the Ceiling

(1)

Be sure to remove the fan protection (4pcs) for

 

transportation before hanging up the indoor unit.

(2)

When placing the unit inside the ceiling, determine

 

the pitch of the suspension bolts using the supplied

 

full-scale installation diagram. (Fig. 6-3)

 

Tubing and wiring must be laid inside the ceiling

 

when suspending the unit. If the ceiling is already

 

constructed, lay the tubing and wiring into position

Hole-in-anchor

Concrete

Insert

Hole-in-plug

Suspension bolt (M10 or 3/8") (locally purchased)

Fig. 6-1

23-5/8"(600mm)

Ceiling opening dimensions

21-1/32"(534mm)

Suspension bolt pitch

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling opening dimensions

 

 

21-1/32"(534mm)

Suspension bolt pitch

23-5/8"(600mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22-5/8"(575mm)

Drain tube

 

 

 

 

 

 

 

 

 

 

 

2-3/32"

6-5/16"

6-11/16"

connection port

 

 

 

(outer dia

1-1/32"(

26mm))

 

 

(53mm)

(160mm)

(170mm)

1-25/32"

 

 

 

 

 

(45mm)

 

 

 

8-15/32" (215mm)

11-5/32"(283mm)

 

 

4-19/32"

(117mm)

1-25/32" (45mm)

 

 

 

1-3/16"

(30mm)

 

 

for connection to the unit before placing the unit

 

inside the ceiling.

(3)

The length of suspension bolts must be appropriate

 

for a distance between the bottom of the bolt and the

 

bottom of the unit of more than 19/32" (15 mm) as

 

shown in the diagram. (Fig. 6-3)

(4)

Thread the 3 hexagonal nuts (locally purchased) and

 

2 supplied washers onto each of the 4 suspension

 

bolts as shown in the diagram. Use 1 nut and 1

Power supply port

Over 19/32" (15mm)

Refrigerant tubing joint (narrow tube side)

1/4( 6.35mm) (flared)

Fig. 6-2

1/2" – 23/32" (13~18mm)

washer for the upper side, and 2 nuts and 1 washer

for the lower side, so that the unit will not fall off the

suspension lugs. (Fig. 6-4)

(5) Adjust so that the distance between the unit and the

ceiling bottom is 1/2" (13 mm) to 23/32" (18 mm).

Tighten the nuts on the upper side and lower side of

the suspension lug. (Fig. 6-4)

Supplied screw

Full-scale installation diagram

(printed on top of container box)

 

 

 

Fig. 6-3

 

 

 

 

 

 

 

 

 

 

 

Suspension bolt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nuts and washers

 

 

 

 

 

 

 

 

 

 

 

Suspension lug

(used for upper and lower)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Double nut

Notch

1/2" – 23/32"

(13~18mm)

Fig. 6-4

7

Image 85
Contents 17,500BTU / h 11,900BTU / hSafety Precautions Prohibit Table of Contents CZ-RD515U Applicable MULTI-OUTDOOR Units Operating Range Temperature Indoor Air Intake Temp Outdoor Air Intake TempUnit Specifications SpecificationsIndoor Unit CS-MKE9NB4U & CZ-18BT1U 208V Indoor UnitIndoor Unit CS-MKE12NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U Indoor Unit CS-KE18NB4UW & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U Indoor Unit Major Component SpecificationsIndoor Unit Body CS-MKE9NB4U Indoor Unit Panel CZ-18BT1UCB-CS-MKE12NB4U Indoor Unit Body CS-MKE12NB4UCB-CS-KE18NB4U Indoor Unit Body CS-KE18NB4UWCS-MKE12NB4U & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U Other Component SpecificationsView Dimensional DataIndoor Unit CS-KE18NB4UW & CZ-18BT1U Indoor unit Refrigerant Flow DiagramElectrical Data Electric Wiring DiagramsDisassembly Procedure MaintenanceDisconnect the connectors in the control box Remove the air intake grillRemove the ceiling panel Remove the power box and control box Remove the indoor air temperature sensorScrew Ground cable CN07 CN03 CN09 CN06 Remove the main body lower section Remove the heat exchanger sensor Remove the drain pump and float switchRemove the heat exchanger Remove the turbo fan and fan motorOperation Functions FunctionsEmergency operation Auto cooling/heating operationLamp colors Timer backupOverload prevention during heating Protective FunctionsFreeze prevention Cold-air prevention during heatingPrecautions before Performing Inspection or Repair Troubleshooting Before Calling for ServiceMethod of Self-Diagnostics Indoor Unit Self-diagnostics LampsChecking the Indoor and Outdoor Units Using the TEST/T-RUN terminalsReplace the controller Replace the circuit board or the fuseOff Blinking Illuminated Serial Communication Error Identification ProcedureBefore the Operation Condition E01From the previous page a Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorNoise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Locations most susceptible to noise Trouble CorrectionPage CS-MKE9NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U Appendix aModel No Indoor Units CZ-18BT1UCeiling Panel Contents FeaturesSafety Precautions Product InformationSafety Instructions Installation LocationElectrical Requirements AvoidUnit Display and Operation Button Names of PartsSymbols Remote Controller DisplayRemote Controller Temperature setting buttons Temp HR. Timer button 1-HOUR OFF TimerMode selector button SensorSingle/Multiple switch Using the Remote ControllerAutomatic Operation Operation with the Remote ControllerManual Operation StepNight Setback Mode Adjusting the Fan SpeedHigh Power Mode Special Remarks Setting the TimerHow to set the on time How to set the OFF timeHow to set daily ON/OFF repeat timer 1030 pm 710 am 1100 am Present timeAdjusting the Airflow Direction Using the 1-HOUR OFF TimerHour OFF Timer Operation together with the daily ON/OFF repeat timerWhen the air conditioner is not running Care and CleaningCleaning the flaps Cleaning the main unit and Remote ControllerHow to remove the air intake grille How to remove the filterAir filter Care After a prolonged idle periodWired Remote Controller TroubleshootingOperating Range Model No Indoor Unit SpecificationsModel No Outdoor Unit Model No Ceiling PanelCS-KE18NB4UW & CZ-18BT1U Appendix BCU-KE12NK1 CS-KE12NB41CS-KE18NB4UW CU-KE18NKU CZ-18BT1UFan Only Installation Location DRY orange, Cool green and FAN green Remote Controller Display Remote Controller FAN Using the Remote Controller Operation with the Remote Controller Fan Only Special Remarks How to set the OFF time Sweep Cool Drysweep FAN Heat Care and Cleaning Air filter Max Min For Single use For Multiple Use Model No Outdoor Unit Indoor Unit For Single useCS-KE12NB41 Model No Ceiling Panel CZ-18BT1UFor Multiple use Page 852-6-4190-585-00-1 For Indoor Unit ContentsPlease Read Before Starting Others When ServicingAccessories Supplied with Unit Table Tools Required for Installation not suppliedGeneral Optional Copper Tubing KitAdditional Materials Required for Installation Installation Site SelectionIndoor Unit  direct sunlightEmbedding the Tubing and Wiring Preparation for Suspending How to Install the Indoor UnitSuspending the Indoor Unit Placing the Unit Inside the Ceiling Attach so that the hose band Installing the Drain PipingFastener is on the side Drain port10a Checking the DrainageIndoor unit Gaps Ceiling surface Ceiling panel Installing the Ceiling PanelAttaching the air-intake grille Wiring the Ceiling Panel and the IndicatorWhen Removing the Ceiling Panel for Servicing Checking After InstallationAdjusting the Auto Flap Wiring Instructions General precautions on wiringFor Outdoor Unit  For solid core wiring or F-cable How to connect wiring to the terminal For Indoor Unit For stranded wiring How to Test Run the Air Conditioner Rear side Remote control holder Remote Controller Installation PositionTo take out the remote controller, pull it forward Mounting on a WallAddress Setting of the Remote Controller Address SwitchInstallation Check Sheet Connecting a Home Automation DeviceCZ-RD515U Appendix DModel No. CZ-RD515U Operating Instructions Wired Remote ControllerAutomatic Switching between Cooling and Heating Installation Location SET button Timer and Present Time setting buttonsTimer Select button Remote Controller Display Automatic Operation Only for COOL/DRY/HEAT Model Heating Mode Only for COOL/DRY/HEAT Model Remote Controller DisplayProgrammed Backup functionDaily on / OFF 910 pm 710 am 1130 pm Present timeUsing the 1-HOUR OFF Timer Page Appendix E Installation Instructions CZ-RD515U Remote controller installation guidelines Parts supplied with the remote controllerHow to install the remote controller Installation locationInstalling directly onto the wall Installing with in-wall junction boxHow to wire the remote controller WI1011-0 Page DC1111-0
Related manuals
Manual 69 pages 14.27 Kb Manual 132 pages 33 Kb Manual 124 pages 42.9 Kb Manual 56 pages 332 b

CZ-18BT1U, CS-KE18NB4UW, CS-MKE12NB4U, CU-3KE19NBU, CU-4KE24NBU specifications

The Panasonic CS-KE18NB4UW and CU-KE12NK1, along with the CS-KE12NB41, CZ-18BT1U, and CU-KE18NKU, represent a suite of advanced air conditioning solutions built with cutting-edge technologies designed to provide optimal comfort, energy efficiency, and air quality in various settings.

One of the standout features of this lineup is the inverter technology. Inverter air conditioners adjust the compressor speed to maintain the desired temperature efficiently. This leads to significant energy savings compared to traditional air conditioners, which tend to frequently cycle on and off, consuming more power. By continuously regulating the temperature, the Panasonic units not only save electricity but also prolong the lifespan of the compressor.

Another noteworthy characteristic is the nanoe™ technology integrated into some of these models. Nanoe™ technology uses hydroxyl radicals to purify the air, minimizing harmful bacteria and allergens. This makes the Panasonic units particularly suitable for users with allergies or respiratory issues, providing a cleaner and healthier indoor environment.

In terms of design, these models are sleek and compact, allowing them to fit seamlessly into any room decor, whether in a home, office, or commercial space. The quiet operation is another advantage, making them ideal for bedrooms and study areas where minimal noise is essential.

Furthermore, the CS-KE18NB4UW and CU-KE12NK1 offer a range of powerful cooling and heating capacities, making them versatile solutions for various climate conditions. The cold climate performance ensures consistent heating in colder regions, while the robust cooling capabilities make them perfect for hot summer months.

The user-friendly features include a smart remote control system, allowing users to adjust settings with ease from a distance. Some models are equipped with Wi-Fi capability, enabling integration with smart home systems for enhanced control and programmability.

In conclusion, the Panasonic CS-KE18NB4UW, CU-KE12NK1, CS-KE12NB41, CZ-18BT1U, and CU-KE18NKU air conditioning units exemplify innovation and efficiency. With their inverter technology, air purification features, compact designs, and smart functionalities, they stand out as ideal choices for maintaining comfortable and healthy indoor environments throughout the year.